Chiller daikin datos tecnicos

alejandrocastillo7121 580 views 68 slides Jun 06, 2021
Slide 1
Slide 1 of 68
Slide 1
1
Slide 2
2
Slide 3
3
Slide 4
4
Slide 5
5
Slide 6
6
Slide 7
7
Slide 8
8
Slide 9
9
Slide 10
10
Slide 11
11
Slide 12
12
Slide 13
13
Slide 14
14
Slide 15
15
Slide 16
16
Slide 17
17
Slide 18
18
Slide 19
19
Slide 20
20
Slide 21
21
Slide 22
22
Slide 23
23
Slide 24
24
Slide 25
25
Slide 26
26
Slide 27
27
Slide 28
28
Slide 29
29
Slide 30
30
Slide 31
31
Slide 32
32
Slide 33
33
Slide 34
34
Slide 35
35
Slide 36
36
Slide 37
37
Slide 38
38
Slide 39
39
Slide 40
40
Slide 41
41
Slide 42
42
Slide 43
43
Slide 44
44
Slide 45
45
Slide 46
46
Slide 47
47
Slide 48
48
Slide 49
49
Slide 50
50
Slide 51
51
Slide 52
52
Slide 53
53
Slide 54
54
Slide 55
55
Slide 56
56
Slide 57
57
Slide 58
58
Slide 59
59
Slide 60
60
Slide 61
61
Slide 62
62
Slide 63
63
Slide 64
64
Slide 65
65
Slide 66
66
Slide 67
67
Slide 68
68

About This Presentation

datos tecnicos


Slide Content

Catalog 624-16
Trailblazer
®
Air-Cooled Scroll Compressor Chillers
With High Efficiency Variable Speed Fan Technology
Model AGZ-E
030 to 241 Tons (100 to 840 kW)
HFC-410A Refrigerant
60/50 Hz

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 2 www.DaikinApplied.com
Table of Contents
Table of Contents
©2018 Daikin Applied. Illustrations and data cover the Daikin Applied product at the time of publication and we reserve the right to
make changes in design and construction at any time without notice.
Manufactured in an ISO 9001 & ISO 14001 certified facility
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . .3
Features and Benefits . . . . . . . . . . . . . . . . . . 4
Application Considerations . . . . . . . . . . . . .7
Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . .17
Selection Procedure . . . . . . . . . . . . . . . . . .23
Performance Data . . . . . . . . . . . . . . . . . . . .25
Pressure Drop Data . . . . . . . . . . . . . . . . . . .27
Physical Data - Packaged Unit . . . . . . . . . . 29
Dimensions & Weights - Packaged Units .33
Dimensions & Weights - Heat Recovery
Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Isolators . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Electrical Data . . . . . . . . . . . . . . . . . . . . . . .48
Options and Accessories . . . . . . . . . . . . . .59
Engineering Guide Specifications . . . . . . .64
Daikin Tools Pathfinder version: 8.30
The ratings in this catalog are consistent with the Daikin Tools selection program version shown.
For the most up-to-date information, please go to www.DaikinApplied.com.

*Heat Recovery option outside the scope of
AHRI ACCL Certification Program.

Introduction
www.DaikinApplied.com 3 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
The Trailblazer
®
family of air-cooled scroll chillers continues
the Daikin Applied legacy of high quality, high efficiency,
latest technology and quiet operation. These features make
the Trailblazer
®
family the best overall value in air-cooled
packaged chillers available today. The Trailblazer® series
offers a wide selection of units from 30 to 241 tons with dual
refrigerant circuits available as packaged units with optional
heat recovery or pump packages, or as remote evaporators.
Efficient Operation
The Trailblazer
®
units utilize environmentally acceptable
R-410A refrigerant and meet the performance requirements
of ASHRAE Standard 90.1 for efficiency. Excellent part-load
performance is achieved with four or six scroll compressors.
A variable speed condenser fan option is also available to
provide even higher part load efficiency. High overall efficiency
= lower annual energy costs.
RapidRestore
®
and Fast Loading
When power has been interrupted, the Trailblazer
®
has the
capability to restore cooling quickly by using RapidRestore
®

and Fast Loading. These options make Trailblazer
®
ideal for
mission critical buildings, data centers, healthcare facilities,
and manufacturing processes. Once power is restored after
a power loss duration of up to 180 seconds, the time for a
Trailblazer
®
chiller to restart is less than 125 seconds with the
chiller reaching full load within 220 seconds.
Application Flexibility
Trailblazer
®
units are available as packaged chillers with
optional heat recovery or pump packages as well as remote
evaporator configurations. Information on remote evaporator
models and factory-installed pump packages can be found in a
separate installation manual available on
www.DaikinApplied.com.
Quiet Operation
The Trailblazer® units live up to the Daikin Applied reputation
for low operating sound levels and make these chillers
“neighborhood friendly.” Full load sound pressure levels as low
as 60 dB without insulation.
LEED
®
Points
Developed by the U.S. Green Building Council (USGBC)
in 1998, Leadership in Energy and Environmental Design
(LEED
®
) is an internationally recognized certification program
and intends to provide building owners and operators a
consistent structure for identifying and implementing practical
and measurable green building design, construction,
operations and maintenance solutions.
For building owners who want to pursue LEED
®
Green Building
Certification, the Trailblazer® series of air-cooled chillers does
qualify for the Energy and Atmosphere Credit 4, Enhanced
Refrigerant Management worth 2 points.
Air-Cooled Chiller Products
1000 200 300 400 500 600
Trailblazer® Air-Cooled Chiller
Model AMZ • 10 - 40 RT
Pathfinder® Air-Cooled Screw Compressor Chiller
Model AWV VFD
•100-565 RT
100% Configurable with Variable Volume Ratio (VVR) Technology
Remote Evaporator options available
2F-4056 (12/17) ©2017 Daikin Applied
Trailblazer® Air-Cooled Scroll Compressor Chiller
Model AGZ-E • 30 - 240 RT
Variable Speed Condenser Fan Technology with
Remote Evaporator, Heat Recovery and High-Efficiency options available
Introduction

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 4 www.DaikinApplied.com
Features and Benefits
CHILLER NOMENCLATURE
A G Z XXX E D
Unit Design Features
Daikin Trailblazer
®
air-cooled chillers are a product of our
commitment to offer quiet, reliable, energy efficient equipment,
incorporating high quality compressors, and innovative
packaging.
Construction
Trailblazer
®
chillers are factory-assembled and mounted
on a heavy-gauge steel base. The base distributes the unit
weight for roof loading. Their small footprint allows smaller
mounting pads or support structures and is a plus for retrofit or
replacement applications.
Compressors
Reliable hermetic scroll compressors with cast iron scrolls
and three Teflon
®
impregnated bearings are used on the
Trailblazer
®
chillers to promote longevity.
Each model has the ability to modulate its capacity. Models
with four compressors will have four steps of capacity
modulation while models with six compressors will have six
steps. Compressors stage on depending on the load of the
system. This results in excellent part-load efficiency and
reduced annual operating costs.
Features include motor temperature protection, scroll
temperature protection, missing phase protection, reverse
phase protection, low control circuit voltage protection, short
cycling detection and alert, Modbus
®
communication to system
controller, operational and fault history storage, and LED status
display.
Evaporator
Trailblazer
®
units are designed to maximize efficiency in the
smallest possible footprint. The evaporator is a compact,
high efficiency, dual circuit, brazed plate-to-plate type heat
exchanger consisting of parallel stainless steel plates. These
heat exchangers provide excellent heat exchange efficiency
in a compact footprint and are especially attractive for smaller
capacity units. Evaporators are designed and constructed
according to, and listed by, Underwriters Laboratories (UL).
Optional Remote Evaporator
Units 30-241 tons with the optional remote evaporator will have
the evaporator shipped separately for field mounting and piping
to the outdoor unit.
Condenser Coils
Condenser coils are all aluminum alloy microchannel design
with a series of flat tubes containing multiple, parallel flow
microchannels layered between the refrigerant manifold piping.
A variety of optional coil materials and coatings are available
so that the unit can be constructed to meet almost any
environment. Packaged unit options include:
• copper tube/aluminum fins (30-70 ton models only)
• copper tube/copper fins (30-70 ton models only)
• copper tube/aluminum Black-fins (30-70 ton models only)
• Epoxy coating can be applied to any coil option
See “Condenser Coil Options and Coating Considerations” on
page 15 for discussion of environmental factors related to
material and coating options.
Figure 1: Microchannel Coil
Air-Cooled
Global Design
Scroll Compressor
Compressors
D = 2 Compressors/Circuit
T = 3 Compressors/Circuit
Design VintageNominal Tons
Features and Benefits

Features and Benefits
www.DaikinApplied.com 5 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Figure 2: Trailblazer

with Optional Full Louver Package
Optional High Efficiency Variable Speed
Condenser Fans
This option (available on 75-241 ton models) adds variable
speed drives to the condenser fans on the chiller. The
MicroTech® III controller will adjust the speed of the condenser
fans using the VFD’s to optimize chiller efficiency and maintain
proper head pressure. This feature improves part load
efficiency substantially and offers the ability to operate in low
ambient conditions down to -10°F.
Control System
The MicroTech
®
III advanced DDC chiller controller surpasses
all other microprocessor-based chiller control systems
available today. This powerful, user-friendly control system
provides the flexibility and performance needed for either
stand-alone unit operation or the controller can be easily tied
into the building automation system of choice using the Daikin
Open Choices
®
feature.
Open Choices
®
allows one to choose from open standard
protocols such as BACnet
®
, Modbus
®
and L
onWorks
®
to
communicate easily with the building automation system that best meets the facility requirements. These optional
communications modules are available factory installed or can
be easily field installed.
The MicroTech
®
III controller’s design will not only permit
the chiller to run more efficiently, but will also simplify
troubleshooting if a system failure occurs. Every MicroTech
®
III
controller is programmed and tested prior to shipment to help
provide a trouble-free start-up.
Optional Remote Interface Panel
In addition to the unit-mounted user interface provided with
MicroTech
®
III controls, the Trailblazer® chillers can be
individually equipped with a remote user interface. It provides
convenient access to unit diagnostics and control adjustments
without having to access a rooftop or outdoor location. One
remote panel can be connected to up to eight chillers.
Intelligent Equipment®
Intelligent Equipment (IE) from Daikin
Applied is a secure, cloud-based controls
solution that enables delivery equipment
and/or system information to customers
via web or mobile devices. A power
measurement module and communications
gateway installed on Daikin equipment
enables the unit to be directly connected
to the Internet via wireless (cellular, Wi-Fi)
or local area network (LAN), providing
management, monitoring control analysis
and decision-making functionality for Daikin
chiller systems and the facility.
Features
• Remote monitoring and control of Daikin chillers
• Remote servicing capabilities
• Integration to the Energy Star
®
Portfolio Manager
®
• Advanced data analytics including equipment
performance, financial performance and building Comfort
Index metrix based on ASHRAE Standard 55-2010
• Dynamic user dashboards with photo-realistic graphics
and responsive-design interface optimized for users’
mobile devices, tablets or PCs
• Secure, role-based user access
Benefits
• Informed decision-making
• Increased equipment efficiency
• 24/7 monitoring capability
• Real-time equipment information
• Accelerated equipment payback
• Historical performance data
• Can be used with, or without, an existing building
automation system (BAS)
Also see ASP 31-384 for more details.

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 6 www.DaikinApplied.com
Features and Benefits
Optional Pump Package
The on-board, integrated chilled water pump package provides
important benefits:
• Simplify the chilled water system design and installation
• Provide installation savings by reducing field piping,
wiring and control costs
• Save valuable floor space inside the building.
• Reduce project engineering content
• Greatly reduce pump operating cost with the optional
variable flow pump VFD
Standard Components
Single Pump: Single spring inside seal, vertical, in-line,
radially split-case pump, serviceable without breaking pipe
connections. The motor and pump rotating assembly can be
serviced without removing the pump casing from the line.
Dual Pumps in a Single Casting: Single-spring inside-
seal vertical, in-line, radially split-case pumps, mounted
in a common casing with a common inlet connection and
outlet connection and including a flapper valve to prevent
recirculation when only one pump is operating. An isolation
valve is included that allows one pump to operate when the
other is removed. The pumps are designed for duty/standby,
not parallel operation. All information and performance curves
for the single pump arrangement (Model 4380) can be used for
the dual pump arrangement (Model 4392).
The package is also is equipped with a “Y” type inlet strainer, a
combination triple-duty outlet valve having a discharge shutoff
valve, check valve, and flow throttling valve, a combination
suction guide with flow stabilizing outlet vanes and stainless
steel strainer with a disposable fine-mesh start-up strainer,
a flow switch mounted and wired, factory power and control
wiring, interconnecting piping and insulation of all cold
surfaces. Various tank and connection options are available
for field mounting. Refer to the schematic in Figure 3 for more
information.
Figure 3: Optional Pump Package Schematic
Optional Variable Flow VFD
The operating cost savings resulting from using variable
chilled water flow via a pump VFD is well known. In the past,
however, its usage has been somewhat limited by the cost
and uncertainty of field installing the required system pressure
differential sensors.
Daikin Applied can now offer flow control through the pump
VFD without the need for external pressure sensors. In addition
to the sensorless operation, there are three other selectable
operating modes:
BAS Input: The pump speed and system flow will be
controlled from a customer-supplied BAS input signal.
Remote Sensor Control: The VFD is wired to a pressure
sensor mounted in the chilled water piping system. This is the
standard VFD control when a sensorless VFD is not used.
Locally Selected Constant Speed Control: Provides manual
control of the pump speed, overriding any current automatic
speed control.
Consult the current version of the installation manual for
additional detailed information. It is available from the local
Daikin Applied sales office or on www.DaikinApplied.com.
Optional Partial Heat Recovery
Partial heat recovery (available on 75-241 ton models) adds
optional factory-installed heat exchangers and control logic to
provide hot water for many uses such as dehumidification and
pre-heating water for a boiler. This option reduces operating
costs by using heat that already exists in the chiller instead of
paying for another source of energy.
Figure 4: Partial Heat Recovery Heat Exchangers
Dual
Vertical
Pumps
“Y” Type
Inlet
Strainer
Chilled
Water
Inlet
Inlet
Guide
Optional
VFD
Controllers
Chilled
Water
Outlet
Triple-Duty
Outlet Valve
Flow
Switch
DrainEvap Out Press.
Gauge Port
Pump
Package
Control
Panel
Brazed-Plate
Evaporator
Evap In Press.
Gauge Port

Application Considerations
www.DaikinApplied.com 7 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Operating and Standby Limits
Table 1: Operating Limits
Maximum standby ambient temperature 130°F (54°C)
Maximum operating ambient temperature 105°F (41°C)
-with optional high ambient package (see “High Ambient Operation” on page 14) 125°F (52°C)
Minimum operating ambient temperature (standard control) 32°F (0°C)
-with optional low ambient control (see “Low Ambient Operation” on page 14) -10°F (-23°C)
Leaving chilled water temperature 40°F to 65°F (4°C to 18°C)
Leaving chilled fluid temperatures (with anti-freeze) - Note that in cases of high ambient
temperature, the lowest leaving water temperature settings may be outside of the chiller operating
envelope; consult Daikin Tools® to ensure chiller is capable of the required lift.
15°F to 65°F (-9°C to 18°C)
Operating chilled water delta-T range 6°F to 16°F (3.3°C to 8.9°C)
Maximum evaporator operating inlet fluid temperature 81°F (27°C)
Maximum evaporator non-operating inlet fluid temperature 100°F (38°C)
Unit Placement
Trailblazer
®
units are for outdoor applications and can be
mounted either on a roof or at ground level. For roof mounted applications, install the unit on a steel channel or I-beam
frame to support the unit above the roof. For ground level
applications, install the unit on a substantial base that will not
settle. Use a one-piece concrete slab with footings extended
below the frost line. Be sure the foundation is level within 0.5”
(13 mm) over its length and width. The foundation must be
strong enough to support the unit weight - see the Dimensions
section starting on page 33.
Service Clearance
Sides
• Models 30-70: Minimum of 4 feet (1.2 meters)
• Models 75-241: It is highly recommended to provide
a minimum of 8 feet (2.4 meters) on one side to allow
for coil replacement. Coils can be removed from the
top, allowing a minimum of 4 feet (1.2 meters) of side
clearance; however, the unit performance may be
derated.
Control Panel End
• All Models: Minimum of 4 feet (1.2 meters)
Opposite Control Panel End
• Models 30-70 with Aluminum Fin/Copper Tube Coils:
Minimum of 4 feet (1.2 meters)
• Models 30-70 with Microchannel Coils:
Minimum of 7.5 feet (2.3 meters)
• Models 75-241: Minimum of 4 feet (1.2 meters)
Figure 5: Service Clearance
Operational Spacing Requirements
Sufficient clearance must be maintained between the unit
and adjacent walls or other units to allow the required unit
air flow to reach the coils. Failure to do so will result in a
capacity reduction and an increase in power consumption.
No obstructions are allowed above the unit at any height. The
clearance requirements shown are a general guideline and
cannot account for all scenarios. Such factors as prevailing
winds, additional equipment within the space, design outdoor
air temperature, and numerous other factors may require more
clearance than what is shown. Additional clearances may be
required under certain circumstances.
Graphs on the following pages give the minimum clearance for
different types of installations and also capacity reduction and
power increase if closer spacing is used. The graphs are based
on individual cases and should not be combined with other
scenarios.
Minimum = 4 ft (1.2 m)
Minimum = 4 ft (1.2 m)
Minimum = 4 ft
(1.2 m)
Minimum = 7.5 ft (2.3 m)
for models 030-070
with Microchannel Coils
Control Panel
Minimum = 4 ft (1.2 m)
for models
030-070 with Al/Cu Coils
& 075-241
075-241 Ton Models: 8ft (2.4 m) recommended on one side

