Cfb boiler basic design, operation and maintenance

97,666 views 179 slides Apr 21, 2013
Slide 1
Slide 1 of 179
Slide 1
1
Slide 2
2
Slide 3
3
Slide 4
4
Slide 5
5
Slide 6
6
Slide 7
7
Slide 8
8
Slide 9
9
Slide 10
10
Slide 11
11
Slide 12
12
Slide 13
13
Slide 14
14
Slide 15
15
Slide 16
16
Slide 17
17
Slide 18
18
Slide 19
19
Slide 20
20
Slide 21
21
Slide 22
22
Slide 23
23
Slide 24
24
Slide 25
25
Slide 26
26
Slide 27
27
Slide 28
28
Slide 29
29
Slide 30
30
Slide 31
31
Slide 32
32
Slide 33
33
Slide 34
34
Slide 35
35
Slide 36
36
Slide 37
37
Slide 38
38
Slide 39
39
Slide 40
40
Slide 41
41
Slide 42
42
Slide 43
43
Slide 44
44
Slide 45
45
Slide 46
46
Slide 47
47
Slide 48
48
Slide 49
49
Slide 50
50
Slide 51
51
Slide 52
52
Slide 53
53
Slide 54
54
Slide 55
55
Slide 56
56
Slide 57
57
Slide 58
58
Slide 59
59
Slide 60
60
Slide 61
61
Slide 62
62
Slide 63
63
Slide 64
64
Slide 65
65
Slide 66
66
Slide 67
67
Slide 68
68
Slide 69
69
Slide 70
70
Slide 71
71
Slide 72
72
Slide 73
73
Slide 74
74
Slide 75
75
Slide 76
76
Slide 77
77
Slide 78
78
Slide 79
79
Slide 80
80
Slide 81
81
Slide 82
82
Slide 83
83
Slide 84
84
Slide 85
85
Slide 86
86
Slide 87
87
Slide 88
88
Slide 89
89
Slide 90
90
Slide 91
91
Slide 92
92
Slide 93
93
Slide 94
94
Slide 95
95
Slide 96
96
Slide 97
97
Slide 98
98
Slide 99
99
Slide 100
100
Slide 101
101
Slide 102
102
Slide 103
103
Slide 104
104
Slide 105
105
Slide 106
106
Slide 107
107
Slide 108
108
Slide 109
109
Slide 110
110
Slide 111
111
Slide 112
112
Slide 113
113
Slide 114
114
Slide 115
115
Slide 116
116
Slide 117
117
Slide 118
118
Slide 119
119
Slide 120
120
Slide 121
121
Slide 122
122
Slide 123
123
Slide 124
124
Slide 125
125
Slide 126
126
Slide 127
127
Slide 128
128
Slide 129
129
Slide 130
130
Slide 131
131
Slide 132
132
Slide 133
133
Slide 134
134
Slide 135
135
Slide 136
136
Slide 137
137
Slide 138
138
Slide 139
139
Slide 140
140
Slide 141
141
Slide 142
142
Slide 143
143
Slide 144
144
Slide 145
145
Slide 146
146
Slide 147
147
Slide 148
148
Slide 149
149
Slide 150
150
Slide 151
151
Slide 152
152
Slide 153
153
Slide 154
154
Slide 155
155
Slide 156
156
Slide 157
157
Slide 158
158
Slide 159
159
Slide 160
160
Slide 161
161
Slide 162
162
Slide 163
163
Slide 164
164
Slide 165
165
Slide 166
166
Slide 167
167
Slide 168
168
Slide 169
169
Slide 170
170
Slide 171
171
Slide 172
172
Slide 173
173
Slide 174
174
Slide 175
175
Slide 176
176
Slide 177
177
Slide 178
178
Slide 179
179

About This Presentation

This material provides the basic of design, operation and maintenance so that you can use this as guide line to operation, to inspect your boiler. Hope this will be benefit you.


Slide Content

1
CFB Boiler Design, Operation and
Maintenance
By Pichai Chaibamrung

2
Content Day1
1. Introduction to CFB
2. Hydrodynamic of CFB
3. Combustion in CFB
4. Heat Transfer in CFB
5. Basic design of CFB
6. Operation
7. Maintenance
8. Basic Boiler Safety
9. Basic CFB control

3
Objective

To understand the typical arrangement in CFB

To understand the basic hydrodynamic of CFB

To understand the basic combustion in CFB

To understand the basic heat transfer in CFB

To understand basic design of CFB

To understand theory of cyclone separator
Know Principle Solve Everything

4
1. Introduction to CFB
1.1 Development of CFB
1.2 Typical equipment of CFB
1.3 Advantage of CFB

5
1.1 Development of CFB

1921, Fritz Winkler, Germany, Coal Gasification

1938, WarenLewis and Edwin Gilliland, USA, Fluid Catalytic Cracking,
Fast Fluidized Bed

1960, Douglas Elliott, England, Coal Combustion, BFB

1960s, Ahlstrom Group, Finland, First commercial CFB boiler, 15
MW
th
, Peat

6
1.2 Typical Component of CFB Boiler

7
1.2 Typical Component of CFB Boiler
Wind box and grid nozzle
primary air is fed into wind box.
Air is equally distributed on
furnace cross section by passing
through the grid nozzle. This will
help mixing of air and fuel for
completed combustion

8
1.2 Typical Component of CFB Boiler
Bottom ash drain
coarse size of ash that is not
take away from furnace by
fluidizing air will be drain
at bottom ash drain port
locating on grid nozzle
floor by gravity.
bottom ash will be cooled
and conveyed to silo by
cooling conveyor.