Application Considerations

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 8 www.DaikinApplied.com
Application Considerations
Case 1: Building or Wall on One Side of Unit
NOTE: Assumes a solid height wall taller than unit. Refer to
Case 4 for partial wall openings.
For models AGZ030-100E, maintain a 4 feet minimum from
any solid height wall taller than unit.
For models AGZ110-130E, maintain a 6 feet minimum from any
solid height wall taller than unit.
For models AGZ140-241E, maintain a 8 ft minimum clearance
from any solid height wall taller than unit.
Figure 6: Building or Wall on One Side of Unit
Case 2: Two Units, Side-by-Side
For models 030-180, there must be a minimum of 4 feet
between two units placed side-by-side; however, performance
may be affected at this distance. For models 191-241,
the minimum is 6 feet as closing spacing may cause air
recirculation and elevated condenser pressure. Assuming
the requirement of one side having at least 8 feet of
service clearance is met, Case 2 figures show performance
adjustments as the distance between two units increases.
Figure 7: Two Units, Side-by-Side
Figure 8: Case 2 - Full Load Capacity Reduction
Figure 9: Case 2 - Power Increase
Height
of
Wall
Distance
Between
Wall
and
Unit
D
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4 5 6 8
% Capacity Reduction
Distance Between Units (ft)
Full Load Capacity Reduction
AGZ030-070E AGZ075-100E
AGZ110-130E AGZ140-180E
AGZ191-211E AGZ226-241E
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
4 5 6 8
% Power Increase
Distance Between Units (ft)
Power Increase
AGZ030-070E AGZ075-100E
AGZ110-130E AGZ140-180E
AGZ191-211E AGZ226-241E
Application Considerations

Application Considerations
www.DaikinApplied.com 9 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Case 3: Three or More Units, Side-by-Side
For all models, there must be a minimum distance between
any units placed side-by-side; however, performance may be
affected at this distance. Minimum distances are: models 030
to 070 - 4 feet, models 075 to 100 - 5 feet, models 110 to 241
- 6 feet. Figure 11 and Figure 12 depict Case 3 performance
adjustments as the distance between units increases.
NOTE: Data in Figure 11 and Figure 12 is for the middle unit
with a unit on each side. See Case 2 adjustment
factors for the two outside units.
Figure 10: Three or More Units, Side-by-Side
Figure 11: Case 3 - Full Load Capacity Reduction
Figure 12: Case 3 - Power Increase
Case 4: Open Screening Walls
Screening walls may be used to help conceal a unit. When
possible, design these walls such that the combination of
open area and distance from the unit (see Figure 13) does
not require performance adjustment. If the wall opening
percentage is less than recommended for the distance to the
unit, it should be considered as a solid wall. It is assumed that
the wall height is equal to or less than the unit height when
mounted on its base support. If the wall height is greater than
the unit height, see Case 5 for adjustment factors. The distance
from the sides of the unit to the walls must be sufficient for
service. For uneven wall spacing, the distance from the unit to
each wall can be averaged providing no distance is less than 4
feet. Values are based on walls on all four sides.
Figure 13: Case 4 Allowable Wall Open Area
0.0
1.0
2.0
3.0
4.0
5.0
6.0
4 5 6 8
% Capacity Reduction
Distance Between Units
Full Load Capacity Reduction
AGZ030-035E AGZ040-070E AGZ075-100E
AGZ0110-130E AGZ140-180E AGZ191-211E
AGZ226-241E
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
4 5 6 8
% Power Increase
Distance Between Units (ft)
Power Increase
AGZ030-035E AGZ040-070E AGZ075-100E
AGZ0110-130E AGZ140-180E AGZ191-211E
AGZ226-241E
3.0
4.0
5.0
6.0
7.0
8.0
9.0
0 10 20 30 40 50
Distance from Wall to Unit (ft)
% Open Wall Area
Wall Free Area vs. Distance
AGZ030-070E AGZ075-100E
AGZ110-130E AGZ140-180E
AGZ191-241E

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 10 www.DaikinApplied.com
Application Considerations
Case 5: Pit Installation
Pit installations can cause operating problems resulting from
air recirculation and restriction and require care that sufficient
air clearance is provided, safety requirements are met and
service access is provided. A solid wall surrounding a unit is
substantially a pit and this data should be used.
Steel grating is sometimes used to cover a pit to prevent
accidental falls or trips into the pit. The grating material
and installation design must be strong enough to prevent
such accidents, yet provide abundant open area to avoid
recirculation problems. Have any pit installation reviewed by
the Daikin Applied sales representative prior to installation to
ensure it has sufficient air-flow characteristics and approved by
the installation design engineer to avoid risk of accident. The
following de-rates are based on single chiller installations only.
Models AGZ030-070E:
The Case 5 figures for models AGZ030-070E show adjustment
factors for pit/wall heights of 4 feet, 5 feet, and 6 feet.
Figure 14: Case 5 - Full Load Capacity Reduction
(AGZ030E-070E)
Figure 15: Case 5 - Power Increase (AGZ030-070E)
Figure 16: Case 5 - Pit Installation
Models AGZ075-130E:
The Case 5 figures for models AGZ075-130E show adjustment
factors for pit/wall heights of 5 feet, 6 feet, and 8 feet.
Figure 17: Case 5 - Full Load Capacity Reduction
(AGZ075-130E)
Figure 18: Case 5 - Power Increase (AGZ075-130E)
0.0
1.0
2.0
3.0
4.0
5.0
6.0
0 8 10 12 13 14
% Capacity Reduction
Depth of Pit / Wall Height (ft)
Full Load Capacity Reduction (AGZ030-070E)
D istance = 4 f t D istance = 5 f t D istance = 6 f t
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
0 8 10 12 13 14
% Power Increase
Depth of Pit / Wall Height (ft)
Power Increase (AGZ030-070E)
Distance = 4 f t Distance = 5 f t Distance = 6 f t
0.0
1.0
2.0
3.0
4.0
5.0
6.0
0 8 10 12 13 14
% Capacity Reduction
Depth of Pit / Wall Height ft)
Full Load Capacity Reduction (AGZ075-130E)
D istance = 5 f t D istance = 6 f t D istance = 8 f t
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
0 8 10 12 13 14
% Power Increase
Depth of Pit / Wall Height (ft)
Power Increase (AGZ075-130E)
Distance = 5 f t Distance = 6 f t Distance = 8 f t

Application Considerations
www.DaikinApplied.com 11 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Models AGZ140-241E:
The Case 5 figures for models AGZ140-241E show adjustment
factors for pit/wall heights of 6 feet, 8 feet, and 10 feet.
Figure 19: Case 5 - Full Load Capacity Reduction
(AGZ140-180E)
Figure 20: Case 5 - Power Increase (AGZ140-211E)
Figure 21: Case 5 - Full Load Capacity Reduction
(AGZ191-241E)
Figure 22: Case 5 - Power Increase (AGZ226-241E)
Chilled Water Piping
Field installed water piping to the chiller must include:
• A cleanable strainer installed at the water inlet to the
evaporator to remove debris and impurities before they
reach the evaporator, causing damage. See the Inlet
Strainer Guidelines and the current version of the product
Installation, Operation and Maintenance manual on www.
DaikinApplied.com for additional details.
• Adequate piping support to eliminate weight and strain on
the fittings and connections.
• A water flow switch must be installed in the horizontal
piping of the supply (evaporator outlet) water line to avoid
evaporator freeze-up under low or no flow conditions. The
flow switch may be ordered as a factory-installed option,
a field-installed kit, or may be supplied and installed in the
field. (See page 59 for more information.)
• Piping for units with brazed-plate evaporators must have
a drain and vent connection provided in the bottom of
the lower connection pipe and to the top of the upper
connection pipe respectively, see Figure 23. These
evaporators do not have drain or vent connections due to
their construction.
It is recommended that the field installed water piping to the
chiller include:
• Thermometers at the inlet and outlet connections of the
evaporator.
• Water pressure gauge connection taps and gauges at
the inlet and outlet connections of the evaporator for
measuring water pressure drop.
• Vibration eliminators in both the supply and return water
lines. Pressure gauges must be installed in the inlet and
outlet water lines to the evaporator.
• Insulate chilled water piping to reduce heat loss and
prevent condensation. For information on freeze
protection, see “Evaporator Freeze Protection” on page
13.
0.0
1.0
2.0
3.0
4.0
5.0
6.0
0 8 10 12 13 14
% Capacity Reduction
Depth of Pit / Wall Height (ft)
Full Load Capacity Reduction (AGZ140-180E)
D istance = 6 f t D istance = 8 f t D istance = 10 f t
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
0 8 10 12 13 14
% Power Increase
Depth of Pit / Wall Height (ft)
Power Increase (AGZ140-211E)
Distance = 6 ft Distance = 8 ft Distance = 10 ft
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
0 8 10 12 13 14
% Capacity Reduction
Depth of Pit / Wall Height (ft)
Full Load Capacity Reduction (AGZ191-241E)
Distance = 6 ft Distance = 8 ft Distance = 10 ft
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
0 8 10 12 13 14
% Power Increase
Depth of Pit / Wall Height (ft)
Power Increase (AGZ226-241E)
Distance = 6 ft Distance = 8 ft Distance = 10 ft

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 12 www.DaikinApplied.com
Application Considerations
Figure 23: Typical Piping, Brazed-Plate Evaporator
Inlet Strainer Guidelines
An inlet water strainer kit must be installed in the chilled water
piping before the evaporator inlet. Several paths are available
to meet this requirement:
1. A factory installed option.
2. A field-installed kit shipped-loose with the unit that
consists of:
• Y-type area strainer with 304 stainless steel perforated
basket, Victaulic pipe connections and strainer cap.
• Extension pipe with two Schrader fittings that can be
used for a pressure gauge and thermal dispersion flow
switch. The pipe provides sufficient clearance from the
evaporator for strainer basket removal.
• ½-inch blowdown valve
• Two grooved clamps
Both are sized per Table 2 and with the pressure drop shown in
the Strainer Pressure Drop graph. Connection sizes are given
in the physical data section beginning on page 29.
3. A field-supplied strainer that meets specification and
installation requirements of the current Installation,
Operation and Maintenance Manual available at
www.DaikinApplied.com.
Figure 24: Factory Installed Strainer
Table 2: Strainer Data
Trailblazer™
Model
Strainer Size
in (mm)
Maximum
perforation size
in (mm)
Factory
Installed
Option
Field
Installed
Option
030-070 2.5 (64) 0.063 (1.6) Y Y
075-130 3.0 (76) 0.063 (1.6) Y Y
140-180 4.0 (102) 0.063 (1.6) Y Y
191-241 6.0 (152) 0.063 (1.6) Y Y
Figure 25: Strainer Pressure Drop
Water Flow Limitations
Constant Flow
The evaporator flow rates and pressure drops shown in Figure 31 on page 27 and Table 20 on page 28 are for full load design purposes. The maximum flow rate and pressure drop
are based on a 6°F temperature drop. Flow rates above the
maximum values will result in unacceptable temperature and
pressure drops and can cause excessive erosion, potentially
leading to failure.
The minimum flow and pressure drop is based on a full load
evaporator temperature drop of 16°F. Evaporator flow rates
Air
Vent
Flow
Switch
Vibration
Eliminators
Drain
Outlet
Inlet
P
Isolation
Valves
Strainer
WELDED PIPE CONNECTIONS ARE NOT ALLOWED
BETWEEN THE STRAINER AND EVAPORATOR DUE
TO THE CHANCE OF SLAG ENTERING THE EVAPORATOR
2.5 in
3.0 in
4.0 in
6.0 in.
2.0 in.
0.1
1.0
10.0
100.0
10.0 100.0 1000.0
Pressure Drop ( ft)
Flow Rate (gpm)

Application Considerations
www.DaikinApplied.com 13 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
below the minimum values can result in laminar flow causing
freeze-up problems, scaling and poor control.
Variable Flow
Reducing evaporator flow in proportion to load can reduce
system power consumption. The rate of flow change should be
a maximum of 10 percent of the flow per minute. For example,
if the maximum design flow is 200 gpm and it will be reduced to
a flow of 140 gpm, the change in flow is 60 gpm. Ten percent of
200 gpm equals 20 gpm change per minute, or a minimum of
three minutes to go from maximum to desired flow. The water
flow through the evaporator must remain between the minimum
and maximum values listed in Table 20 on page 28. If flow
drops below the minimum allowable, large reductions in heat
transfer can occur. If the flow exceeds the maximum rate,
excessive pressure drop and tube erosion can occur.
System Water Volume Considerations
All chilled water systems need adequate time to recognize
a load change, respond to the change and stabilize to avoid
undesirable short cycling of the compressors or loss of
temperature control. In air conditioning systems, the potential
for short cycling usually exists when the building load falls
below the minimum chiller plant capacity or on close-coupled
systems with very small water volumes. Some of the things
the designer should consider when looking at water volume
are the minimum cooling load, the minimum chiller plant
capacity during the low load period and the desired cycle time
for the compressors. Assuming that there are no sudden load
changes and that the chiller plant has reasonable turndown,
a rule of thumb of “gallons of water volume equal to two to
three times the chilled water gpm flow rate” is often used. A
storage tank may have to be added to the system to reach the
recommended system volume.
Evaporator Freeze Protection
Evaporator freeze-up can be a concern in the application of
air-cooled water chillers in areas experiencing below freezing
temperatures. To protect against freeze-up, insulation and
an electric heater are furnished with the evaporator. AGZ-E
chillers have an external plate heater and thermostat that
helps protect the evaporator down to -20°F (-29°C) ambient air
temperature. Although the evaporator is equipped with freeze
protection, it does not protect water piping external to the unit
or the evaporator itself if there is a power failure or heater
burnout, or if the chiller does not directly control the chilled
water pumps. Use one of the following recommendations for
additional protection:
1. If the unit will not be operated during the winter, drain
evaporator and chilled water piping and flush with glycol.
2. Add a year-round glycol solution to the chilled water
system to provide freeze protection. Freeze point should
be approximately 10°F(5.6°C) below minimum design
ambient temperature or 10°F below the lowest design
leaving water temperature, whichever is lower. The use
of glycol anti-freeze is generally considered the safest
protection against freeze-up, however, it will reduce the
performance of the unit, depending the concentration.
Take this into consideration during initial system design
and selection. On glycol applications, a minimum fluid
concentration should be based on Burst Protection limits.
3. The field addition of thermostatically controlled heat
tracing and insulation to exposed piping. Factory
insulation will have to be removed and replaced after
installation of the tracing.
4. Continuous circulation of water through the chilled water
piping and evaporator. (Dependent on power availability).
The evaporator heater cable or immersion heater is factory
wired to the 115 volt circuit in the control box. This power
should be supplied from a separate source to maximize unit
protection, but it can be supplied from the control circuit.
Operation of the heaters is automatic through the ambient
sensing thermostat that energizes the evaporator heaters for
protection against freezing. Unless the evaporator is drained in
the winter or contains an adequate concentration of anti-freeze,
the disconnect switch to the evaporator heater must be closed.
Conversely, do not apply heat to the evaporator if it is drained.
Chilled Water Pump
It is important that the chilled water pumps be wired to, and
controlled by, the chiller’s microprocessor. The chiller controller
has the capability to selectively send the signal to a pump
relay (by others) to start pump A or B or automatically alternate
pump selection and also has standby operation capability.
The controller will energize the pump whenever at least one
circuit on the chiller is enabled to run, whether there is a
call for cooling or not. This helps ensure proper unit start-up
sequence. The pump will also be turned on when the water
temperature stats equal to or goes below the Freeze Setpoint
for longer than a specified time to help prevent evaporator
freeze-up. Connection points are shown in the Field Wiring
Diagram on page 49 and page 50.
CAUTION
Adding glycol or draining the system is the recommended
method of freeze protection. If the chiller does not have
the ability to control the pumps and the water system is
not drained in temperatures below freezing, catastrophic
evaporator failure may occur.
Failure to allow pump control by the chiller may cause the
following problems:
1. If any device other than the chiller attempts to start the
chiller without first starting the pump, the chiller will lock
out on the No Flow alarm and require manual reset.
2. If the chiller evaporator water temperature drops below
the “Freeze setpoint” the chiller will attempt to start the
water pumps to avoid evaporator freeze. If the chiller
does not have the ability to start the pumps, the chiller
will alarm due to lack of water flow.
3. If the chiller does not have the ability to control
the pumps and the water system is not drained in
temperatures below freezing, the chiller may be subject
to catastrophic evaporator failure due to freezing. The
freeze rating of the evaporator is based on the immersion
heater and pump operation. The immersion heater itself
may not be able to properly protect the evaporator from
freezing without circulation of water.