9
1.2 Typical Component of CFB Boiler
HP Blower
supply high pressure air to
fluidize bed material in loop
seal so that it can overflow to
furnace
Rotameter
Supplying of HP
blower to loop seal

10
1.2 Typical Component of CFB Boiler
Cyclone separator
located after furnace exit and
before convective part.
use to provide circulation by
trapping coarse particle back to
the furnace
Fluidized boiler without this
would be BFB not CFB

11
1.2 Typical Component of CFB Boiler
Evaporative or Superheat Wing Wall
located on upper zone of furnace
it can be both of evaporative or SH
panel
lower portion covered by erosion
resistant materials

12
1.2 Typical Component of CFB Boiler
Fuel Feeding system
solid fuel is fed into the lower
zone of furnace through the
screw conveyor cooling with
combustion air. Number of
feeding port depend on the
size of boiler

13
1.2 Typical Component of CFB Boiler
Refractory
refractory is used to protect
the pressure part from
serious erosion zone such as
lower bed, cyclone separator

14
1.2 Typical Component of CFB Boiler
Solid recycle system (Loop seal)
loop seal is located between
dip leg of separator and
furnace. Its design physical is
similar to furnace which have
air box and nozzle to
distribute air. Distributed air
from HP blower initiate
fluidization. Solid behave like
a fluid then over flow back to
the furnace.

15
1.2 Typical Component of CFB Boiler
Kick out
kick out is referred to
interface zone between
the end of lower zone
refractory and water tube.
It is design to protect the
erosion by by-passing the
interface from falling
down bed materials

16
1.2 Typical Component of CFB Boiler
Lime stone and sand system
lime stone is pneumatically feed or gravitational feed into
the furnace slightly above fuel feed port. the objective is to
reduce SOxemission.
Sand is normally fed by gravitation from silo in order to
maintain bed pressure. Its flow control by speed of rotary
screw.

17
1.2 Typical Arrangement of CFB Boiler

18
1.3 Advantage of CFB Boiler

Fuel Flexibility

19
1.3 Advantage of CFB Boiler

High Combustion Efficiency
-Good solid mixing
-Low unburned loss by cyclone, fly ash recirculation
-Long combustion zone

In situ sulfur removal

Low nitrogen oxide emission

20
2. Hydrodynamic in CFB
2.1 Regimes of Fluidization
2.2 Fast Fluidized Bed
2.3 Hydrodynamic Regimes in CFB
2.4 Hydrodynamic Structure of Fast Beds

21
2.1 Regimes of Fluidization

Fluidization is defined as the operation through which fine
solid are transformed into a fluid like state through
contact with a gas or liquid.

22
2.1 Regimes of Fluidization

Particle Classification
<130
<180
<250
<600
CFB1
Size (micron)
<590<25025%
>420>100100%
<840<45050%
75%
100%
Distribution
<1190<550
<1680<1000
BFBCFB2

23
2.1 Regimes of Fluidization

Particle Classification

24
2.1 Regimes of Fluidization

Comparison of Principal Gas-Solid Contacting Processes

25
2.1 Regimes of Fluidization

Packed Bed
The pressure drop per unit height of a packed beds of a uniformly size
particles is correlated as (Ergun,1952)
Where U is gas flow rate per unit cross section of the bed called
Superficial Gas Velocity

26
2.1 Regimes of Fluidization

Bubbling Fluidization Beds
Minimum fluidization velocity is velocity where the fluid
drag is equal to a particle’s weight less its buoyancy.

27
2.1 Regimes of Fluidization

Bubbling Fluidization Beds
For B and D particle, the bubble is started when superficial
gas is higher than minimum fluidization velocity
But for group A particle the bubble is started when
superficial velocity is higher than minimum bubbling
velocity

28
2.1 Regimes of Fluidization

Turbulent Beds
when the superficial is continually increased through a
bubbling fluidization bed, the bed start expanding, then
the new regime called turbulent bed is started.

29
2.1 Regimes of Fluidization

30
2.1 Regimes of Fluidization

Terminal Velocity
Terminal velocity is the particle velocity when the
forces acting on particle is equilibrium

31
2.1 Regimes of Fluidization

Freeboard and Furnace Height
- considered for design heating-surface area
- considered for design furnace height
- to minimize unburned carbon in bubbling
bed
- the freeboard heights should be exceed or
closed to the transport disengaging heights

32
2.2 Fast Fluidization

Definition

33
2.2 Fast Fluidization

Characteristics of Fast Beds
- non-uniform suspension of slender particle agglomerates or clusters moving
up and down in a dilute
- excellent mixing are major characteristic
- low feed rate, particles are uniformly dispersed in gas stream
- high feed rate, particles enter the wake of the other, fluid drag on the leading
particle decrease, fall under the gravity until it drops on to trailing particle

34
2.3 Hydrodynamic regimes in a CFB
Lower Furnace below SA:
Turbulent or bubbling
fluidized bed
Furnace Upper SA:
Fast Fluidized Bed
Cyclone Separator :
Swirl Flow
Return leg and lift leg :
Pack bed and Bubbling Bed
Back Pass:
Pneumatic Transport

35
2.4 Hydrodynamic Structure of Fast Beds

Axial VoidageProfile
Bed Density Profile of 135 MWe CFB Boiler (Zhang et al., 2005)
Secondary air is fed

36
2.4 Hydrodynamic Structure of Fast Beds

Velocity Profile in Fast Fluidized Bed

37
2.4 Hydrodynamic Structure of Fast Beds

Velocity Profile in Fast Fluidized Bed

38
2.4 Hydrodynamic Structure of Fast Beds

Particle Distribution Profile in Fast Fluidized Bed

39
2.4 Hydrodynamic Structure of Fast Beds

Particle Distribution Profile in Fast Fluidized Bed

40
2.4 Hydrodynamic Structure of Fast Beds

Particle Distribution Profile in Fast Fluidized Bed
Effect of SA injection on particle
distribution by M.Koksal and
F.Hamdullahpur (2004). The
experimental CFB is pilot scale CFB.
There are three orientations of SA
injection; radial, tangential, and mixed