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 14 www.DaikinApplied.com
Application Considerations
Low Ambient Operation
Compressor staging is adaptively determined by system load,
ambient air temperature, and other inputs to the MicroTech
®
III
control. The standard minimum ambient temperature is 32°F
(0°C). A low ambient option with fan VFD allows operation
down to -10°F (-23°C). The minimum ambient temperature
is based on still conditions where the wind is not greater
than 5 mph. Greater wind velocities will result in reduced
discharge pressure, increasing the minimum operating
ambient temperature. Field installed louvers are available and
recommended to help allow the chiller to operate effectively
down to the ambient temperature for which it was designed.
High Ambient Operation
Trailblazer
®
units for high ambient operation (105°F to 125°F,
40°C to 52°C) require the addition of the optional high ambient
package that includes a small fan with a filter in the air intake
to cool the control panel. All units with the optional VFD low
ambient fan control include the high ambient option.
Partial Heat Recovery
Partial heat recovery for Trailblazer
® chillers is achieved by
adding an auxiliary heat exchanger in each unit refrigerant
circuit between the compressors and the condenser coils.
The heat exchangers transfer the heat from the compressor
discharge gas to a separate water loop which can be used
for various heating applications. The heating recovery cycle
is only available when the chiller is running. The partial heat
recovery auxiliary heat exchanger can return water up to
155°F; however, this value cannot be set. The amount of heat
produced can be up to 50% of the nominal cooling capacity
and is dependent on the requested cooling load, the operating
temperatures, and the water flow rate through the auxiliary
heat exchangers. Please note, if potable water is desired, a
secondary heat exchanger in a separate water loop must be
used. Contact a local Daikin Applied sales representative for
information on specific applications.
Partial heat recovery components that are factory-supplied:
• Brazed plate heat exchangers - one in each circuit with
the water piped together in parallel for one inlet and one
outlet water connection, see Figure 32 for pressure drops.
• Insulation of heat exchangers and water piping at the unit.
• Separate temperature sensors for inlet and outlet water
piping at the heat exchangers.
• Connections for air vent at the outlet water piping and
drain at the inlet water piping.
• Immersion heater for each auxiliary heat exchanger for
freeze protection.
Required partial heat recovery field piping (see Figure 26) and
connections (see page 51) are listed below.
• An external 3-way valve or a variable speed pump in the
auxiliary heat exchanger water piping for modulation of
flow through the heat exchangers by the unit controller.
Heat recovery water loop pump must also be controlled
by the chiller controller.
• A cleanable strainer with perforations no larger than
0.063” (1.6 mm) diameter must be installed within 5 feet
(1500 mm) of pipe length from the heat exchanger inlet
and downstream of any welded connections, see Figure
25 for pressure drop.
• Water piping and other portions of the heat recovery
water loop must be insulated to prevent heat loss and
possible injury due to hot surfaces.
• A field-installed safety or relief valve on the water side is
required to prevent risks in case the water temperature
thermostat should fail.
• Separate 120 volt power supply for immersion heaters. A
junction box for a 120 Volt power connection is provided.
• A water tank and an additional water heater is suggested
in the heat recovery piping loop for initial water
temperature control and better loop stability. Typical loop
sizing guidance is water volume (in gallons) be greater
than or equal to two to three times the heat recovery
water flow rate (in gallons/minute).

Application Considerations
www.DaikinApplied.com 15 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Figure 26: Partial Heat Recovery Field Piping Schematic
Condenser Coil Options and Coating
Considerations
The standard coils on the Trailblazer
®
chiller are an all
aluminum alloy microchannel design with a series of flat
tubes containing multiple, parallel flow microchannels layered
between the refrigerant manifolds. The microchannel coils are
designed to withstand 1000+ hour acidified synthetic sea water
fog (SWAAT) test (ASTM G85-02) at 120°F (49°C) with 0%
fin loss and develop no leaks. The all-aluminum microchannel
coils provide superior longevity and durability for non-corrosive
applications.
Should the standard microchannel coil not meet the corrosion
requirements for the application, additional coil options are
available.
Aluminum fin/copper tube coils consist of 3/8 inch (10 mm)
seamless copper tubes mechanically bonded into plate-type
aluminum fins. The fins have full drawn collars to completely
cover the tubes. The aluminum fin/copper tube option provides
excellent durability in non-corrosive environments, and adds
the benefit of ease of field repair. This option is only available
for models AGZ030-070E.
Figure 27: Aluminum Fin/Copper Tube Coils
ELIMINATOR
VIBRATION
*FIELD INSTALLED HEAT RECOVERY LOOP
AGZE PACKAGE CHILLER WITH 
OPTIONAL HEAT RECOVERY
MICROCHANNEL ALUMINUM C OIL
5. WATER PIPING CONNECTIONS AT THE UNIT ARE 2.0" VICTAULIC.
4. FOR POTABLE WATER USE - A SECONDARY HEAT EXCHANGER IN A SEPARATE LOOP IS REQUIRED.
NOTES:
A VFD CONTROLLED WATER PUMP OR AN ELECTRONIC 3-WAY VALVE IS REQUIRED FOR TEMPERATURE CONTROL.1.
FIELD INSTALLED 3-WAY VALVE OR WATER PUMP VFD TO BE CONTROLLED BY 0-10 DCV OR 4-20 mA OUTPUT FROM2.
 THE CHILLER UNIT CONTROLLER.
GALLONS OF WATER VOLUME FOR THE HEAT RECOVERY PIPING LOOP SHOULD EQUAL 2 TO 3 TIMES THE3.
 HEAT RECOVERY LOOP GPM FLOW RATE.
VIBRATION
ELIMINATOR
0AD334549813
(USER OPTION)
WATER PUMP
FIELD INSTALLED
CONNECTIONS
CONTROLLED WATER PUMP
TERMINAL BOX FOR FIELD WIRING TO HEAT
BACK END OF UNIT
ARE NOT REQUIRED WHEN USING A VFD
3-WAY VALVE
HEAT LOAD
HEAT
SHUT OFF
THERMOMETER
EXCHANGER FREEZE PROTECTION HEATERS
ELECTRONIC
RECOVERY
SHUT OFF
CONNECTION
TEE
TEE CONNECTION & ELECTRONIC 3-WAY VALVE
1
FIELD
1
5
INLET WATER
STRAINER

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 16 www.DaikinApplied.com
Application Considerations
BlackFin

coils include aluminum fins pre-coated with a
durable phenolic epoxy coating. In addition to providing a
durable coating on the fin material, the BlackFin

coils provide
and epoxy barrier between the aluminum fin stock and the
copper tube, to prevent the galvanic corrosion that can occur
between the dissimilar metals. This option will provide a 1000+
hour salt spray rating per ASTM B117-90. The BlackFin®
option provides an economical solution for enhanced protection
in mildly corrosive environments. This option is only available
for models AGZ030-070E.
Copper-fin coils consist of 3/8 inch (10 mm) seamless copper
tubes mechanically bonded into plate-type copper fins. The fins
have full drawn collars to completely cover the tubes. Since the
fin and the tube materials are similar, the opportunity for
galvanic corrosion is eliminated. The copper fin/copper tube
option provides excellent longevity in marine environments;
however this option is not well suited for industrial or chemical
atmospheric contamination. This option is only available for
models AGZ030-070E.
Table 3: Coil/Coating Selection Matrix
Coil Option Non-Corrosive
1
Unpolluted Marine
2
Industrial
3
Combined Marine-Industrial
4
Standard Microchannel +++ - - -
Aluminum Fin/Copper Tube
5
+++ - - -
Copper Fin/Copper Tube
5
+++ +++ - -
BlackFin®
5
+++ + + -
Epoxy-coated Coils +++ +++ +++ ++
NOTE:
1. Non-corrosive environments may be estimated by the appearance of existing equipment in the immediate area where the chiller is to be placed.
2. Marine environments should take into consideration proximity to the shore as well as prevailing wind direction.
3. Industrial contaminants may be general or localized, based on the immediate source of contamination (i.e. diesel fumes due to proximity to a loading dock).
4. Combined marine-industrial are influenced by proximity to shore, prevailing winds, general and local sources of
contamination.
5. Available for models AGZ030-070E only.
Epoxy coil coating is a water-based extremely flexible
and durable epoxy polymer coating uniformly applied to all
coil surfaces through a multi-step, submerged electrostatic
coating process. Epoxy-coated condenser coils provide
a 6000+ hour salt spray resistance per ASTM B117-90,
applied to both the coil and the coil frames. The epoxy-
coated coils also receive a UV-resistant urethane top-coat
to provide superior resistance to degradation from direct
sunlight. This coil coating option provides the best overall
protection against corrosive marine, industrial or combined
atmospheric contamination. This coating option may be
applied to any of the untreated coil options offered, to
provide excellent longevity and resistance to corrosion.
Figure 28: Epoxy Coil Coating

Sound Data
www.DaikinApplied.com 17 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Background
Sound levels can be as important as unit cost and efficiency.
The inherently quiet scroll compressors used in Trailblazer®
chillers are coupled with precision engineering for industry-
leading sound levels.
AHRI has established standards to provide uniform methods
for the determination of the sound levels of equipment. For
large air-cooled chillers, it is AHRI Standard 370, Sound
Ratings of Large Outdoor Refrigeration and Air-Conditioning
Equipment. Data contained in this section are in accordance
with this standard.
“A” Weighting
Sound values may be represented several ways. One of the
more common forms is the “A” weighted value, which adds or
subtracts a specific amount to each center band frequency,
then logarithmically adds the values to establish a single
value. The “A” scale is used to represent how the human ear
receives sound. The amount added in each frequency band
directly corresponds to how sensitive the human ear is to each
frequency.
Table 4: “A” Scale Relative Response to Human Ear
Frequency, f , in Hz
31.5 631252505001K 2K 4K 8K16K
dB(A)−39.4−26.2−16.1−8.6−3.20 +1.2+1.0−1.1−6.6
Sound Pressure Levels - Full Load
Sound pressure is the sound level that can be measured at
some distance from the source. Sound pressure varies with
distance from the source and depends on the surroundings.
For example, a brick wall (a reflective surface) located 10
feet from a unit will affect the sound pressure measurements
differently than a brick wall at 20 feet. Sound pressure is
measured in decibels (dB).
All sound pressure data in the following pages are considered
typical of what can be measured in a free field with a handheld
sound meter, in the absence of any nearby reflective surfaces
except the floor under the unit. Sound pressure levels are
measured at 30 feet (10 meters) from the side of the unit at
100% load and standard AHRI conditions (per AHRI standard
550/590) of 95°F (35°C) ambient air temperature and 44°F
(7°C) leaving evaporator water temperatures for air-cooled
units.
Sound Power Levels
Sound power is a calculated quantity and cannot be measured
directly like sound pressure. Sound power is not dependent on
the surrounding environment or distance from the source, as
is sound pressure. It can be thought of as basic sound level
emanating from the unit without consideration of distance or
obstructions. Measurements are taken over a prescribed area
around the unit and the data is mathematically calculated to
give the sound power, dB. Acoustical consultants sometimes
use sound power octave band data to perform a detailed
acoustical analysis.
Figure 29: Sound Power vs. Sound Pressure
The data in Table 6 on page 19 and Table 10 on page 21
present sound power levels per AHRI Standard 370, “Sound
Rating of Large Outdoor Refrigerating and Air Conditioning
Equipment”. This standard was developed to establish uniform
methods of determining the sound power radiated by large
outdoor equipment. Measurements are taken over a prescribed
area around the unit and the data is mathematically calculated
to give the sound power, dB.
Sound Reduction due to Distance from
the Unit
The distance between a source of sound and the location of
the sound measurement plays an important role in minimizing
sound problems. Sound pressure can be calculated at any
distance from the unit if sound power and “Q,” the directionality
factor, are known. “Q” is a dimensionless number that
compensates for the type of sound reflection from the source.
For example, a unit sitting on a flat roof or ground with no other
reflective surfaces or attenuation due to grass, snow, etc.,
between source and receiver will have Q=2. See Figure 30 for
definitions of Q=1, Q=2, and Q=4.
Sound Source
(Sound Power)
Sound Pressure
Measured at 30ft (10m)
Sound Data

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 18 www.DaikinApplied.com
Sound Data
Figure 30: “Q” Reflective Sources Illustration
Once sound power and “Q” are known, sound pressure at any
distance from the unit can be calculated using the following
equation:
Lp = Lw - (20 log r) + (10 log Q) - 0.5
Where:
Lp = sound pressure
Lw = sound power
r = distance from unit in feet
Q = directionality factor
With Q=1, Unit suspended in space (theoretical condition), the
equation simplifies to:
Lp = Lw - (20 log r) -0.5
With Q=2, for a unit sitting on a flat roof or ground with no
adjacent vertical wall as a reflective surface, the equation
simplifies to:
Lp = Lw - (20 log r) + 2.5
With Q=4 for a unit sitting on a flat roof or ground with one
adjacent vertical wall as a reflective surface, the equation
simplifies to:
Lp = Lw - (20 log r) + 5.5
Results for typical distances and the two most usual cases of
“Q” are tabulated in Table 5.
Table 5: dB Conversion of Sound Power to Pressure
Distance from
Sound Source
ft (m)
DB Reduction from Sound Power at the Source
to Sound Pressure at Referenced Distance
Q=2 Q=4
30 (9) 27.1 24.0
50 (15) 31.6 28.5
75 (23) 35.1 32.0
100 (30) 37.6 34.5
150 (46) 41.1 38.0
200 (61) 43.6 40.5
300 (91) 47.6 44.0
Sound Data Notes
When referencing sound data below, please note:
1. Octave band readings are flat dB, overall is A-weighted.
2. Sound pressure data taken at 30 feet (9 meters) from
side of unit
3. Q=2, unit on flat surface with no adjacent wall.
Sound Data

Sound Data
www.DaikinApplied.com 19 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Table 6: 60 Hz Sound Power without Sound Insulation
Table 7: 60 Hz Sound Power with Sound Insulation
Model
Octave Band at Center Frequency Overall A-Weighted
63125 250 5001000200040008000Without Sound Insulation75% Load 50% Load 25% Load
30 92 91 88 87 83 78 73 68 88 87 85 84
35 92 91 89 87 83 78 73 68 88 87 85 84
40 92 91 90 88 84 79 74 69 89 88 86 85
45 93 92 91 89 85 79 74 69 90 89 87 86
50 93 93 91 89 85 79 74 69 90 89 87 86
55 93 93 93 89 86 81 76 71 91 90 88 87
60 94 93 94 89 86 81 76 71 91 90 88 87
65 95 94 94 89 87 81 76 71 92 91 89 88
70 95 95 94 89 87 81 76 71 92 91 90 89
75 95 95 95 89 87 81 76 71 92 91 89 88
80 95 95 95 89 87 81 76 71 92 91 89 88
90 94 95 92 91 89 83 81 81 93 92 90 89
100 93 95 92 92 89 83 82 82 94 93 91 90
110 93 96 92 92 90 84 84 82 95 94 92 91
120 93 96 92 92 90 84 84 82 95 94 92 91
130 94 97 93 93 91 85 85 84 96 95 93 92
140 95 98 93 94 93 87 86 85 97 96 94 93
150 96 98 95 94 95 90 88 85 99 98 96 95
161 97 98 96 95 95 91 90 86 99 98 96 95
170 96 98 96 94 91 88 88 85 97 96 94 93
180 96 98 96 94 91 88 88 85 97 96 94 93
191 96 98 96 94 91 88 88 85 97 96 94 93
211 97 98 97 94 94 90 89 85 99 98 96 95
226 98 98 98 94 94 90 90 86 99 98 96 95
241 98 98 98 95 96 90 90 86 100 99 97 96
Model
Octave Band at Center Frequency Overall A-Weighted
63125 250 5001000200040008000 With Sound Insulation 75% Load 50% Load 25% Load
30 84 84 83 84 77 75 74 70 85 84 82 81
35 84 84 83 84 77 75 74 70 85 84 82 81
40 84 84 83 84 77 75 74 70 85 84 82 81
45 85 85 85 86 80 77 75 70 87 86 84 83
50 85 85 85 86 80 77 75 70 87 86 84 83
55 85 85 85 86 80 77 75 70 87 86 84 83
60 85 85 85 86 80 77 75 70 87 86 84 83
65 86 85 85 86 80 77 75 70 87 86 84 83
70 88 85 85 86 80 77 75 70 87 86 85 84
75 88 85 86 86 81 81 77 70 88 87 85 84
80 88 85 87 86 83 81 77 71 88 88 86 85
90 88 87 87 86 83 80 77 71 88 87 85 84
100 90 86 86 86 83 80 78 71 88 87 85 84
110 90 86 87 86 82 79 76 71 88 87 85 84
120 91 85 88 86 82 81 79 72 89 88 86 85
130 91 85 88 86 82 81 80 72 89 88 86 85
140 91 86 90 87 82 81 80 72 89 88 86 85
150 92 87 91 87 84 84 82 72 90 90 88 87
161 93 87 91 87 85 84 82 72 91 90 88 87
170 92 88 89 89 86 82 80 74 91 90 88 87
180 92 88 89 89 86 82 80 74 91 90 88 87
191 92 88 89 89 86 82 80 74 91 90 88 87
211 93 88 90 89 89 84 81 74 93 92 90 89
226 94 88 91 89 89 84 82 75 93 92 90 89
241 94 88 91 90 91 84 82 75 94 93 91 90