41
2.4 Hydrodynamic Structure of Fast Beds

Particle Distribution Profile in Fast Fluidized Bed
No SA, the suspension
density is proportional
l to solid circulation rate
With SA 20% of PA,
the solid particle is hold up
when compare to no SA
Increasing SA to 40%
does not significant on
suspension density above
SA injection point
but the low zone is
denser than low SA ratio
Increasing solid circulation
rate effect to both
lower and upper zone
of SA injection point
which both zone is
denser than low
solid circulation rate

42
2.4 Hydrodynamic Structure of Fast Beds

Effects of Circulation Rate on VoidageProfile
higher solid recirculation rate

43
2.4 Hydrodynamic Structure of Fast Beds

Effects of Circulation Rate on VoidageProfile
higher solid recirculation rate
Pressure drop across the L-valve is
proportional to solid recirculation rate

44
2.4 Hydrodynamic Structure of Fast Beds

Effect of Particle Size on Suspension Density Profile
-Fine particle --> higher suspension density
-Higher suspension density --> higher heat transfer
-Higher suspension density --> lower bed temperature

45
2.4 Hydrodynamic Structure of Fast Beds

Core-Annulus Model
-the furnace may be spilt into two zones : core and
annulus
Core
-
Velocity is above superficial velocity
-
Solid move upward
Annulus
-
Velocity is low to negative
-
Solids move downward
core
annulus

46
2.4 Hydrodynamic Structure of Fast Beds

Core-Annulus Model
core
annulus

47
2.4 Hydrodynamic Structure of Fast Beds

Core Annulus Model
-the up-and-down movement solids in the core and
annulus sets up an internal circulation
-the uniform bed temperature is a direct result of internal
circulation

48
3. Combustion in CFB
3.1 Coal properties for CFB boiler
3.2 Stage of Combustion
3.3 Factor Affecting Combustion Efficiency
3.4 Combustion in CFB
3.5 Biomass Combustion

49
3.1 Coal properties for CFB Boiler
Properties
- coarse size coal shall be crushed by coal crusher
- sizing is an importance parameter for CFB boiler improper size might
result in combustion loss
- normal size shall be < 8 mm

50
3.2 Stage of Combustion
A particle of solid fuel is injected into an FB undergoes the
following sequence of events:
- Heating and drying
- Devolatilizationand volatile combustion
- Swelling and primary fragmentation (for some types of coal)
- Combustion of char with secondary fragmentation and attrition

51
3.2 Stages of Combustion

Heating and Drying
-Combustible materials constitutes around 0.5-5.0% by
weight
of total solids in combustor
-Rate of heating 100 °C/sec –1000 °C/sec
-Heat transfer to a fuel particle (Halder1989)

52
3.2 Stages of Combustion
Devolatilizationand volatile combustion
- first steady release 500-600 C
- second release 800-1000C
- slowest species is CO (Keairns et al., 1984)
- 3 mm coal take 14 sec to devolatilze
at 850 C (Basu and Fraser, 1991)

53
3.2 Stages of Combustion

Char Combustion
2 step of char combustion
1. transportation of oxygen to carbon surface
2. Reaction of carbon with oxygen on the carbon surface
3 regimes of char combustion
- Regime I: mass transfer is higher than kinetic rate
- Regime II: mass transfer is comparable to kinetic rate
- Regime III: mass transfer is very slow compared to kinetic rate

54
3.2 Stage of Combustion

CommunitionPhenomena During Combustion
Volatile release cause the
particle swell
Volatile release in non-porous
particle cause the high
internal pressure result in
break a coal particle into
fragmentation
Char burn under regime I, II,
the pores increases in size à
weak bridge connection of
carbon until it can’t withstand
the hydrodynamic force. It will
fragment again call “
secondary fragmentation”
Attrition, Fine particles from
coarse particles through
mechanical contract like
abrasion with other particles
Char burn under regime I
which is mass transfer is
higher than kinetic trasfer.
The sudden collapse or other
type of second fragmentation
call percolative fragmentation
occurs

55
3.3 Factor Affecting Combustion Efficiency

Fuel Characteristics
the lower ratio of FC/VM result in higher combustion
efficiency (Makansi, 1990), (Yoshioka and Ikeda,1990),
(Oka, 2004) but the improper mixing could result in lower
combustion efficiency due to prompting escape of volatile
gas from furnace.

56
3.3 Factor Affecting Combustion Efficiency

Operating condition (Bed Temperature)
-higher combustion temperature ---> high combustion
efficiency
High combustion temperature result in high
oxidation reaction, then burn out time
decrease. So the combustion efficiency
increase.
Limit of Bed temp
-Sulfur capture
-Bed melting
-Water tube failure

57
3.3 Factor Affecting Combustion Efficiency

Fuel Characteristic (Particle size)
-The effect of this particle size is not clear
-Fine particle, low burn out time but the
probability to be dispersed from cyclone
the high
-Coarse size, need long time to burn out.
-Both increases and decreases are
possible when particle size decrease

58
3.3 Factor Affecting Combustion Efficiency

Operating condition (superficial velocity)
- high fluidizing velocity decrease combustion efficiency because
Increasing probability of small char particle be elutriated from
circulation loop
- low fluidizing velocity cause defluidization, hot spot and sintering

59
3.3 Factor Affecting Combustion Efficiency

Operating condition (excess air)
-combustion efficiency improve which excess air < 20%
Excess air >20% less
significant improve
combustion efficiency.
Combustion loss
decrease
significantly when
excess air < 20%.