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 20 www.DaikinApplied.com
Sound Data
Table 8: 60 Hz Sound Pressure (at 30 feet from side of unit) without Sound Insulation
Table 9: 60 Hz Sound Pressure (at 30 ft from side of unit) with Sound Insulation
Model
Octave Band at Center Frequency, 30 ft. from unit Overall A-Weighted
63 125 250 500 1000200040008000Without Sound Insulation75% Load50% Load25% Load
30 65 64 61 60 56 51 46 41 61 60 58 57
35 65 64 62 60 56 51 46 41 61 60 58 57
40 65 64 63 61 57 52 47 42 62 61 59 58
45 66 65 64 62 58 52 47 42 63 62 60 59
50 66 66 64 62 58 52 47 42 63 62 60 59
55 66 66 66 62 59 54 49 44 64 63 61 60
60 67 66 67 62 59 54 49 44 64 63 61 60
65 68 67 67 62 60 54 49 44 65 64 62 61
70 68 68 67 62 60 54 49 44 65 64 63 62
75 68 68 68 62 60 54 49 44 65 64 62 61
80 66 63 63 63 62 56 53 53 66 65 63 62
90 67 67 67 64 62 56 54 54 67 66 64 63
100 66 68 65 65 62 56 57 55 67 66 64 63
110 66 69 67 65 61 55 55 55 67 66 64 63
120 68 67 67 65 61 59 60 57 68 67 65 64
130 67 68 68 64 61 60 60 55 68 67 65 64
140 68 69 69 65 61 60 61 56 69 68 66 65
150 69 70 70 65 62 62 62 56 70 69 67 66
161 69 70 70 65 62 63 62 56 70 69 67 66
170 69 71 69 67 64 61 60 58 70 69 67 66
180 69 71 69 67 64 61 61 58 70 69 67 66
191 69 71 69 67 64 61 61 58 70 69 67 66
211 70 71 70 67 66 62 62 58 71 70 68 67
226 70 71 70 67 66 62 62 59 71 70 68 67
241 70 71 70 68 68 62 62 59 72 71 69 68
Model
Octave Band at Center Frequency, 30 ft. from unit Overall A-Weighted
63 125 250 500 1000200040008000 With Sound Insulation75% Load50% Load25% Load
30 57 57 56 57 50 48 47 43 58 57 55 54
35 57 57 56 57 50 48 47 43 58 57 55 54
40 57 57 56 57 50 48 47 43 58 57 55 54
45 58 58 58 59 53 50 48 43 60 59 57 56
50 58 58 58 59 53 50 48 43 60 59 57 56
55 58 58 58 59 53 50 48 43 60 59 57 56
60 58 58 58 59 53 50 48 43 60 59 57 56
65 59 58 58 59 53 50 48 43 60 59 57 56
70 61 58 58 59 53 50 48 43 60 59 58 57
75 61 58 59 59 54 54 50 43 61 60 58 57
80 61 59 59 59 55 54 50 44 61 60 58 57
90 61 60 60 59 56 53 50 44 61 60 58 57
100 63 59 59 59 56 53 51 44 61 60 58 57
110 63 59 60 59 55 52 49 44 61 60 58 57
120 64 58 61 59 55 54 51 45 61 61 59 58
130 63 58 61 59 56 54 51 45 62 61 59 58
140 64 59 62 60 56 54 53 45 63 62 60 59
150 65 60 63 60 57 56 54 45 63 63 61 60
161 65 60 63 60 58 56 54 45 64 63 61 60
170 65 61 62 62 59 55 53 47 64 63 61 60
180 65 61 62 62 60 56 54 47 64 63 61 60
191 65 61 62 62 60 56 54 47 64 63 61 60
211 66 61 63 62 62 57 55 47 66 65 63 62
226 66 61 63 62 62 57 55 48 66 65 63 62
241 66 61 63 63 63 57 55 48 67 66 64 63

Sound Data
www.DaikinApplied.com 21 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Table 10: 50 Hz Sound Power
Table 11: 50 Hz Sound Power with Sound Insulation
Model
Octave Band at Center Frequency Overall A-Weighted
63 125 250 500 1000 200040008000Without Sound Insulation75% Load50% Load25% Load
30 89 88 85 84 80 75 70 65 85 84 82 81
35 89 88 85 84 80 75 70 65 85 84 82 81
40 89 88 86 84 80 75 70 65 85 84 82 81
45 89 88 87 85 81 76 71 66 86 85 83 82
50 90 89 88 86 82 76 71 66 87 86 84 83
55 90 90 88 86 82 76 71 66 87 86 84 83
60 90 90 90 86 83 78 73 68 88 87 85 84
65 91 90 91 86 83 78 73 68 88 87 85 84
70 92 91 91 86 84 78 73 68 89 88 87 86
75 92 92 91 86 84 78 73 68 89 89 86 85
80 92 92 91 86 84 78 73 68 89 89 86 85
90 91 92 88 88 86 80 78 78 90 90 87 86
100 90 92 88 89 86 80 79 79 91 91 88 87
110 90 93 88 89 87 81 81 79 91 91 88 87
120 90 93 88 89 87 81 81 79 91 91 88 87
130 91 94 89 90 88 82 82 80 92 92 89 88
140 92 95 89 91 90 84 83 81 94 94 91 90
150 93 95 91 91 92 87 85 81 95 95 92 91
161 94 95 92 92 92 88 86 82 95 95 92 91
170 93 95 93 90 87 84 84 82 94 94 91 90
180 93 95 93 91 88 85 84 82 94 94 91 90
191 93 95 93 91 88 85 85 82 94 94 91 90
211 94 95 93 91 91 87 85 81 95 95 92 91
226 95 95 94 91 91 87 86 82 95 95 92 91
241 95 95 94 92 93 87 86 82 96 96 93 92
Model
Octave Band at Center Frequency
63 125 250 500 1000 200040008000 With Sound Insulation75% Load50% Load25% Load
30 81 81 80 81 74 72 71 67 82 81 79 78
35 81 81 80 81 74 72 71 67 82 81 79 78
40 81 81 80 81 74 72 71 67 82 81 79 78
45 82 82 82 83 77 74 72 67 84 83 81 80
50 82 82 82 83 77 74 72 67 84 83 81 80
55 82 82 82 83 77 74 72 67 84 83 81 80
60 82 82 82 83 77 74 72 67 84 83 81 80
65 83 82 82 83 77 74 72 67 84 83 81 80
70 85 82 82 83 77 74 72 67 84 83 82 81
75 85 82 83 83 78 78 74 67 85 84 82 81
80 85 83 83 83 80 78 74 68 85 85 83 82
90 85 84 84 83 80 77 74 68 85 84 82 81
100 87 83 83 83 80 77 75 68 85 84 82 81
110 87 83 84 83 79 76 73 68 85 84 82 81
120 88 82 85 83 79 78 76 69 86 85 83 82
130 88 82 85 83 79 78 77 69 86 85 83 82
140 88 83 87 84 79 78 77 69 86 85 83 82
150 89 84 88 84 81 81 79 69 88 87 85 84
161 90 85 88 84 82 81 79 69 88 87 85 84
170 89 85 86 86 83 79 77 71 88 87 85 84
180 89 85 86 86 83 79 77 71 88 87 85 84
191 89 85 86 86 83 79 77 71 88 87 85 84
211 90 85 87 86 86 81 78 71 89 89 87 86
226 91 85 88 86 86 81 79 72 90 89 87 86
241 91 85 88 87 88 81 79 72 91 90 88 87

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 22 www.DaikinApplied.com
Sound Data
Table 12: 50 Hz Sound Pressure (at 30 feet from side of unit)
Table 13: 50 Hz Sound Pressure (at 30 ft from side of unit) with Sound Insulation
Model
Octave Band at Center Frequency, 30 ft. from unit Overall A-Weighted
63 125 250 500 1000200040008000Without Sound Insulation75% Load50% Load25% Load
30 62 61 58 57 53 48 43 38 58 57 55 54
35 62 61 59 57 53 48 43 38 58 57 55 54
40 62 61 60 58 54 49 44 39 59 58 56 55
45 63 62 61 59 55 49 44 39 60 59 57 56
50 63 63 61 59 55 49 44 39 60 59 57 56
55 63 63 63 59 56 51 46 41 61 60 58 57
60 64 63 64 59 56 51 46 41 61 60 58 57
65 65 64 64 59 57 51 46 41 62 61 59 58
70 65 65 64 59 57 51 46 41 62 61 60 59
75 65 65 65 59 57 51 46 41 62 61 59 58
80 63 60 60 60 59 53 50 49 63 62 60 59
90 64 64 64 61 59 53 51 51 64 63 61 60
100 63 65 62 62 59 53 54 52 64 63 61 60
110 63 66 64 62 58 52 52 52 64 63 61 60
120 65 64 64 62 58 56 57 54 65 64 62 61
130 64 65 65 61 58 57 57 52 65 64 62 61
140 65 66 66 62 58 57 58 53 66 65 63 62
150 66 67 67 62 59 59 59 53 67 66 64 63
161 66 67 67 62 59 60 59 53 67 66 64 63
170 66 68 66 64 61 58 57 55 67 66 64 63
180 66 68 66 64 61 58 58 55 67 66 64 63
191 66 68 66 64 61 58 58 55 67 66 64 63
211 67 68 67 64 63 59 59 55 68 67 65 64
226 67 68 67 64 63 59 59 56 68 67 65 64
241 67 68 67 65 64 59 59 56 69 68 66 65
Model
Octave Band at Center Frequency, 30 ft. from unit
63 125 250 500 1000 200040008000 With Sound Insulation75% Load50% Load25% Load
30 54 54 53 54 47 45 44 40 55 54 52 51
35 54 54 53 54 47 45 44 40 55 54 52 51
40 54 54 53 54 47 45 44 40 55 54 52 51
45 55 55 55 56 50 47 45 40 57 56 54 53
50 55 55 55 56 50 47 45 40 57 56 54 53
55 55 55 55 56 50 47 45 40 57 56 54 53
60 55 55 55 56 50 47 45 40 57 56 54 53
65 56 55 55 56 50 47 45 40 57 56 54 53
70 58 55 55 56 50 47 45 40 57 56 55 54
75 58 55 56 56 51 51 47 40 58 57 55 54
80 58 55 56 56 53 51 47 41 58 58 56 55
90 58 57 57 56 53 50 47 41 58 57 55 54
100 60 56 56 56 53 50 48 41 58 57 55 54
110 60 56 57 56 52 49 46 41 58 57 55 54
120 61 55 58 56 52 51 48 42 58 58 56 55
130 61 55 58 56 53 51 48 42 59 58 56 55
140 61 56 59 57 53 51 50 42 60 59 57 56
150 62 57 60 57 54 53 51 42 60 60 57 57
161 62 57 60 57 55 53 51 42 61 60 58 57
170 62 58 59 59 56 52 50 44 61 60 58 57
180 62 58 59 59 57 53 51 44 61 60 58 57
191 62 58 59 59 57 53 51 44 61 60 58 57
211 63 58 60 59 59 54 52 44 63 62 60 59
226 63 58 60 59 59 54 52 45 63 62 60 59
241 63 58 60 60 60 54 52 45 63 63 61 60

Selection Procedure
www.DaikinApplied.com 23 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Selection with Inch-Pound (IP) units
Trailblazer
®
chillers are ideal for a wide range of applications
and operating conditions. The performance tables beginning
on page 25 cover the standing application rating conditions
of the current AHRI Standard 550/590. The tables are based
on a 10°F (5.5°C) temperature drop through the evaporator.
Adjustment factors for applications having other than a 10°F
(5.5°C) drop can be found in Table 16 on page 24.
The minimum leaving chilled water temperature setpoint
without glycol is 40°F (4°C). For brine selections, see Table
14 and Table 15 on page 24 for glycol adjustment factors.
Ratings are based on a 0.0001 ft
2
x hr x ºF/Btu fouling factor in
the evaporator at sea level operation. For other fouling factors,
different Delta-Ts, or altitude correction factors see Table 16 on
page 24. For applications outside the catalog ratings, please
contact a local Daikin Applied sales representative.
Selection example
Given:
• 50 tons minimum
• 95°F ambient temperature
• 120 gpm, 54°F to 44°F chilled water
• 0.0001 evaporator fouling factor
1. From Table 17 on page 25, an AGZ055E at the given
conditions will produce 51.8 tons with a unit kW input of 59.6
and a unit EER of 10.4.
2. Use the following formula to calculate any unknown
elements (water only):
3. Determine the evaporator pressure drop. Using Figure 31
on page 27, enter at about 124 gpm and follow up to
the AGZ055E line intersect. Read horizontally to obtain an
evaporator pressure drop of 13 feet of water.
Selection example using ethylene glycol
Given:
• 44 tons minimum
• 95°F ambient air temperature
• 54°F - 44°F chilled water temperature
• 0.0001 evaporator fouling factor
• Protect from freezing down to 0°F
1. From Table 14 on page 24, select an ethylene glycol
concentration of 40% to protect against freezing at 0°F.
2. At 40% ethylene glycol, the adjustment factors are:
• Capacity = 0.981
• kW = 0.993
• GPM = 1.132
• Pressure Drop = 1.557
3. Select the AGZ050E from Table 17 on page 25 and
correct with 40% ethylene glycol factors.
4. Correct capacity = 0.981 X 48.3 tons = 47.3 tons
5. Correct kW = 0.993 X 54.6 kW = 54.2 kW
6. Calculate chilled water flow:
• Water flow @ corrected capacity
• Glycol flow (at 40% solution)
Determine the evaporator pressure drop. Using Figure 31
on page 27, enter at 128.5 gpm (water) and follow up to
the AGZ050E line intersect. Read horizontally to obtain an
evaporator pressure drop of 17 feet. Correct the pressure drop
for 40% solution = 1.557 x 17 feet = 26.5 feet for ethylene
glycol using Table 14 on page 24.
Selection with SI units
Use the SI tables and the same procedures as with IP units.
Use the following formula to calculate any missing elements
(water only):