60
3.3 Factor Affecting Combustion Efficiency
Operating Condition
The highest loss of combustion result from elutriation of char particle
from circulation loop. Especially, low reactive coal size smaller than 1
mm it can not achieve complete combustion efficiency with out fly
ash recirculation system.
However, the significant efficiency improve is in range 0.0-2.0 fly ash
recirculation ratio.

61
3.4 Combustion in CFB Boiler

Lower Zone Properties
-This zone is fluidized by primary air constituting about
40-80% of total air.
-This zone receives fresh coal from coal feeder and
unburned coal from cyclone though return valve
-Oxygen deficient zone, lined with refractory to protect
corrosion
-Denser than upper zone

62
3.4 Combustion in CFB Boiler

Upper Zone Properties
-Secondary is added at interface between lower and upper
zone
-Oxygen-rich zone
-Most of char combustion occurs
-Char particle could make many trips around the furnace
before they are finally entrained out through the top of
furnace

63
3.4 Combustion in CFB Boiler

Cyclone Zone Properties
-Normally, the combustion is small when compare to in
furnace
-Some boiler may experience the strong combustion in
this zone which can be observe by rising temperature in
the cyclone exit and loop seal

64
3.5 Biomass Combustion

Fuel Characteristics
- high volatile content (60-80%)
- high alkali content àsintering, slagging, and fouling
- high chlorine content àcorrosion

65
3.5 Biomass Combustion

Agglomeration
SiO2 melts at 1450 C
Eutectic Mixture melts at 874 C
Sintering tendency of fuel is indicated by the following
(Hulkkonenet al., 2003)

66
3.5 Biomass Combustion
Options for Avoiding the Agglomeration Problem
- Use of additives
- china clay, dolomite, kaolin soil
- Preprocessing of fuels
- water leaching
- Use of alternative bed materials
- dolomite, magnesite, and alumina
- Reduction in bed temperature

67
3.5 Biomass Combustion

Agglomeration

68
3.5 Biomass Combustion

Fouling
- is sticky deposition of ash due to evaporation of alkali salt
- result in low heat transfer to tube

69
3.5 Biomass Combustion

Corrosion Potential in Biomass Firing
-hot corrosion
-chlorine reacts with alkali metal àfrom low
temperature melting alkali chlorides
-reduce heat transfer and causing high temperature
corrosion

70
4. Heat Transfer in CFB
4.1 Gas to Particle Heat Transfer
4.2 Heat Transfer in CFB

71
4.1 Gas to Particle Heat Transfer

Mechanism of Heat Transfer
In a CFB boiler, fine solid particles
agglomerate and form clusters or
stand in a continuum of generally
up-flowing gas containing sparsely
dispersed solids. The continuum is
called the dispersed phase, while
the agglomerates are called the
cluster phase.
The heat transfer to furnace wall
occurs through conduction from
particle clusters, convection from
dispersed phase, and radiation
from both phase.

72
4.1 Heat Transfer in CFB Boiler

Effect of Suspension Density and particle size
Heat transfer coefficient is proportional to the square root of suspension density

73
4.1 Heat Transfer in CFB Boiler

Effect of Fluidization Velocity
No effect from fluidization velocity when leave the suspension density constant

74
4.1 Heat Transfer in CFB Boiler

Effect of Fluidization Velocity

75
4.1 Heat Transfer in CFB Boiler

Effect of Fluidization Velocity

76
4.1 Heat Transfer in CFB Boiler

Effect of Vertical Length of Heat Transfer Surface

77
4.1 Heat Transfer in CFB Boiler

Effect of Bed Temperature

78
4.1 Heat Transfer in CFB Boiler

Heat Flux on 300 MW CFB Boiler (Z. Man, et. al)

79
4.1 Heat Transfer in CFB Boiler

Heat transfer to the walls of commercial-size
Low suspension density low
heat transfer to the wall.

80
4.1 Heat Transfer in CFB Boiler

Circumferential Distribution of Heat Transfer Coefficient

81
5 Design of CFB Boiler

5.1 Design and Required Data

5.2 Combustion Calculation

5.3 Heat and Mass Balance

5.4 Furnace Design

5.5 Cyclone Separator

82
5.1 Design and Required Data
The design and required data normally will be specify by owner
or client. The basic design data and required data are;
Design Data :
-
Fuel ultimate analysis-Weather condition
-
Feed water quality -Feed water properties
Required Data :
-
Main steam properties-Flue gas temperature
-
Flue gas emission -Boiler efficiency

83
5.2 Combustion Calculation

Base on the design and required data the following data
can be calculated in this stage :
-Fuel flow rate -Combustion air flow rate
-Fan capacity -Fuel and ash handling capacity
-Sorbentflow rate

84
5.3 Heat and Mass Balance
Fuel and
sorbent
Unburned in
bottom ash
Feed water
Combustion air
Main steam
Blow down
Flue gas
Moisture in fuel
and sorbent
Unburned in fly ash
Moisture in
combustion air
Radiation
Heat input
Heat output

85
5.3 Heat and Mass Balance

Mass Balance
Fuel and
sorbent
bottom ash
Solid Flue gas
Moisture in fuel
and sorbent
fly ash
Make up
bed material
bottom ash
Fuel and
sorbent
Make up
bed material
Solid in Flue gas
fly ash
Mass output
Mass input

86
5.4 Furnace Design

The furnace design include:
1.
Furnace cross section
2.
Furnace height
3.
Furnace opening
1. Furnace cross section
Criteria
- moisture in fuel
- ash in fuel
- fluidization velocity
- SA penetration
- maintain fluidization in lower
zone at part load