Selection Procedure

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 24 www.DaikinApplied.com
Selection Procedure
Ethylene & Propylene Glycol Factors
Trailblazer® units can operate with a leaving chilled fluid
temperature range of 20°F (-7°C) to 65°F (18°C). A glycol
solution is required when leaving chilled fluid temperature
is below 40°F (4°C). The use of glycol will reduce the
performance of the unit depending on concentration.
NOTE: Ethylene and propylene glycol ratings are outside
the scope of the current AHRI Standard 550/590
certification program.
Table 14: Ethylene Glycol Correction Factors
Table 15: Propylene Glycol Correction Factors
Altitude Correction Factors
Performance tables are based at sea level. Elevations
other than sea level affect the performance of the unit.
The decreased air density will reduce condenser capacity
consequently reducing the unit’s performance. For
performance at elevations other than sea level refer to Table
16.
Evaporator Temperature Drop Factors
Performance tables are based on a 10°F (5°C) temperature
drop through the evaporator. Adjustment factors for
applications with temperature ranges from 6°F to 16°F (3.3°C
to 8.9°C) are in Table 16. Temperature drops outside this
6°F to 16°F (3.3°C to 8.9°C) range can affect the control
system’s capability to maintain acceptable control and are not
recommended.
Table 16: Capacity and Power Derates
NOTE: Derate factors for models with remote evaporators
can be found in the current installation manual at
www.DaikinApplied.com.
AHRI Certification
Performance on all 60Hz standard packaged models are
certified per AHRI standard 550/590. Chillers that are 50Hz or
that have an optional remote evaporator or include the partial
heat recovery option are outside the scope of the AHRI rating
program.
% E.G.
Freeze Point
Capacity Power Flow
Pressure
Drop° F ° C
10 26 -3.3 0.997 0.999 1.028 1.090
20 18 -7.8 0.993 0.997 1.059 1.216
30 7 -14 0.987 0.995 1.094 1.379
40 -7 -22 0.981 0.993 1.132 1.557
50 -28 -33 0.972 0.99 1.174 1.811
% P.G.
Freeze Point
Capacity Power Flow
Pressure
Drop° F ° C
10 26 -3.3 0.995 0.998 1.011 1.025
20 19 -7.8 0.988 0.995 1.03 1.15
30 9 -14 0.979 0.992 1.056 1.375
40 -5 -22 0.968 0.988 1.09 1.701
50 -27 -33 0.955 0.983 1.131 2.128
Altitude
Water
Delta T
Fouling Factor
0.0001 (0.0176)0.00025 (0.044)0.00075 (0.132)0.00175 (0.308)
°F°CCap.PowerCap.PowerCap.PowerCap.Power
Sea
Level
63.30.9780.9930.9750.9910.9630.9870.9400.980
84.40.9890.9960.9860.9940.9730.9900.9500.983
105.61.0001.0000.9960.9990.9840.9940.9610.987
126.71.0091.0031.0051.0010.9930.9970.9690.990
147.71.0181.0041.0141.0031.0020.9990.9780.991
168.91.0251.0071.0211.0061.0091.0010.9850.994
2000
feet
63.30.9771.0010.9731.0000.9610.9960.9380.989
84.40.9871.0060.9841.0040.9711.0000.9480.993
105.60.9981.0090.9951.0070.9821.0030.9590.996
126.71.0071.0111.0041.0100.9911.0060.9670.998
147.71.0141.0141.0111.0130.9981.0090.9741.001
168.91.0221.0161.0181.0141.0051.0100.9811.003
4000
feet
63.30.9731.0110.9701.0100.9571.0060.9350.998
84.40.9841.0140.9801.0130.9681.0090.9451.001
105.60.9951.0190.9911.0170.9791.0130.9551.005
126.71.0041.0211.0001.0200.9871.0160.9641.008
147.71.0111.0241.0071.0230.9941.0180.9711.011
168.91.0181.0271.0141.0261.0021.0210.9781.014
6000
feet
63.30.9691.0210.9661.0200.9541.0160.9311.008
84.40.9801.0260.9771.0240.9641.0200.9421.013
105.60.9891.0290.9861.0270.9731.0230.9501.015
126.70.9981.0330.9951.0310.9821.0270.9591.020
147.71.0071.0361.0041.0340.9911.0300.9671.022
168.91.0141.0371.0111.0360.9981.0310.9741.024

Performance Data
www.DaikinApplied.com 25 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Table 17: 60 Hz Part Load Performance Data (IP) Table 18: 60 Hz Part Load Performance Data (IP)
Model % Load Tons kW EER IPLV
030
100 28.10 32.98 10.30
15.10
75 21.08 19.43 13.03
50 14.05 10.36 16.29
25 7.03 4.68 18.03
035
100 34.90 40.95 10.30
15.40
75 26.18 23.87 13.15
50 17.45 12.55 16.67
25 8.73 5.57 18.78
040
100 39.20 41.17 11.42
16.50
75 29.40 24.45 14.43
50 19.60 13.21 17.80
25 9.800 6.160 19.09
045
100 42.60 46.50 10.98
16.40
75 31.95 26.84 14.27
50 21.30 14.33 17.82
25 10.65 6.620 19.29
050
100 48.30 54.58 10.61
16.00
75 36.23 31.28 13.88
50 24.15 16.70 17.34
25 12.08 7.670 18.87
055
100 51.80 59.62 10.42
15.90
75 38.85 34.64 13.46
50 25.90 18.00 17.26
25 12.95 7.940 19.57
060
100 57.00 64.89 10.53
15.80
75 42.75 36.67 13.98
50 28.50 20.08 17.02
25 14.25 9.340 18.30
065
100 58.70 66.50 10.59
15.80
75 44.03 38.08 13.87
50 29.35 20.65 17.05
25 14.68 9.800 17.97
070
100 65.10077.320 10.10
15.80
75 48.82543.260 13.54
50 32.55022.670 17.23
25 16.27510.370 18.83
075
100 74.25 81.74 10.90
15.84
75 55.69 47.46 14.10
50 37.12 26.53 16.80
25 18.56 11.84 18.80
080
100 78.62 87.12 10.83
15.86
75 58.96 50.39 14.04
50 39.31 27.86 16.93
25 19.65 12.67 18.61
090
100 86.82 98.21 10.61
15.73
75 65.12 56.60 13.81
50 43.41 30.85 16.88
25 21.71 14.00 18.60
100
100 101.5 115.6 10.54
15.99
75 76.14 64.71 14.12
50 50.76 35.34 17.23
25 25.38 16.58 18.37
Model % Load Tons kW EER IPLV
110
100 111.6 125.8 10.64
15.87
75 83.67 71.84 13.98
50 55.78 39.38 17.00
25 27.89 17.88 18.72
120
100 123.7 140.9 10.53
15.88
75 92.78 79.10 14.08
50 61.85 43.73 16.97
25 30.93 20.00 18.56
130
100 130.9 153.6 10.22
15.77
75 98.14 84.70 13.90
50 65.43 46.49 16.89
25 32.71 21.11 18.59
140
100 142.8 159.0 10.77
16.25
75 107.1 92.29 13.92
50 71.38 48.11 17.80
25 35.69 22.52 19.02
150
100 149.8 167.3 10.74
15.88
75 112.4 96.23 14.01
50 74.90 53.00 16.96
25 37.45 23.87 18.83
161
100 156.2 180.7 10.37
15.83
75 117.1 102.3 13.74
50 78.09 54.50 17.19
25 39.04 25.38 18.46
170
100 163.1 196.4 9.960
16.13
75 122.3 105.4 13.93
50 81.54 56.25 17.39
25 40.77 24.93 19.63
180
100 181.9 222.8 9.790
16.12
75 136.4 117.3 13.95
50 90.93 62.60 17.43
25 45.46 28.17 19.37
191
100 190.7 219.2 10.44
16.19
75 143.1 120.0 14.31
50 95.37 66.45 17.22
25 47.69 29.49 19.41
211
100 197.4 230.5 10.28
16.51
75 148.1 124.1 14.32
50 98.71 66.87 17.71
25 49.36 29.34 20.19
226
100 212.1 234.8 10.84
16.65
75 159.1 133.5 14.30
50 106.1 71.14 17.89
25 53.03 30.72 20.72
241
100 230.0 269.5 10.24
16.43
75 172.5 146.7 14.12
50 115.0 77.66 17.77
25 57.50 34.56 19.97
Performance Data

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 26 www.DaikinApplied.com
Performance Data
Table 19: 60Hz Part Load Performance Data (IP) with High Efficiency Fan VFD option
Model % Load Tons kW EER IPLV
075
100 74.25 82.50 10.80
17.61
75 55.69 44.95 14.87
50 37.12 23.07 19.31
25 18.56 10.40 21.43
080
100 78.62 87.93 10.73
17.30
75 58.96 47.94 14.76
50 39.31 24.88 18.96
25 19.65 11.48 20.54
090
100 86.82 98.17 10.61
17.09
75 65.12 54.74 14.27
50 43.41 27.54 18.92
25 21.71 12.60 20.67
100
100 101.7 116.7 10.46
16.95
75 76.28 63.40 14.44
50 50.85 32.80 18.60
25 25.43 15.20 20.07
110
100 111.6 125.8 10.64
17.53
75 83.67 68.70 14.61
50 55.78 34.53 19.39
25 27.89 15.70 21.32
120
100 123.7 142.9 10.39
17.25
75 92.78 76.20 14.61
50 61.85 39.30 18.89
25 30.93 17.73 20.93
130
100 130.9 152.1 10.32
17.24
75 98.14 81.91 14.38
50 65.43 41.18 19.06
25 32.71 18.71 20.98
140
100 142.8 160.5 10.67
17.24
75 107.1 91.94 13.98
50 71.38 44.42 19.28
25 35.69 19.89 21.53
Model % Load Tons kW EER IPLV
150
100 149.8 168.1 10.69
17.16
75 112.4 94.43 14.28
50 74.90 47.92 18.76
25 37.45 20.67 21.74
161
100 156.2 181.5 10.33
16.66
75 117.1 99.58 14.11
50 78.09 51.38 18.24
25 39.04 23.18 20.21
170
100 163.1 197.3 9.920
17.21
75 122.3 101.9 14.41
50 81.54 52.07 18.79
25 40.77 22.57 21.67
180
100 181.9 221.7 9.840
16.90
75 136.4 115.8 14.13
50 90.93 59.10 18.46
25 45.46 25.61 21.30
191
100 190.7 220.4 10.38
17.42
75 143.1 121.4 14.14
50 95.37 59.40 19.27
25 47.69 25.41 22.52
211
100 197.4 230.4 10.28
17.43
75 148.1 125.3 14.18
50 98.71 61.27 19.33
25 49.36 26.60 22.27
226
100 212.1 237.1 10.74
17.39
75 159.1 133.4 14.31
50 106.1 66.00 19.29
25 53.03 29.50 21.57
241
100 230.0 269.4 10.25
17.19
75 172.5 145.0 14.28
50 115.0 73.04 18.90
25 57.50 32.01 21.56

Pressure Drop Data
www.DaikinApplied.com 27 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Figure 31: Pressure Drop Curves - Unit Evaporator (Reference Data Table 20, next page)
Figure 32: Pressure Drop Curves - Heat Recovery Auxilliary Heat Exchangers (Reference Data Table 21, next page)
A
A
A
B
B
B
C
C
C
D
D
D
E
E
E
F
F
F
G
G
G
H
H
H
I
I
I
J
J
J
K
K
K
L
L
L
M
M
M
N
N
N
O
O
O
P
P
P
Q
Q
Q
S
S
S
T
T
T
U
U
U
V
V
V
W
W
W
X
X
X
Y
Y
Y
1
10
100
10 100 1000
Differential Pressure (ft)
Flow Rate (gpm)
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
1
1
2
2
3
3
4
4
5
5
6
6
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
20.0
0.0 50.0 100.0 150.0 200.0 250.0
Differential Pressure (ft)
Flow Rate (gpm)
Pressure Drop Data

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 28 www.DaikinApplied.com
Pressure Drop Data
Table 20: Pressure Drop Data - Unit Evaporator
Table 21: Pressure Drop Data - Heat Recovery Auxilliary Braze Plate Heat Exchangers
Part Load Flow System Only Full Load Flow System Only Fixed and Variable Flow Systems
Minimum Flow Rate
2
Minimum Flow Rate
1
Nominal Flow Rate Maximum Flow Rate
Curve
Ref.
Model
IP SI IP SI IP SI IP SI
GPM DP ft.lpsDP kpa GPM DP ft.lpsDP kpaGPM DP ft.lpsDP kpaGPM DP ft.lpsDP kpa
A 030E 27.0 1.7 1.7 5.1 42.2 4.0 2.7 12.0 67.4 9.8 4.3 29.4 112.426.0 7.1 77.7
B 035E 33.5 2.4 2.1 7.1 52.4 5.6 3.3 16.7 83.813.7 5.3 40.9 139.636.4 8.8 108.7
C 040E 37.1 2.5 2.3 7.4 57.9 5.8 3.7 17.3 92.614.2 5.8 42.5 154.437.7 9.7 112.6
D 045E 40.9 2.3 2.6 6.8 63.9 5.3 4.0 15.8 102.213.2 6.5 39.4 170.434.410.8102.7
E 050E 46.4 2.7 2.9 7.9 72.5 6.2 4.6 18.5 115.915.2 7.3 45.3 193.240.012.2119.6
F 055E 49.7 2.3 3.1 7.0 77.7 5.5 4.9 16.3 124.313.4 7.8 40.0 207.235.613.1106.2
G 060E 54.0 2.3 3.4 6.9 84.3 5.4 5.3 16.1 134.913.1 8.5 39.3 224.834.714.2103.6
H 065E 55.5 2.4 3.5 7.3 86.7 5.7 5.5 17.0 138.713.9 8.8 41.4 231.236.614.6109.3
I 070E 61.5 3.0 3.9 8.8 96.1 6.9 6.1 20.6 153.816.9 9.7 50.4 256.444.516.2133.0
J 075E 69.8 1.2 4.4 3.6 109.12.8 6.9 8.4 174.56.9 11.0 20.5 290.818.218.3 54.3
K 080E 73.8 1.2 4.7 3.7 115.42.9 7.3 8.6 184.67.1 11.6 21.3 307.618.919.4 56.6
L 090E 80.1 1.4 5.1 4.3 125.13.4 7.9 10.1 200.28.3 12.6 24.8 333.622.121.0 66.1
M 100E 92.4 1.3 5.8 4.0 144.33.2 9.1 9.5 230.97.8 14.6 23.3 384.820.824.3 62.2
N 110E 102.0 1.4 6.4 4.2 159.53.3 10.1 9.9 255.18.2 16.1 24.4 425.221.626.8 64.6
O 120E 113.1 1.5 7.1 4.5 176.73.6 11.1 10.7 282.78.8 17.8 26.4 471.223.529.7 70.3
P 130E 119.5 1.5 7.5 4.4 186.83.5 11.8 10.4 298.88.6 18.9 25.7 498.022.931.4 68.3
Q 140E 128.9 1.7 8.1 5.1 201.54.0 12.7 12.1 322.39.9 20.3 29.7 537.226.433.9 79.0
R 150E 136.1 1.7 8.6 4.9 212.73.9 13.4 11.7340.39.8 21.5 29.2 567.226.335.8 78.4
S 161E 143.6 1.8 9.1 5.5 224.44.4 14.2 13.0 359.010.822.7 32.4 598.429.137.8 87.0
T 170E 154.1 1.9 9.7 5.6 240.84.5 15.2 13.4 385.211.224.3 33.4 642.030.240.5 90.2
U 180E 164.8 2.3
10.4 6.9 257.65.3 16.2 15.9 412.112.826.0 38.3 686.833.543.3 99.9
V 191E 179.6 2.5 11.3 7.5 280.64.8 17.7 14.3 449.09.9 28.3 29.6 748.524.747.2 74.0
W 211E 187.2 2.7 11.8 8.0 292.55.1 18.4 15.2 468.010.629.5 31.7 780.226.549.1 79.1
X 226E 196.8 1.9 12.4 5.6 307.53.9 19.4 11.6492.08.8 31.0 26.4 816.722.551.5 67.3
Y 241E 216.8 2.2 13.7 6.5 338.84.6 21.3 13.7 542.010.534.1 31.5 903.527.356.9 81.5
Minimum Flow Nominal Flow Maximum Flow
Ref.Unit Model(GPM)Dp (ft) l/sDP kpa (GPM)Dp (ft) l/sDP kpa (GPM)Dp (ft) l/sDP kpa
1
AGZ075
21 0.8 1.3 2.3 42 2.7 2.7 8.1 120 18.07.6 53.8AGZ080
AGZ090
2
AGZ100
30 1.1 1.9 3.2 60 3.2 3.8 9.6 132 18.08.3 53.8AGZ110
AGZ120
3
AGZ130
40 1.1 2.5 3.3 80 3.7 5.0 11.1 195 18.012.353.8
AGZ140
4
AGZ150
46 1.2 2.9 3.7 92 4.0 5.8 12.0 205 18.012.953.8
AGZ161
5
AGZ170
57 1.6 3.6 4.7 114 5.3 7.2 15.8 230 18.014.553.8
AGZ180
AGZ191
AGZ211
6
AGZ226
70 1.8 4.4 5.3 140 6.4 8.8 19.1 250 18.015.853.8
AGZ241