87
5.4 Furnace Design
2. Furnace height
Criteria
- Heating surface
- Residual time for sulfur
capture
3. Furnace opening
Criteria
- Fuel feed ports
- Sorbent feed ports
- Bed drain ports
- Furnace exit section

88
5.5 Cyclone Separator

6.1 Theory

6.2 Critical size of particle

89
5.5 Cyclone Separator

The centrifugal force on the particle entering the cyclone
is

The drag force on the particle can be written as

Under steady state drag force = centrifugal force

90
5.5 Cyclone Separator

Vrcan be considered as index of cyclone efficiency, from
above equation the cyclone efficiency will increase for :
-Higher entry velocity
-Large size of solid
-Higher density of particle
-Small radius of cyclone
-low value of viscosity of gas

91
5.5 Cyclone Separator

The particle with a diameter larger than theoretical cut-
sizeof cyclone will be collected or trapped by cyclone
while the small size will be entrained or leave a cyclone

Actual operation, the cut-off size diameter will be defined
as d50 that mean 50% of the particle which have a
diameter more than d50 will be collected or captured.

92
6. Operation

93
Content
6.1 Before start
6.2 Grid pressure drop test
6.3 Cold Start
6.4 Normal Operation
6.5 Normal Shutdown
6.6 Hot Shutdown
6.7 Hot Restart
6.8 Malfunction and Emergency

94
6.1 Before Start

all maintenance work have been completely done

All function test have been checked

cooling water system is operating

compressed air system is operating

Make up water system

Deaeratorsystem

Boiler feed water pump

Condensate system

Oil and gas system

Drain and vent valves

Air duct, flue gas duct system

95
6.1 Before Start

Blow down system

Sand feeding system

Lime stone feeding system

Solid fuel system

Ash drainage system

Control and safety interlock system

96
6.2 Grid Pressure Drop Test

For check blockage of grid
nozzle

Furnace set point = 0

Test at every PA. load

Compare to clean data or design
data

Shall not exceed 10% from
design data

Perform in cold condition
Pw
Pb
FI
Pf= 0

97
6.3 Cold Start
Fill boiler
Boiler Interlock
Start up Burner
Feed Solid Fuel
Boiler Warm Up
Purge
Start Fan
Feed Bed Material
Raise to MCR
-100 mm normal level
ID,HP,SA,PA
Low level cut off
300 S
Tb 150-200 C
30-50 mbar, Tb 550-600 C

98
Fill Boiler
-Close all water side drain valve
-Open all air vent valve at drum and
superheat
-Open start up vent valve 10-15%
-Slowly feed water to drum until level 1/3 of
sigh glass

99
Start Fan
1.Start ID.Fan
2.Start HP Blower
3.Start SA.Fan
4.Start PA.Fan

100
Boiler Interlock
Emergency stop in order
Furnace P. < Max (2/3)
ID. Fan running
HP Blower start
Drum level > min (2/3)
SA. Fan running
PA. Fan running
HP. Blower P. > min
PA. Flow to grid > min
Trip Solid Fuel
Flue gas T after Furnace < max
Trip Soot Blower
Trip Oil
Trip Sand
Trip Lime Stone
Trip Bottom Ash

101
Purge

To carry out combustible gases

To assure all fuel are isolated
from furnace

Before starting first burner for
cold start

If bed temp < 600 C or OEM
recommend and no burner in
service

Total air flow > 50%

300 sec for purging time

102
Purge
NFPA85: CFB Boiler purge logic

103
Start up burner

Help to heat up bed temp to allowable temperature for
feeding solid fuel

Will be stopped if bed temp > 850 C

Before starting, all interlock have to passed

Main interlock

Oil pressure > minimum

Control air pressure > minimum

Atomizing air pressure > minimum

104
Start up burner
NFPA85 - Typical burner safety for CFB boiler

105
Drum and DA low level cut-off

Test for safety

During burner are operating

Open drain until low level

Signal feeding are not allow

Steam drum low level = chance
to overheating of water tube

DA low level = danger for BFWP

106
Boiler warm up

Gradually heating the boiler to reduce the effect of
thermal stress on pressure part, refractory and drum swell

Increase bed temp 60-80 C/hr by adjusting SUB

Control flue gas temperature <470 C until steam flow >
10% MCR

Close vent valves at drum and SH when pressure > 2 bar

Continue to increase firing rate according to
recommended start up curve

Operate desuperheaterwhen steam temperature are with
in 30 C of design point

Slowly close start up and drain valve while maintain steam
flow > 10% MCR

107
Feed bed material

Bed material should be sand which size is according to
recommended size

Start feed sand when bed temp >150 C

Do not exceed firing rate >30% if bed pressure <20 mbar
otherwise overheating may occur for refractory and nozzle

Continue feed bed material unit it reach 30 mbar

108
Feed solid fuel

Must have enough bed material

Bed temperature > 600 C or manufacturer
recommendation or refer to NFPA85 Appendix H

Pulse feed every 90 s

Placing lime stone feeding, ash removal system
simultaneously

Slowly decrease SUB firing rate while increasing solid fuel
feed rate

Stop SUB one by one, observe bed temperature increasing

Turn to auto mode control

109
Rise to MCR

Continue rise pressure and temperature according to
recommended curve until reach design point

Drain bottom ash when bed pressure >45-55 mbar

Slowly close start up valve

Monitor concerning parameters

110
6.4 Normal Operation

Increasing
- manual increase air flow
- manual increase fuel flow
- monitor excess oxygen
- monitor steam pressure

Decreasing
- manual decrease air flow
- manual decrease fuel flow
- monitor excess oxygen
- monitor steam pressure
Changing Boiler load (manual)

111
6.4 Normal Operation

Furnace and emssion
- monitor fluidization in hot
loop
- monitor gas side pressure drop
- monitor bed pressure
- monitor bed temperature
-monitor wind box pressure
- monitor SOx, Nox, CO
Furnace and Emission Monitoring

112
6.4 Normal Operation

Bottom ash drain
- automatic or manual draining
of bottom ash shall be judged by
commissioning engineer for the
design fuel.
- when fuel is deviated from the
design, operator can be judge by
themselves that draining need
to perform or not.
- bed pressure is the main
parameter to start draining

Soot blower
- initiate soot blower to clean
the heat exchanger surface in
convective part
- frequent of soot blowing
depend on the degradation of
heat transfer coefficient.
- normally 10 C higher than
normal value of exhaust
temperature
Bottom ash and Soot Blower

113
6.4 Normal Operation

Boiler Walk Down
- boiler expansion joint
- Boiler steam drum
- Boiler penthouse
- Safety valve
- Boiler lagging
- Spring hanger
- Valve and piping
- Damper position
- Loop seal
- Bottom screw
- Combustion chamber
- Fuel conveyor

114
6.4 Normal Operation

Sizing Quality
-crushed coal, bed material, lime stone and bottom ash
sizing shall be periodically checked by the operator
-sieve sizing shall be performed regularly to make sure
that their sizing is in range of recommendation

115
6.5 Normal Shut Down
1.
Reduce boiler load to 50% MCR
2.
Place O2 control in manual mode
3.
Monitor bed temperature
4.
Continue reducing load according to shut down curve
5.
Maintain SH steam >20 C of saturation temperature
6.
Start burner when bed temperature <750 C
7.
Empty solid fuel and lime stone with bed material >650 C
8.
Decrease SUB firing rate according to suggestion curve
9.
Maintain drum level in manual mode
10.
Stop solid fuel, line stone, sand feeding system

116
6.5 Normal Shut Down
11.
Maintain drum level near upper limit
12.
Continue fluidizing the bed to cool down the system at 2
C/min by reducing SUB firing rate
13.
Stop SUB at bed temperature 350 C
14.
Continue fluidizing until bed temperature reach 300 C
15.
Slowly close inlet damper of PAF and SAF so that IDF
can control furnace pressure in automatic mode
16.
Stop all fan after damper completely closed
17.
Stop HP blower 30 S after IDF stopped
18.
Stop chemical feeding system when BFWP stop
19.
Continue operate ash removal system until it empty

117
6.5 Normal Shut Down
20.
Open vent valve at drum and SH when drum pressure
reach 1.5-2 bar
21.
Open manhole around furnace when bed temp < 300 C

118
6.6 Emergency Shut down

Boiler can be held in hot stand by condition about 8 hrs

Hot condition is bed temp >650 C otherwise follow cold
star up procedure

Boiler load should be brought to minimum

Stop fuel feeding

Wait O2 increase 2 time of normal operation

Stop air to combustion chamber to minimize heat loss

119
6.7 Hot restart

Purge boiler if bed temperature < 600 C

Start SUBsif bed temperature > 500 C

Monitor bed temperature rise

If bed temperature does not rise after pulse feeding solid
fuel. stop feeding and start purge

120
6.8 Malfunction and Emergency

Bed pressure

Bed temperature

Circulation

Tube leak

Drum level

121
Bed Pressure
Bed pressure is an one of importance
parameter that effect on boiler efficiency
and reliability.
Measured above grid nozzle about 20 cm.
Pw
Pb
FI
Pf= 0

122
Bed Pressure

Effect of low bed pressure
-poor heat transfer
-boiler responds
-high bed temperature
-damage of air nozzle and refractory

Effect of high bed pressure
-increase heat transfer
-more efficient sulfur capture
-more power consumption of fan

123
Bed Pressure

Cause of low bed pressure
-loss of bed material
-too fine of bed materials
-high bed temperature

Cause of high bed pressure
-agglomeration
-too coarse of bed material

124
Bed Temperature

Measured above grid nozzle about
20 cm

Measured around the furnace cross
section

It is the significant parameter to
operate CFB boiler

125
Bed temperature

Effect of high bed temperature
-ineffective sulfur capture
-chance of ash melting
-chance of agglomeration
-chance to damage of air nozzle

126
Bed temperature

Cause of high bed temperature
-low bed pressure
-too coarse bed material
-too coarse solid fuel
-improper drain bed material
-low volatile fuel
-improper air flow adjustment

127
Circulation

Circulation is particular
phenomena of CFB boiler.

Bed material and fuel are
collected at cyclone separator

Return to the furnace via loop
seal

HP blower supply HP air to
fluidize collected materials to
return to furnace

128
Circulation

Effect of malfunction circulation
-No circulation result in forced shut down
-high rate of circulation
-high circulation rate need more power of blower
-low rate of circulation

129
Circulation

Cause of malfunction circulation
-insufficiency air flow to loop seal nozzle
-insufficient air pressure to loop seal
-plugging of HP blower inlet filter
-blocking or plugging of loop seal nozzle
-

130
Tube leak

Water tube leak
-furnace pressure rise
-bed temperature reduce
-stop fuel feeding
-open start up valve
-don’t left low level of drum
-continue feed water until flue gas temp < 400 C
-continue combustion until complete
-small leak follow normal shut down

131
Drum level
Sudden loss of drum level
-when the cause is known and immediately correctable
before level reach minimum allowable. Reestablish steam
drum level to its normal value and continue boiler
operation
-if the cause is not known. Start immediate shut down
according to emergency shut down procedure

132
Drum level
Gradual loss of drum level
-boiler load shall be reduced to low load
-find out and correct the problem as soon as possible
-if can not maintain level and correct the problem, boiler
must be taken out of service and normal shut down
procedure shall be applied.