Physical Data - Packaged Unit
www.DaikinApplied.com 29 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Physical Data - Packaged Unit
Table 22: Physical Data - AGZ030E - AGZ040E
Table 23: Physical Data - AGZ045E - AGZ055E
NOTE: 1) Models 030-060: Fan Motor hp = 2.0 for 380V/60Hz, 575V/60Hz, & 400V/50Hz.
All Models: Fan RPM = 950 for 400V/50Hz. Airflow =(0.83 x 60Hz Airflow) for 400V/50Hz.
2) Water connection shown is nominal pipe size.
3) Brazed plate evaporators do not have drain or vent connections integral to the heat exchanger. The connections must be installed in the field inlet and
outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual, available on www.DaikinApplied.com.
Physical Data
AGZ-E (Microchannel Packaged Chiller)
AGZ030E AGZ035E AGZ040E
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2
BASIC DATA
Unit Operating Charge lbs (kg) - Sealed Filter Drier 15 (16.8) 15 (16.8) 14 (6.4) 14 (6.4) 21 (9.5) 21 (9.5)
- Replaceable Core Filter Drier17 (7.7) 17 (7.7) 16 (7.3) 16 (7.3) 23 (10.5) 23 (10.5)
COMPRESSORS, SCROLL, HERMETIC
Nominal HP 7.5 / 7.5 7.5 / 7.5 9.0 / 9.0 10.0 / 10.0 10.0 / 10.0 10.0 / 10.0
Oil charge per Compressor , oz (g)
85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)
85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)
Staging, 4 Stages (If Circuit is in Lead) 0-25-50-75-1000-25-50-75-1000-23-50-73-1000-27-50-77-1000-25-50-75-1000-25-50-75-100
CONDENSER, MICROCHANNEL
Coil Inlet Face Area, sq. ft. (sq. m.) 24.9 (2.3) 24.9 (2.3) 24.9 (2.3) 24.9 (2.3) 49.8 (4.6) 49.8 (4.6)
Rows Deep/Fins Per Inch 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21
CONDENSER FANS, DIRECT DRIVE PROPELLER
# of Fans per Circuit - Fan Diameter in (mm) 2 - 30 (762)2 - 30 (762)2 - 30 (762)2 - 30 (762)2 - 30 (762) 2 - 30 (762)
Fan Motor, hp (kW) (for 208V,230V,460V/60Hz)
1
1.5 (1.1) 1.5 (1.1) 1.5 (1.1)
Fan & Motor RPM (for all 60Hz)
1
1140 1140 1140
Airflow, cfm (l/s)
1
34,000 (16,047) 34,000 (16,047) 40,400 (19,067)
EVAPORATOR, BRAZED PLATE
3
Dry Weight lbs (kg) 84 (38.1) 91 (41.3) 98 (44.5)
Water Volume, gallons (liters) 1.6 (6.1) 1.8 (6.8) 1.9 (7.2)
Grooved inlet/outlet connection, in. (mm)
2
2.5 (65) 2.5 (65) 2.5 (65)
Max. Water Pressure, psi (kPa) 653 (4502) 653 (4502) 653 (4502)
Max. Refrigerant Pressure, psi (kPa) 653 (4502) 653 (4502) 653 (4502)
Physical Data
AGZ-E (Microchannel Packaged Chiller)
AGZ045E AGZ050E AGZ055E
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2
BASIC DATA
Unit Operating Charge lbs (kg)
- Replaceable Core Filter Drier (Microchannel only)
21 (9.5) 21 (9.5) 21 (9.5) 21 (9.5) 21 (9.5) 21 (9.5)
23 (10.5) 23 (10.5) 23 (10.5) 23 (10.5) 23 (10.5) 23 (10.5)
COMPRESSORS, SCROLL, HERMETIC
Nominal HP 12.0 / 12.0 12.0 / 12.0 13.0 / 13.0 13.0 / 13.0 13.0 / 13.0 15.0 / 15.0
Oil charge per Compressor , oz (g)
110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)
110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)
Staging, 4 Stages (If Circuit is in Lead) 0-25-50-75-1000-25-50-75-1000-25-50-75-1000-25-50-75-1000-23-50-73-1000-27-50-77-100
CONDENSER, MICROCHANNEL Coil Inlet Face Area, sq. ft. (sq. m.) 49.8 (4.6) 49.8 (4.6) 49.8 (4.6) 49.8 (4.6) 49.8 (4.6) 49.8 (4.6)
Rows Deep/Fins Per Inch 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21
CONDENSER FANS, DIRECT DRIVE PROPELLER
# of Fans per Circuit - Fan Diameter in (mm) 2 - 30 (762)2 - 30 (762)2 - 30 (762)2 - 30 (762)2 - 30 (762)2 - 30 (762)
Fan Motor, hp (kW) (for 208V,230V,460V/60Hz)
1
1.5 (1.1) 1.5 (1.1) 1.5 (1.1)
Fan & Motor RPM (for all 60Hz)
1
1140 1140 1140
Airflow, cfm (l/s)
1
40,400 (19,067) 40,400 (19,067) 40,400 (19,067)
EVAPORATOR, BRAZED PLATE
3
Dry Weight lbs (kg) 112 (50.1) 126 (57.2) 133 (60.3)
Water Volume, gallons (liters) 2.3 (8.7) 2.6 (9.8) 2.8 (10.6)
Grooved inlet/outlet connection, in. (mm)
2
2.5 (65) 2.5 (65) 2.5 (65)
Max. Water Pressure, psi (kPa) 653 (4502) 653 (4502) 653 (4502)
Max. Refrigerant Pressure, psi (kPa) 653 (4502) 653 (4502) 653 (4502)

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 30 www.DaikinApplied.com
Physical Data - Packaged Unit
Table 24: Physical Data - AGZ060E - AGZ070E
Table 25: Physical Data - AGZ075E - AGZ090E
NOTE: 1) Models 030-060: Fan Motor hp = 2.0 for 380V/60Hz, 575V/60Hz, & 400V/50Hz.
All Models: Fan RPM = 950 for 400V/50Hz. Airflow =(0.83 x 60Hz Airflow) for 400V/50Hz.
2) Water connection shown is nominal pipe size.
3) Brazed plate evaporators do not have drain or vent connections integral to the heat exchanger. The connections must be installed in the field inlet and
outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual, available on www.DaikinApplied.com.
Physical Data
AGZ-E (Microchannel Packaged Chiller)
AGZ060E AGZ065E AGZ070E
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2
BASIC DATA
Unit Operating Charge lbs (kg) - Sealed Filter Drier 21 (9.5) 21 (9.5) 21 (9.5) 21 (9.5) 21 (9.5) 21 (9.5)
- Replaceable Core Filter Drier23 (10.5) 23 (10.5) 23 (10.5) 23 (10.5) 23 (10.5) 23 (10.5)
COMPRESSORS, SCROLL, HERMETIC
Nominal HP 15.0 / 15.0 15.0 / 15.0 15.0 / 15.0 15.0 / 15.0 15.0 / 20.0 15.0 / 20.0
Oil charge per Compressor , oz (g)
110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)
110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)
Staging, 4 Stages (If Circuit is in Lead) 0-25-50-75-1000-25-50-75-1000-25-50-75-1000-25-50-75-1000-21-50-71-1000-28-50-78-100
CONDENSER, MICROCHANNEL
Coil Inlet Face Area, sq. ft. (sq. m.) 49.8 (4.6) 49.8 (4.6) 49.8 (4.6) 49.8 (4.6) 49.8 (4.6) 49.8 (4.6)
Rows Deep/Fins Per Inch 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21
CONDENSER FANS, DIRECT DRIVE PROPELLER
# of Fans per Circuit - Fan Diameter in (mm) 2 - 30 (762)2 - 30 (762) 2 - 30 (762) 2 - 30 (762) 2 - 30 (762)2 - 30 (762)
Fan Motor, hp (kW) (for 208V,230V,460V/60Hz)
1
1.5 (1.1) 2.0 (1.5) 2.0 (1.5)
Fan & Motor RPM (for all 60Hz)
1
1140 1140 1140
Airflow, cfm (l/s)
1
40,400 (19,067) 48,000 (22654) 48,000 (22654)
EVAPORATOR, BRAZED PLATE
3
Dry Weight lbs (kg) 150 (68.1) 150 (68.1) 150 (68.1)
Water Volume, gallons (liters) 3.2 (12.1) 3.2 (12.1) 3.2 (12.1)
Grooved inlet/outlet connection, in. (mm)
2
2.5 (65) 2.5 (65) 2.5 (65)
Max. Water Pressure, psi (kPa) 653 (4502) 653 (4502) 653 (4502)
Max. Refrigerant Pressure, psi (kPa) 653 (4502) 653 (4502) 653 (4502)
Physical Data
AGZ-E (Microchannel Packaged Chiller)
AGZ075E AGZ080E AGZ090E
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2
BASIC DATA
Unit Operating Charge lbs (kg)
- Replaceable Core Filter Drier (Microchannel only)
46 (20.9) 46 (20.9) 46 (20.9) 46 (20.9) 48 (21.8) 48 (21.8)
COMPRESSORS, SCROLL, HERMETIC
Nominal HP 20.0 / 20.0 20.0 / 15.0 20.0 / 20.0 20.0 / 20.0 25.0 / 20.0 20.0 / 25.0
Oil charge per Compressor , oz (g)
152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)
152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)
Staging, 4 Stages (If Circuit is in Lead) 0-27-47-73-1000-25-50-75-1000-25-50-75-1000-25-50-75-1000-28-50-72-1000-22-50-78-100
CONDENSER, MICROCHANNEL
Coil Inlet Face Area, sq. ft. (sq. m.) 79.5 (7.4) 79.5 (7.4) 79.5 (7.4) 79.5 (7.4) 79.5 (7.4) 79.5 (7.4)
Rows Deep/Fins Per Inch 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21
CONDENSER FANS, DIRECT DRIVE PROPELLER
# of Fans per Circuit - Fan Diameter in (mm) 3 - 30 (762)3 - 30 (762)3 - 30 (762)3 - 30 (762)3 - 30 (762)3 - 30 (762)
Fan Motor, hp (kW) 2.0 (1.5) 2.0 (1.5) 2.0 (1.5)
Fan & Motor RPM (for all 60Hz)
1
1140 1140 1140
Airflow, cfm (l/s)
1
67,740 (31,970) 67,740 (31,970) 67,740 (31,970)
EVAPORATOR, BRAZED PLATE
3
Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)
Water Volume, gallons (liters) 7.9 (30) 8.7 (33) 8.7 (33)
Grooved inlet/outlet connection, in. (mm)
2
3.0 (77) 3.0 (77) 3.0 (77)
Max. Water Pressure, psi (kPa) 650 (4482) 650 (4482) 650 (4482)
Max. Refrigerant Pressure, psi (kPa) 650 (4482) 650 (4482) 650 (4482)

Physical Data - Packaged Unit
www.DaikinApplied.com 31 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Table 26: Physical Data - AGZ100E - AGZ120E
Table 27: Physical Data - AGZ130E - AGZ161E
NOTE: 1) All Models: Fan RPM = 950 for 400V/50Hz. Airflow =(0.83 x 60Hz Airflow) for 400V/50Hz.
2) Water connection shown is nominal pipe size.
3) Brazed plate evaporators do not have drain or vent connections integral to the heat exchanger. The connections must be installed in the field inlet and
outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual, available on www.DaikinApplied.com.
Physical Data
AGZ-E (Microchannel Packaged Chiller)
AGZ100E AGZ110E AGZ120E
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2
BASIC DATA
Unit Operating Charge lbs (kg)
- Replaceable Core Filter Drier (Microchannel only)
49 (22.3) 49 (22.3) 64 (29.1) 64 (29.1) 65 (29.5) 65 (29.5)
COMPRESSORS, SCROLL, HERMETIC
Nominal HP 25.0 / 25.0 25.0 / 30.0 30.0 / 25.0 25.0 / 30.0 30.0 / 30.0 30.0 / 30.0
Oil charge per Compressor , oz (g)
152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)
152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)
Staging, 4 Stages (If Circuit is in Lead) 0-24-48-71-1000-24-48-76-1000-27-50-73-1000-23-50-77-1000-25-50-75-1000-25-50-75-100
CONDENSER, MICROCHANNEL
Coil Inlet Face Area, sq. ft. (sq. m.) 79.5 (7.4) 79.5 (7.4) 106 (9.9) 106 (9.9) 106 (9.9) 106 (9.9)
Rows Deep/Fins Per Inch 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21
CONDENSER FANS, DIRECT DRIVE PROPELLER
# of Fans per Circuit - Fan Diameter in (mm) 3 - 30 (762)3 - 30 (762)4 - 30 (762)4 - 30 (762)4 - 30 (762)4 - 30 (762)
Fan Motor, hp (kW) 2.0 (1.5) 2.0 (1.5) 2.0 (1.5)
Fan & Motor RPM (for all 60Hz)
1
1140 1140 1140
Airflow, cfm (l/s)
1
67,740 (31,970) 90,320 (42,627) 90,320 (42,627)
EVAPORATOR, BRAZED PLATE
3
Dry Weight lbs (kg) 317 (144) 339 (154) 369 (168)
Water Volume, gallons (liters) 10.6 (41) 11.4 (44) 12.5 (48)
Grooved inlet/outlet connection, in. (mm)
2
3.0 (77) 3.0 (77) 3.0 (77)
Max. Water Pressure, psi (kPa) 650 (4482) 650 (4482) 650 (4482)
Max. Refrigerant Pressure, psi (kPa) 650 (4482) 650 (4482) 650 (4482)
Physical Data
AGZ-E (Microchannel Packaged Chiller)
AGZ130E AGZ140E AGZ150E AGZ161E
CIRCUIT 1CIRCUIT 2CIRCUIT 1CIRCUIT 2CIRCUIT 1CIRCUIT 2CIRCUIT 1CIRCUIT 2
BASIC DATA
Unit Operating Charge lbs (kg)
- Replaceable Core Filter Drier (Microchannel only)
65 (29.5)65 (29.5)76 (34.5)76 (34.5)76 (34.5)76 (34.5)78 (34.5)78 (34.5)
COMPRESSORS, SCROLL, HERMETIC
Nominal HP 30.0 / 30.030.0 / 40.040.0 / 30.030.0 / 40.040.0 / 30.040.0 / 40.040.0 / 40.040.0 / 40.0
Oil charge per Compressor , oz (g)
213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)
213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)
Staging, 4 Stages (If Circuit is in Lead)
0-23-46-69-
100
0-23-46-77-
100
0-29-50-71-
100
0-21-50-79-
100
0-27-50-73-
100
0-27-53-80-
100
0-27-53-80-
100
0-27-53-80-
100
CONDENSER, MICROCHANNEL
Coil Inlet Face Area, sq. ft. (sq. m.) 106 (9.9)106 (9.9)132.4 (12.4)132.4 (12.4)132.4 (12.4)132.4 (12.4)132.4 (12.4)132.4 (12.4)
Rows Deep/Fins Per Inch 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21
CONDENSER FANS, DIRECT DRIVE PROPELLER
# of Fans per Circuit - Fan Diameter in (mm) 4 - 30 (762)4 - 30 (762)5 - 30 (762)5 - 30 (762)5 - 30 (762)5 - 30 (762)5 - 30 (762)5 - 30 (762)
Fan Motor, hp (kW) 2.0 (1.5) 2.0 (1.5) 2.0 (1.5) 2.0 (1.5)
Fan & Motor RPM (for all 60Hz)
1
1140 1140 1140 1140
Airflow, cfm (l/s)
1
90,320 (42,627) 112,900 (53,283) 112,900 (53,283) 112,900 (53,283)
EVAPORATOR, BRAZED PLATE
3
Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211) 465 (211)
Water Volume, gallons (liters) 13.8 (53) 15.0 (57) 16.1 (61) 16.1 (61)
Grooved inlet/outlet connection, in. (mm)
2
3.0 (77) 4.0 (102) 4.0 (102) 4.0 (102)
Max. Water Pressure, psi (kPa) 650 (4482) 650 (4482) 650 (4482) 650 (4482)
Max. Refrigerant Pressure, psi (kPa) 650 (4482) 650 (4482) 650 (4482) 650 (4482)