133
7. Maintenance

134
Before maintenance work

Make sure that all staff are understand about safety
instruction for doing CFB boiler maintenance work

Make sure that all maintenance and safety equipments
shall be a first class

135
Overview Boiler Maintenance
Refractory and tube are the main
area that need to be checked

136
6.1 WindboxInspection

Inspect sand inside windbox
after shutdown

Drain pipe

Crack

Air gun pipe

Refractory

Crack, wear and fall down inspect
by hammer(knocking) if burner is
under bed design
Drain pipe

137
6.2 Furnace Inspection

Nozzle :

Wear

Fall-off

Refractory

Crack, wear and fall down inspect
by hammer knocking if burner is
under bed design

Feed fuel port

Wear

Crack

Burner
Refractory
Burner Feed Fuel
Nozzle

138
6.2 Furnace Inspection

Limestone port

Crack

Deform

Refractory damage at connection
between port and refractory

Secondary & Recirculation Air
port

Crack

Deform

Refractory damage at connection
between port and refractory

Bed Temperature

Check thermo well deformation

Check wear
Secondary & Recirculation Air port

139
6.3 Kick-Out Inspection

Refractory

Wear

Crack and fall down by
hammer(knocking)

Water tube

Wear

Thickness

140
6.3 Kick-Out Inspection

Water Tube:

Thickness measuring

Erosion at corner

CO Corrosion due to incomplete
combustion at fuel feed side.

Defect from weld build up

Water tube sampling for internal
check every 3 years
Inside water tube inspect by borescope
welded build up excessive metal because use welding rod
size bigger than tube thickness

141
6.4 Superheat I (Wingwall)

Water Tube:

Thickness measuring

Erosion at tube connection

Refractory

Crack and fall down by
hammer(knocking)

Guard

Crack

fall down

142
6.4 Superheat I (Omega Tube)

Offset Water Tube:

Thickness measuring

Erosion at offset tube

SH tube

Thickness measuring

Omega Guard

Crack

fall down
Omega Guard
Offset Water
Tube

143
6.5 Roof

Water Tube:

Thickness measuring

Erosion

Refractory

Crack, wear and fall down by
hammer(knocking)

144
6.6 Inlet Separator

Water Tube:

Thickness measuring near opening
have more erosion than another
tube because of high velocity of flue
gas

Refractory

Crack, wear and fall down by
hammer(knocking)

145
6.7 Steam Drum

Surface :

Surface were black by magnetite

Deposits

Deposits at bottom drum need to
check chemical analysis

Cyclone Separator

Loose

Demister

Blowdownhole

Plugging

U-Clamp

Loose
Deposits at bottom drum

146
6.8 Separator

Central Pipe:

Deformation

Crack

Refractory

Wear at impact zone due to high
impact velocity

Crack and fall down by
hammer(knocking)

147
6.9 Outlet Separator

Water Tube

Tube Thickness

Erosion

Outlet Central Pipe:

Support or Hook

Refractory

Crack and fall down by
hammer(knocking)

148
6.10 Screen Tube

Water Tube

Thickness measuring upper part of
screen tube at corner have more
erosion than another area because
of high velocity of flue gas

Guard

Loose

Refractory

Crack and fall down by
hammer(knocking)
Weld build up or install guard to prevent tube erosion
upper part of screen tube at corner have more erosion

149
6.11 Superheat Tube

Tube

Thickness measuring

High erosion between SH tube and
wall

Steam erosion due to improper soot
blower

Guard

Fall down

Crack

150
6.12 Economizer

Water Tube

Thickness measuring

High erosion between economizer
tube and wall

Steam erosion due to improper soot
blower

Guard

Fall down

Crack
Guard
Install guard to
prevent tube erosion

151
6.13 Air Heater

Tube

Cold end corrosion due to high
concentrate SO3 in flue gas

Steam erosion due to improper soot
blower
Inlet air heater
Cold end corrosion due to SO3 in fluegas

152
8. Basic Boiler Safety

153
Warning
Operating or maintenance procedure which, if
not as described could result in injured death
or damage of equipment

154
General safety precaution

Electrical power shall be turned off before performing
installation or maintenance work. Lock out, tag out shall
be indicated

All personal safety equipment shall be suit for each work

Never direct air water stream into accumulation bed
material or fly ash. This will become breathing hazard

Always provide safe access to all equipment ( plant from,
ladders, stair way, hand rail

Post appropriate caution, warning or danger sign and
barrier for alerting non-working person

Only qualify and authorized person should service
equipment or maintenance work

155
General safety precaution

Do not by-pass any boiler interlocks

Use an filtering dust mask when entering dust zone

Do not disconnect hoist unless you have made sure that
the source is isolated

156
Equipment entry

Never entry confine space until is has been cooled, purged
and properly vented

When entering confine space such as separator, loop seal
furnace be prepared for falling material

Always lock the damper, gate or door before passing
through them

Never step on accumulation of bottom ash or fly ash. Its
underneath still hot

Never use toxic fluid in confine space

Use only appropriate lifting equipment when lift or move
equipment

157
Equipment entry

Stand by personnel shall be positioned outside a confine
space to help inside person incase of emergency

Be carefully aware the chance of falling down when enter
cyclone inlet or outlet.

Don not wear contact lens with out protective eye near
boiler, fuel handing, ash handing system. Airborne particle
can cause eye damage

Don not enter loop seal with out installing of cover over
loop seal downcomer to prevent falling material from
cyclone

158
Operating precautions
CFB boiler process

Use planks on top of bed materials after boiler is cooled
down. This will prevent the chance of nozzle plugging

Do not open any water valve when boiler is in service

Do not operate boiler with out O2 analyzer

Do not use downcomerblown donwwhen pressure > 7
bar otherwise loss of circulation may occure

Do not operate CFB boiler without bed material

When PA is started. PA flow to grid must be increase to
above minimum limit to fully fluidized bed maerial

Do not operate CFB boiler with bed pressure > 80mbar.
This might be grid nozzle plugging

159
Operating precautions

on cold start up the rate of chance in saturated steam shall
not exceed 2 C/min

On cold start up the change of flue gas temp at cyclone
inlet shall not exceed 70 C/min

Do not add feed water to empty steam drum with
different temperature between drum metal and feed water
greater than 50 C

All fan must be operated when add bed material

160
Operating precautions
Refractory

When entering cyclone be aware a chance of falling down

Refractory retain heat for long period. Be prepared for hot
surface when enter this area

An excessive thermal cycle will reduce the life cycle of
refractory

After refractory repair, air cure need to apply about 24 hr
or depend on manufacturer before heating cure

Heating cure shall be done carefully otherwise refractory
life will be reduced

161
Operating precautions
Solid Fuel

Chemical analysis of all solid fuel shall be determined for
first time and compared with OEM standard

Sizing is important

Burp feeding shall be performed during starting feeding
solid fuel instead of continuous feeding

162
9. Basic CFB Boiler Control

163

Basic control

Furnace control

Main pressure control

Main steam pressure control

Drum level control

Feed tank control

Solid fuel control

Primary air control

Secondary air control

Oxygen control

164
Basic control

Simple feedback control
PRIMARY VARIABLE
XT
K
A T A
f(x)
SET POINT
PROCESS
MANIPULATED VARIABLE

165
Basic control

Simple feed forward plus feedback control
PR IM ARY VARIABLE
XT
YT
SECO NDARY
VARIABLE
A T A
f(x)
MA NIP ULATED VARIAB LE
P ROCE SS
S ET POINT
K

166
Basic control

Simple cascade control
PRIMARY VARIABLE
XT
ZT
K
K
SET POINT
A AT
PROCESS
f(x)
MANIPULATED VARIABLE
SECONDARY
VARIABLE

167
Basic control
CO
SP
PV
PID
Control Mode of PID
-MAN (Manual)
-AUT (Automatic)
-CAS (Cascade)
Signal to open0-15 m3/h
0-100% (closed àopen)
4-20 mAElectrical signal 4-20 mA
Eng. Unit 0-15 m3/h
Percent 0-100 % 0-100%

168
Feed water control
LT
PT
PIDPID
Make up water
Heating steam
Pressure
-Manual mode 0-100% heating steam valve
position
-Auto mode, specify pressure set point
-Temperature compensation
Level
-Manual mode 0-100% make up water valve
-Auto mode, specify level set point
-Temperature compensation
-Protection, high level over flow

169
Drum Level control
DP feed
water pump
Control valve
A, SP
M, 0-100%
Main steam flow
Main steam Pressure
Manual mode, 0-100%
control valve
Auto mode, specify drum
level. Automatically adjust
valve
Protection
-lower limit
-2/3 principle
- 10 s delay
-Close steam valve for low level

170
Main steam pressure control
SP
PV
FF
CO

171
Combustion
Calculation
SA SPPA SP
Total air SP Total Fuel SP
Fuel1 SP Fuel3 SPFuel2 SP
PA.Fan
Conveyor1 Conveyor2 Conveyor3
SA.Fan
X -
Main steam
Pressure

172
Solid Fuel Control
M
WT
PIDCascade
Auto
Manual
Manual : speed of coal conveyor is
specified by operator
Auto : operator specify fuel flow load
Cascade: fuel flow set point calculated by
main steam pressure control

173
Primary air control
M
PID
FT
Auto
Cascade
PV
Manual
Manual: position of damper is
specified
Auto: desired air flow is specified by
operator
Cascade: set point is calculated from
master combustion
Flow (interlock) > minimum
PA wind box P > minimum
PA running

174
Secondary air control
M
PID
Auto
Cascade
Manual
FT
FT
PT
Manual
Manual
PIDAuto
Cascade
Lower SA
Upper SA
FT
PV

175
HP Blower Control

Pressure is controlled by control valve

Control valve is connected to primary air

It will release the air to primary air duct if pressure higher
than set point

If operating unit stop due to disturbance or pressure fall
down, stand by unit shall be automatically started

Pressure should be higher than 300 mbar, boiler interlock

Pressure < 350 mbar parallel operation start

176
Furnace Pressure control
M
PID
PT
Auto
Furnace
pressure
Manual
PID
Manual
Auto
2/3 furnace P < max (35 mbar)

177
Lime stone control

Lime stone can be control by

lime stone/ fuel flow ratio

SO2 feed back control

Manual feed rate

178
Fuel oil control
M
A
Pressure control
Pressure
control valve
Flow control
valve
Auto
Manual

179
Referenced
•Prabir Basu , Combustion and gasification in fluidized bed, 2006
•Fluidized bed combustion, Simeon N. Oka, 2004
•Nan Zh., et al, 3D CFD simulation of hydrodynamics of a 150 MWe circulating fluidized bed
boiler, Chemical Engineering Journal, 162, 2010, 821-828
•Zhang M., et al, Heat Flux profile of the furnace wall of 300 MWe CFB Boiler, powder
technology, 203, 2010, 548-554
•Foster Wheeler, TKIC refresh training, 2008
•M. Koksal and F. Humdullahper , Gas Mixing in circulating fluidized beds with secondary
air injection, Chemical engineering research and design, 82 (8A), 2004, 979-992