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 32 www.DaikinApplied.com
Physical Data - Packaged Unit
Table 28: Physical Data - AGZ170E - AGZ180E
Table 29: Physical Data - AGZ191-241E
NOTE: 1) All Models: Fan RPM = 950 for 400V/50Hz. Airflow =(0.83 x 60Hz Airflow) for 400V/50Hz.
2) Water connection shown is nominal pipe size.
3) Brazed plate evaporators do not have drain or vent connections integral to the heat exchanger. The connections must be installed in the field inlet and
outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual, available on www.DaikinApplied.com.
Physical Data
AGZ-E (Microchannel Packaged Chiller)
AGZ170E AGZ180E
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2
BASIC DATA
Unit Operating Charge lbs (kg)
- Replaceable Core Filter Drier (Microchannel only)
80 (36.3) 80 (36.3) 80 (36.3) 80 (36.3)
COMPRESSORS, SCROLL, HERMETIC
Nominal HP 25 / 25 / 30 30 / 30 / 30 30 / 30 / 30 30 / 30 / 30
Oil charge per Compressor , oz (g)
152 (4495) 213 (6299) 213 (6299) 213 (6299)
152 (4495) 213 (6299) 213 (6299) 213 (6299)
213 (6299) 213 (6299) 213 (6299) 213 (6299)
Staging, 6 Stages (If Circuit is in Lead) 0-15-32-47-65-82-1000-18-32-50-65-82-1000-17-33-50-67-83-1000-17-33-50-67-83-100
CONDENSER, MICROCHANNEL
Coil Inlet Face Area, sq. ft. (sq. m.) 132.4 (12.4) 132.4 (12.4) 132.4 (12.4) 132.4 (12.4)
Rows Deep/Fins Per Inch 1 / 21 1 / 21 1 / 21 1 / 21
CONDENSER FANS, DIRECT DRIVE PROPELLER
# of Fans per Circuit - Fan Diameter in (mm) 5 - 30 (762) 5 - 30 (762) 5 - 30 (762) 5 - 30 (762)
Fan Motor, hp (kW) 2.0 (1.5) 2.0 (1.5)
Fan & Motor RPM (for all 60Hz)
1
1140 1140
Airflow, cfm (l/s)
1
112,900 (53,283) 112,900 (53,283)
EVAPORATOR, BRAZED PLATE
3
Dry Weight lbs (kg) 494 (225) 531 (241)
Water Volume, gallons (liters) 17.1 (65) 18.6 (71)
Grooved inlet/outlet connection, in. (mm)
2
4.0 (102) 4.0 (102)
Max. Water Pressure, psi (kPa) 650 (4482) 650 (4482)
Max. Refrigerant Pressure, psi (kPa) 650 (4482) 650 (4482)
Physical Data
AGZ-E (Microchannel Packaged Chiller)
AGZ191E AGZ211E AGZ226E AGZ241E
CIRCUIT 1CIRCUIT 2CIRCUIT 1CIRCUIT 2CIRCUIT 1CIRCUIT 2CIRCUIT 1CIRCUIT 2
BASIC DATA
Unit Operating Charge lbs (kg)
- Replaceable Core Filter Drier (Microchannel only)
87 (39.5)87 (39.5)91 (41.3)91 (41.3)107 (48.6)107 (48.6)111 (50.4)111 (50.4)
COMPRESSORS, SCROLL, HERMETIC
Nominal HP 30 / 30 / 3030 / 40 / 3030 / 40 / 3030 / 40 / 3030 / 40 / 3040 / 30 / 4040 / 40 / 4040 / 40 / 40
Oil charge per Compressor , oz (g)
213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)
213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)
213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)
Staging, 6 Stages (If Circuit is in Lead)
0-16-32-47-
68-84-100
0-16-32-53-
68-84-100
0-15-30-50-
70-85-100
0-15-30-50-
70-85-100
0-14-33-52-
67-81-100
0-19-33-48-
67-86-100
0-17-33-50-
67-83-100
0-17-33-50-
67-83-100
CONDENSER, MICROCHANNEL
Coil Inlet Face Area, sq. ft. (sq. m.) 158.9 (14.8)158.9 (14.8)158.9 (14.8)158.9 (14.8)185.4 (17.3)185.4 (17.3)185.4 (17.3)185.4 (17.3)
Rows Deep/Fins Per Inch 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21
CONDENSER FANS, DIRECT DRIVE PROPELLER
# of Fans per Circuit - Fan Diameter in (mm) 6 - 30 (762)6 - 30 (762)6 - 30 (762)6 - 30 (762)7 - 30 (762)7 - 30 (762)7 - 30 (762)7 - 30 (762)
Fan Motor, hp (kW) 2.0 (1.5) 2.0 (1.5) 2.0 (1.5) 2.0 (1.5)
Fan & Motor RPM (for all 60Hz)
1
1140 1140 1140 1140
Airflow, cfm (l/s)
1
135480 (63940) 135480 (63940) 158060 (74597) 158060 (74597)
EVAPORATOR, BRAZED PLATE
3
Dry Weight lbs (kg) 670 (304) 670 (304) 806 (366) 806 (366)
Water Volume, gallons (liters) 17.95 (68) 17.95 (68) 22.44 (85) 22.44 (85)
Grooved inlet/outlet connection, in. (mm)
2
5.0 (127) 5.0 (127) 5.0 (127) 5.0 (127)
Max. Water Pressure, psi (kPa) 435 (3000) 435 (3000) 435 (3000) 435 (3000)
Max. Refrigerant Pressure, psi (kPa) 652 (4496) 652 (4496) 652 (4496) 652 (4496)

Dimensions and Weights - Packaged Units
www.DaikinApplied.com 33 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Table 28: Physical Data - AGZ170E - AGZ180E
Table 29: Physical Data - AGZ191-241E
NOTE: 1) All Models: Fan RPM = 950 for 400V/50Hz. Airflow =(0.83 x 60Hz Airflow) for 400V/50Hz.
2) Water connection shown is nominal pipe size.
3) Brazed plate evaporators do not have drain or vent connections integral to the heat exchanger. The connections must be installed in the field inlet and
outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual, available on www.DaikinApplied.com.
Physical Data
AGZ-E (Microchannel Packaged Chiller)
AGZ170E AGZ180E
CIRCUIT 1 CIRCUIT 2 CIRCUIT 1 CIRCUIT 2
BASIC DATA
Unit Operating Charge lbs (kg)
- Replaceable Core Filter Drier (Microchannel only)
80 (36.3) 80 (36.3) 80 (36.3) 80 (36.3)
COMPRESSORS, SCROLL, HERMETIC
Nominal HP 25 / 25 / 30 30 / 30 / 30 30 / 30 / 30 30 / 30 / 30
Oil charge per Compressor , oz (g)
152 (4495) 213 (6299) 213 (6299) 213 (6299)
152 (4495) 213 (6299) 213 (6299) 213 (6299)
213 (6299) 213 (6299) 213 (6299) 213 (6299)
Staging, 6 Stages (If Circuit is in Lead) 0-15-32-47-65-82-1000-18-32-50-65-82-1000-17-33-50-67-83-1000-17-33-50-67-83-100
CONDENSER, MICROCHANNEL
Coil Inlet Face Area, sq. ft. (sq. m.) 132.4 (12.4) 132.4 (12.4) 132.4 (12.4) 132.4 (12.4)
Rows Deep/Fins Per Inch 1 / 21 1 / 21 1 / 21 1 / 21
CONDENSER FANS, DIRECT DRIVE PROPELLER
# of Fans per Circuit - Fan Diameter in (mm) 5 - 30 (762) 5 - 30 (762) 5 - 30 (762) 5 - 30 (762)
Fan Motor, hp (kW) 2.0 (1.5) 2.0 (1.5)
Fan & Motor RPM (for all 60Hz)
1
1140 1140
Airflow, cfm (l/s)
1
112,900 (53,283) 112,900 (53,283)
EVAPORATOR, BRAZED PLATE
3
Dry Weight lbs (kg) 494 (225) 531 (241)
Water Volume, gallons (liters) 17.1 (65) 18.6 (71)
Grooved inlet/outlet connection, in. (mm)
2
4.0 (102) 4.0 (102)
Max. Water Pressure, psi (kPa) 650 (4482) 650 (4482)
Max. Refrigerant Pressure, psi (kPa) 650 (4482) 650 (4482)
Physical Data
AGZ-E (Microchannel Packaged Chiller)
AGZ191E AGZ211E AGZ226E AGZ241E
CIRCUIT 1CIRCUIT 2CIRCUIT 1CIRCUIT 2CIRCUIT 1CIRCUIT 2CIRCUIT 1CIRCUIT 2
BASIC DATA
Unit Operating Charge lbs (kg)
- Replaceable Core Filter Drier (Microchannel only)
87 (39.5)87 (39.5)91 (41.3)91 (41.3)107 (48.6)107 (48.6)111 (50.4)111 (50.4)
COMPRESSORS, SCROLL, HERMETIC
Nominal HP 30 / 30 / 3030 / 40 / 3030 / 40 / 3030 / 40 / 3030 / 40 / 3040 / 30 / 4040 / 40 / 4040 / 40 / 40
Oil charge per Compressor , oz (g)
213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)
213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)
213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)213 (6299)
Staging, 6 Stages (If Circuit is in Lead)
0-16-32-47-
68-84-100
0-16-32-53-
68-84-100
0-15-30-50-
70-85-100
0-15-30-50-
70-85-100
0-14-33-52-
67-81-100
0-19-33-48-
67-86-100
0-17-33-50-
67-83-100
0-17-33-50-
67-83-100
CONDENSER, MICROCHANNEL
Coil Inlet Face Area, sq. ft. (sq. m.) 158.9 (14.8)158.9 (14.8)158.9 (14.8)158.9 (14.8)185.4 (17.3)185.4 (17.3)185.4 (17.3)185.4 (17.3)
Rows Deep/Fins Per Inch 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21 1 / 21
CONDENSER FANS, DIRECT DRIVE PROPELLER
# of Fans per Circuit - Fan Diameter in (mm) 6 - 30 (762)6 - 30 (762)6 - 30 (762)6 - 30 (762)7 - 30 (762)7 - 30 (762)7 - 30 (762)7 - 30 (762)
Fan Motor, hp (kW) 2.0 (1.5) 2.0 (1.5) 2.0 (1.5) 2.0 (1.5)
Fan & Motor RPM (for all 60Hz)
1
1140 1140 1140 1140
Airflow, cfm (l/s)
1
135480 (63940) 135480 (63940) 158060 (74597) 158060 (74597)
EVAPORATOR, BRAZED PLATE
3
Dry Weight lbs (kg) 670 (304) 670 (304) 806 (366) 806 (366)
Water Volume, gallons (liters) 17.95 (68) 17.95 (68) 22.44 (85) 22.44 (85)
Grooved inlet/outlet connection, in. (mm)
2
5.0 (127) 5.0 (127) 5.0 (127) 5.0 (127)
Max. Water Pressure, psi (kPa) 435 (3000) 435 (3000) 435 (3000) 435 (3000)
Max. Refrigerant Pressure, psi (kPa) 652 (4496) 652 (4496) 652 (4496) 652 (4496)
Dimensions and Weights - Packaged Units
Figure 33: AGZ030E - AGZ035E
1822
71.8
209
8.2
REF.
2389
94.1
2546
100.2
165
6.5
370
14.6
2X
64
2.5
497
19.6
1094
43.1
22
.875
KNOCKOUTS
FIELD CONTROL
CONNECTIONS
QTY. 3
2235
88.0
DIMENSION DOES NOT INCLUDE
LIFTING BRACKETS
B
153
6.0
A
X
Y
CONTROL BOX
FRONT LEFT CORNER POST PURPOSELY HIDDEN
EVAP.
WYE-STRAINER REQUIRED (FACTORY OR FIELD INSTALLED OPTION)
[22]
Ø.875
POWER ENTRY
KNOCKOUTS
FRONT OR RIGHT SIDE
635
25.0
266
10.5
797
31.4
506
19.9
2396
94.3
506
19.9
51
2.0
80
3.2
152
6.0
127
5.0
Z
BLANK PANELS ARE USED ON UNIT SIDES. SLOPED 50" COILS USED ON INSIDE.
[22] Ø.875 KNOCKOUTS POWER ENTRY KNOCKOUTS ARE ON THE OPPOSITE SIDE OF CONTROL BOX
EVAP. WATER INLET
EVAP. WATER OUTLET
L1
L2
L3
L4
337
13.3
1721
67.8
337
13.3
52
2.0
52
2.0
19
.750
QTY. 4
M1 - M4, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE
M3M1
M2 M4
L4L2
L1 L3
COMPRESSORS CIRCUIT #2
COMPRESSORS CIRCUIT #1
L1 - L4, LIFTING
LOCATIONS
TOP VIEW WITH COILS AND FANS REMOVED
SHIPPING WEIGHT
OPERATING
W EIGHT
LBS (KG)LBS (KG)L1L2 L3 L4 M1 M2 M3 M4
AGZ030E2947 (1337) 2960 (1343) 1011 (459) 799 (362) 635 (288) 502 (228) 980 (445) 775 (352) 673 (305) 532 (241) AGZ035E2873 (1303) 2887 (1310) 1051 (477) 861 (391) 528 (240) 433 (196) 1005 (456) 824 (374) 581 (264) 476 (216)
PACKAGE UNITS WITH MICROCHANNEL COILS
UNIT MODEL
LIFTING (SHIPPING) WEIGHT BY CORNER LBS (KG) MOUNTING (OPERATING) WEIGHT LBS (KG)
XYZ
AGZ030E38.9 (988) 44.5 (1130) 40.9 (1039)
AGZ035E39.7 (1008) 45.5 (1156) 38.1 (968)
UNIT MODEL
CG LOCATION, IN (MM)
PACKAGE UNITS WITH MICROCHANNEL COILS
AB
AGZ030E24.2 (615)2.9 (74)2.5 (64)
AGZ035E23.5 (597)2.2 (56)2.5 (64)
UNIT MODEL
EVAP. DIMENSIONS IN (MM)CONNECTION SIZE
(VICTAULIC)
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED.
SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.
0B
3345471 01AGZ-E, 4 FANS

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 34 www.DaikinApplied.com
Dimensions and Weights - Packaged Units
Figure 34: AGZ040E - AGZ070E
1822
71.8
208
8.2
REF.
2389
94.0
2546
100.2
165
6.5
370
14.6
2X
64
2.5
497
19.6
1094
43.1
22
.875
KNOCKOUTS
FIELD CONTROL
CONNECTIONS
QTY. 3
2235
88.0
DIMENSION DOES NOT INCLUDE
LIFTING BRACKETS
B
153
6.0
A
X
Y
CONTROL BOX
FRONT LEFT CORNER POST PURPOSELY HIDDEN
EVAP.
WYE-STRAINER REQUIRED (FACTORY OR FIELD INSTALLED OPTION)
[22]
Ø.875
POWER ENTRY
KNOCKOUTS
FRONT OR RIGHT SIDE
635
25.0
266
10.5
797
31.4
506
19.9
2396
94.3
506
19.9
51
2.0
80
3.2
152
6.0
127
5.0
Z
[22] Ø.875 KNOCKOUTS POWER ENTRY KNOCKOUTS ARE ON THE OPPOSITE SIDE OF CONTROL BOX
EVAP. WATER INLET
EVAP. WATER OUTLET
L1
L2
L3
L4
L1 - L4, LIFTING
LOCATIONS
337
13.3
1721
67.8
337
13.3
52
2.0
52
2.0
19
.750
QTY. 4
M1 - M4, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE
M3M1
M2 M4
L4L2
L1 L3
COMPRESSORS CIRCUIT #2
COMPRESSORS CIRCUIT #1
TOP VIEW WITH COILS AND FANS REMOVED
XYZ
AGZ040E39.8 (1011) 45.9 (1166) 38.4 (975)
AGZ045E38.9 (988) 44.5 (1130) 41.2 (1047)
AGZ050E39.1 (993) 44.9 (1141) 41.2 (1047)
AGZ055E39.1 (993) 44.8 (1138) 41.2 (1047)
AGZ060E39.2 (996) 44.6 (1133) 41.1 (1044)
AGZ065E39.2 (996) 44.6 (1133) 41.1 (1044)
AGZ070E36.8 (935) 41.8 (1062) 42.6 (1082)
PACKAGE UNITS WITH MICROCHANNEL COILS
UNIT MODEL
CG LOCATION, IN (MM)
SHIPPING WEIGHT
OPERATING
W EIGHT
LBS (KG)LBS (KG)L1L2 L3 L4 M1 M2 M3 M4
AGZ040E2948 (1337) 2964 (1345) 1067 (484) 881 (400) 548 (249) 453 (206) 1022 (464) 844 (383) 601 (273) 496 (225)
AGZ045E3094 (1403) 3112 (1412) 1051 (477) 832 (377) 676 (307) 535 (243) 1021 (463) 809 (367) 715 (324) 567 (257)
AGZ050E3093 (1403) 3114 (1413) 1049 (476) 837 (380) 671 (304) 536 (243) 1020 (463) 814 (369) 712 (323) 568 (258)
AGZ055E3106 (1409) 3128 (1419) 1052 (477) 840 (381) 675 (306) 539 (245) 1023 (464) 817 (371) 716 (325) 572 (260)
AGZ060E3130 (1420) 3155 (1431) 1059 (480) 851 (386) 676 (307) 543 (246) 1031 (468) 828 (376) 718 (326) 577 (262)
AGZ065E3130 (1420) 3155 (1431) 1059 (480) 851 (386) 676 (307) 543 (246) 1031 (468) 828 (376) 718 (326) 577 (262)
AGZ070E3472 (1575) 3497 (1586) 1180 (535) 847 (384) 842 (382) 604 (274) 1157 (525) 830 (377) 880 (399) 631 (286)
PACKAGE UNITS WITH MICROCHANNEL COILS
UNIT MODEL
LIFTING (SHIPPING) WEIGHT BY CORNER LBS (KG) MOUNTING (OPERATING) WEIGHT LBS (KG)
AB
AGZ040E22.8 (579)1.5 (38)2.5 (64)
AGZ045E21.4 (544)0.11 (3)2.5 (64)
AGZ050E20 (508)2.7 (69)2.5 (64)
AGZ055E19.3 (490)2.0 (51)2.5 (64)
AGZ060E17.6 (447)0.3 (8)2.5 (64)
AGZ065E17.6 (447)0.3 (8)2.5 (64)
AGZ070E17.6 (447)0.3 (8)2.5 (64)
UNIT MODEL
EVAP. DIMENSIONS IN (MM) CONNECTION SIZE
(VICTAULIC)
0B
3345471 01AGZ-E, 4 FANS
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED.
SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.

Dimensions and Weights - Packaged Units
www.DaikinApplied.com 35 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Figure 35: AGZ075E - AGZ100E
X
Y
305
12.0
80
3.1
51
2.0
127
5.0
Z
22
.875 KNOCKOUTS
POWER ENTRY KNOCKOUTS
ARE ON THE OPPOSITE SIDE 
OF THE CONTROL BOX
D
AGZ-E, 6 FANS 334547111
0A
COMPR.
CIRCUIT 2
M1 - M4, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE.
M1
M3
M2
M4
L2
L3L1
CIRCUIT 1
L4
COMPR.
TOP VIEW WITH
COILS AND FANS
REMOVED
38.7
984
19 .750
QTY. 4
52
A  (w/o STRAINER OPTION)
2.0
44.0
2433
315
12.4
52 2.0
95.8
1118
B
CONTROL
BOX
[22]
.875 POWER ENTRY
KNOCKOUTS
FRONT OR RIGHT SIDE
1
22 .875 KNOCKOUTS
FIELD CONTROL
CONNECTIONS
QTY. 3
92.7
2355
98.6
2506
8.4
11.5
292
6.5
2.5
64
165
88.02235
DIMENSION DOES NOT INCLUDE
LIFTING BRACKETS
6.9175
213
64
2.5
INLET
WYE-STRAINER
OUTLET
WATER
INSTALLED OPTION)
WATER EVAP. 
(FACTORY OR FIELD REQUIRED
L1
L2
L3 L4
EVAP. 1
37
1.5
24.0
609
147.0
3733
11.4
290
6.0
153
916
36.1
858
33.8
L1 - L4,
LIFTING 
LOCATIONS
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
 MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER 
INCLUDED.  SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY 
OPTIONS OR ACCESSORIES.
NOTES:
IT IS RECOMMENDED THAT THE
1.
 FOR POWER ENTRY WIRE SIZES 
AB
AGZ075E55.6 (1412) 27.1 (688)
AGZ080E54.4 (1382) 25.9 (658)
AGZ090E54.4 (1382) 25.9 (658)
AGZ100E51.6 (1311) 23.1 (587)
CONNECTION
SIZE, IN.
EVAP. DIMENSIONS
IN (MM)
UNIT
MODEL
3.0 (76)
XYZ
AGZ075E45.3 (1151) 38.6 (980) 56.2 (1427)
AGZ080E44.2 (1122) 39.2 (995) 56.5 (1435)
AGZ090E44.2 (1122) 39.2 (995) 55.0 (1397)
AGZ100E43.6 (1108) 38.9 (988) 55.7 (1415)
UNIT
MODEL
CG LOCATION, IN (MM)
SHIPPING WEIGHT OPERATING WEIGHT
LBS (KG)LBS (KG)L1L2L3L4M1 M2 M3 M4
AGZ075E4388 (1990) 4451 (2019) 1341 (608) 1420 (644) 790 (358) 837 (380) 1173 (532) 1242 (563) 989 (449) 1047 (475)
AGZ080E4510 (2046) 4579 (2077) 1407 (638) 1418 (643) 840 (381) 846 (384) 1232 (559) 1241 (563) 1049 (476) 1057 (479)
AGZ090E4540 (2059) 4609 (2091) 1456 (660) 1466 (665) 806 (366) 812 (368) 1276 (579) 1285 (583) 1020 (463) 1028 (466)
AGZ100E4696 (2130) 4780 (2168) 1505 (683) 1480 (671) 863 (391) 848 (385) 1322 (600) 1299 (589) 1089 (494) 1070 (485)
UNIT MODEL
LIFTING (SHIPPING) WEIGHT BY CORNER, LBS (KG) MOUNTING (OPERATING) WEIGHT, LBS (KG)
SIDE LOCATIONS BE USED
 LARGER THAN 350 MCM.

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 36 www.DaikinApplied.com
Dimensions and Weights - Packaged Units
Figure 36: AGZ110E - AGZ130E
Y
X
Z
12.0
2.051
 KNOCKOUTS .875
22
5.0
127
305
POWER ENTRY KNOCKOUTS
ARE ONTHE OPPOSITE SIDE
OF THE CONTROL BOX
80 3.1
 SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
 MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED.
NOTE:
IT IS RECOMMENDED THAT THE
1.
FOR POWER ENTRY WIRE SIZES
COMPR.
CIR. 1
M1 - M6, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE.
M1
M3 M5
L1 L3
M2 L4M4L2
CIR. 2
M6
COMPR.
TOP VIEW WITH
COILS AND FANS
REMOVED.
52
24.8
19 .750
QTY. 6
52
A  (w/o STRAINER OPTION)
2.0
44.0
2.0
315
12.4
630
2433
95.8
1499
59.0
1118
B
CONTROL
BOX
[22]
.875 POWER ENTRY
KNOCKOUTS
FRONT OR RIGHT SIDE
1
22 .875 KNOCKOUTS
FIELD CONTROL
CONNECTIONS
QTY. 3
6.5
165
6.9
175
11.5
292
LIFTING BRACKETS
2.5
64
DIMENSION DOES NOT INCLUDE
98.62506
92.72355
213 8.4
2235
88.0
64
2.5
0A
D
334547121 AGZ-E 8 FANS
OUTLET
L1 - L4,
LOCATIONS
WATER
INLET
 OPTION)
EVAP.
REQUIRED
L1 L2
FIELD INSTALLED
L4
(FACTORY OR
LIFTING
WATER
L3
EVAP. 
WYE-STRAINER
1
192.1
4879
39.2
996
6.0
153
11.4
290
37
1.5
609
24.0
858
33.8
SHIPPING WEIGHT OPERATING WEIGHT
LBS (KG)LBS (KG)L1L2L3L4 M1 M2 M3 M4 M5 M6
AGZ110E5437 (2466) 5528 (2508) 1762 (799) 1769 (802) 951 (431) 955 (433) 1424 (646) 1430 (649) 845 (383) 849 (385) 489 (222) 491 (223)
AGZ120E5696 (2584) 5796 (2629) 1907 (865) 1915 (869) 935 (424) 939 (426) 1548 (702) 1555 (705) 878 (398) 882 (400) 465 (211) 467 (212)
AGZ130E5792 (2627) 5903 (2678) 1941 (880) 1863 (845) 1015 (460) 974 (442) 1575 (714) 1511 (685) 920 (417) 883 (401) 517 (235) 496 (225)
UNIT
MODEL
LIFTING (SHIPPING) WEIGHT BY CORNER, LBS (KG) MOUNTING (OPERATING) WEIGHT, LBS (KG)
XYZ
AGZ110E44.1 (1120) 42.1 (1069) 69.0 (1753)
AGZ120E44.1 (1120) 43.3 (1100) 66.4 (1687)
AGZ130E43.1 (1095) 41.0 (1041) 68.3 (1735)
UNIT
MODEL
CG LOCATION, IN (MM)
AB
AGZ110E95.5 (2426) 69.1 (1755)
AGZ120E93.9 (2385) 67.5 (1715)
AGZ130E92.0 (2337) 65.5 (1664)
EVAP. DIMENSIONS, IN (MM)CONNECTION
SIZE, IN.
3.0 (76)
UNIT
MODEL
SIDE LOCATIONS BE USED
LARGER THAN 350 MCM.

Dimensions and Weights - Packaged Units
www.DaikinApplied.com 37 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Figure 37: AGZ140E - AGZ161E
22
.875 KNOCKOUTS
POWER ENTRY KNOCKOUTS
ARE ON THE OPPOSITE SIDE
OF THE CONTROL BOX
51
2.0
80
3.1
305
12.0
127
5.0
Z
X
Y
0B
334547131
D
AGZ-E 10FANS , 4 COMPRESSORS ,
 MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING 
WEIGHT WITH EVAPORATOR WATER INCLUDED.  SHIPPING 
AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS 
OF ANY OPTIONS OR ACCESSORIES.
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
NOTE:
IT IS RECOMMENDED THAT THE SIDE LOCATIONS BE USED 1.
 FOR POWER ENTRY WIRE SIZES LARGER THAN 350 MCM.
WATER 
(FACTORY OR FIELD
L3
WATER 
EVAP. 
WYE-STRAINER
LOCATIONS
INSTALLED OPTION)
OUTLET
L1 - L4
INLET
REQUIRED
LIFTING
L1
L2 EVAP.  L4
1
210
8.3
237.2
6025
11.4
290
1919 75.5
37
1.5
609
24.0
858
33.8
CONTROL BOX
[22]
.875 
POWER ENTRY KNOCKOUTS FRONT  OR RIGHT SIDE
1
22 .875 KNOCKOUTS
FIELD CONTROL
CONNECTIONS
QTY. 3
6.5
165
LIFTING BRACKETS
DIMENSION DOES NOT INCLUDE
88.0
2235
11.5
292
6.9
2.5
64
2506
98.6
92.7
175
2355
213 8.4
64
2.5
TOP VIEW WITH COILS AND FANS
M5
M1 - M4, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE.
M1
L1
M3
L3
M 2L 2 L4
CIR. 1
M4
REMOVED
M6
COMPR.
COMPR. CIR. 2
19 .750
QTY. 6
2433 95.8
B
67.4
1711 A  (w/o STRAINER OPTION)
61.6
1564
52 2.0
2.0
315
12.4
52
1118
44.0
SHIPPING WEIGHT OPERATING WEIGHT
LBS (KG)LBS (KG)L1L2L3L4 M1 M2 M3 M4 M5 M6
AGZ140E6555 (2973) 6674 (3027) 1862 (845) 1868 (847) 1410 (640) 1415 (642) 1411 (640) 1416 (642) 1070 (485) 1074 (487) 850 (386) 853 (387)
AGZ150E6617 (3001) 6745 (3059) 1888 (856) 1881 (853) 1426 (647) 1421 (645) 1433 (650) 1428 (648) 1085 (492) 1081 (490) 861 (391) 858 (389)
AGZ161E6668 (3025) 6802 (3085) 1917 (870) 1876 (851) 1453 (659) 1422 (645) 1456 (660) 1425 (646) 1104 (501) 1080 (490) 878 (398) 859 (390)
UNIT
MODEL
LIFTING (SHIPPING) WEIGHT BY CORNER, LBS (KG) MOUNTING (OPERATING) WEIGHT, LBS (KG)
XYZAB
AGZ140E44.1 (1120) 42.6 (1083) 83.3 (2117) 122.1 (3102) 67.51 (1715)
AGZ150E43.9 (1116) 42.4 (1077) 83.3 (2115) 120.5 (3062) 65.9 (1674)
AGZ161E43.5 (1105) 42.3 (1074) 83.4 (2117) 120.5 (3062) 65.9 (1674)
UNIT
MODEL
CG LOCATION, IN (MM) EVAP. DIMENSIONS, IN (MM)CONNECTION
SIZE, IN.
4.0 (102)

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 38 www.DaikinApplied.com
Dimensions and Weights - Packaged Units
Figure 38: AGZ170E - AGZ180E
X
Y
22
.875 KNOCKOUTS
POWER ENTRY KNOCKOUTS
ARE ON THE OPPOSITE SIDE
OF THE CONTROL BOX
51
2.0
81
3.2
305
12.0
127
5.0
Z
BOX
CONTROL
[22]
.875 
POWER ENTRY
KNOCKOUTS FRONT 
OR RIGHT SIDE
1
22 .875 KNOCKOUTS
FIELD CONTROL
CONNECTIONS
QTY. 3
64
2.5
98.6
2506
92.7
2355
8.4213
6.9
175
6.5
165
LIFTING BRACKETS
DIMENSION DOES NOT INCLUDE
88.0
2235
11.5
292
64
2.5
 MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING 
WEIGHT WITH EVAPORATOR WATER INCLUDED.  SHIPPING 
AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS  OF ANY OPTIONS OR ACCESSORIES.
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
NOTE:
IT IS RECOMMENDED THAT THE SIDE LOCATIONS BE USED 1.
 FOR POWER ENTRY WIRE SIZES LARGER THAN 350 MCM.
REQUIRED
INLET
WATER 
EVAP. 
L2 L1
L4 L3
OUTLET
L1 - L4
WATER  EVAP. 
(FACTORY OR FIELD
LOCATIONS
LIFTING
WYE-STRAINER INSTALLED OPTION)
1
210
8.3
1.5
37
24.0
609
75.5
1919
237.2
6025
11.4
290
858
33.8
M1 - M4, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE.
M1
L1
M3
L3
M5
M 2L 2 M4 L 4M 6
COMPR.
TOP VIEW WITH
CIR. 2
REMOVED COILS AND FANS
COMPR.
CIR. 1
52 2.0
B
2.052
12.4
315
95.8
2433
61.6
1564
67.4
1711
QTY. 6
.75019
A  (w/o STRAINER OPTION)
1118
44.0
SHIPPING WEIGHT OPERATING WEIGHT
LBS (KG)LBS (KG)L1L2L3L4M1 M2 M3 M4 M5 M6
AGZ170E7170 (3252) 7307 (3314) 2072 (940) 1995 (905) 1581 (717) 1522 (690) 1571 (713) 1512 (686) 1197 (543) 1152 (523) 956 (434) 920 (417)
AGZ180E7412 (3362) 7560 (3429) 2121 (962) 2127 (965) 1580 (717) 1584 (718) 1613 (732) 1617 (733) 1210 (549) 1214 (551) 951 (431) 954 (433)
MOUNTING (OPERATING) WEIGHT, LBS (KG) UNIT
MODEL
LIFTING (SHIPPING) WEIGHT BY CORNER, LBS (KG)
XYZAB
AGZ170E43.2 (1096) 40.4 (1025) 83.6 (2123) 119 (3022) 64.3 (1634)
AGZ180E44.1 (1119) 39.4 (1000) 82.8 (2103) 117 (2971)
62.4 (1584)
UNIT
MODEL
CG LOCATION, IN (MM)EVAP. DIMENSIONS, IN (MM)CONNECTION
SIZE, IN.
4.0 (102)
AGZ-E 10FANS , 6 COMPRESSORS , 334547131
D 0B
62.4 (1584)

Dimensions and Weights - Packaged Units
www.DaikinApplied.com 39 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Figure 39: AGZ191E - AGZ211E
305
12.0
127
5.0
80
3.1
51
2.0
22 .875 KNOCKOUTS
POWER ENTRY POINTS
ARE ON OPPOSITE
SIDE OF CONTROL BOX
Z
Y
2506
98.6
X
Y
IT IS RECOMMENDED THAT THE SIDE LOCATIONS BE USED
 FOR POWER ENTRY WIRE SIZES LARGER THAN 350 MCM.
1.
NOTE: 
LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS. MOUNTING 
WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR 
WATER INCLUDED. SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE 
THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.
NOTE:
L3
M7
ISOLATOR MOUNTING HOLE LOCATIONS ARE ON BOTTOM SURFACE OF UNIT
WITH COILS
M8 L6
CIRCUIT #1
CIRCUIT #2
M4
AND FANS
M 2L 2
COMPRESSORS
L5
M1
TOP VIEW R
EMOVED
L1
M3 M5
L4
COMPRESSORS
M6
[152]
Ø6.0
VICTAULIC
CONN. TYP.
62.91596
2.052
44.0
1118
2241 88.2
315
12.4
2433 95.8
1114
43.8
QTY 8
19
.75
1711
67.4
2.0
52
3577
140.8   w/o STRAINER OPTION
L6
L1
CG
OUTLET
WATER
L4
L5
INLET
L2
EVAP
L3
WATER
1
75.5
1919
7171 282.3
12.1
308
923 36.3
2436
95.9
86.92207
609 24.0
1.537
3167
124.7
00
334547153
D
AGZ-E 12 FANS - BRAZED PLATE  EVAP
CONTROL
BOX
CG
1
64
11.5
2.5
2.5
292
64
CONNECTIONS
FIELD CONTROL 22
92.72355
213 8.4
2235
88.0
DIMENSION DOES NOT
INCLUDE LIFTING BRACKETS
165
6.5
6.9
 KNOCKOUTS .875
175
22 .875 KNOCKOUTS
POWER ENTRY POINTS
FRONT & RIGHT SIDE
LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG
AGZ191E8635 3917 8785 3985 1759 798 1738 788 1458 661 1441 654 1127 511 1113 505 1578 716 1560 708 1164 528 1150 522 974 442 963 437 702 318 694 315
AGZ211E8669 3932 8819 4000 1766 801 1753 795 1461 663 1450 658 1124 510 1116 506 1585 719 1573 713 1166 529 1158 525 975 442 968 439 700 318 695 315
M3 M4 M2
LIFTING (SHIPPING) WEIGHT BY CORNER OPER. WEIGHT
LBS
L1M7 M8
MOUNTING (OPERATING) WEIGHT
KG LBS
M5 M6 L5
KG
M1
UNIT 
MODEL
L2L3L4L6
SHIP WEIGHT
IN. MM IN. MM IN. MM
AGZ191E43.7 1110 40.5 1029 100.6 2555
AGZ211E43.8 1113 40.5 1029 100.4 2550
CG LOCATION
UNIT
MO D E L
XYZ

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 40 www.DaikinApplied.com
Dimensions and Weights - Packaged Units
Figure 40: AGZ226E - AGZ241E
127
5.0
305
12.0 80
3.1
51 2.0
POWER ENTRY POINTS
ARE ON OPPOSITE
SIDE OF CONTROL BOX
22 .875 KNOCKOUTS
Z
Y
Y
X
INLET
L2
L1
L4
L5L3
OUTLET
L6 L8
EVAP
WATER
L7
CG
WATER
1
54.1
1375
86.9
2207
308 12.1
24.0
609
86.9
2207
75.51919
37
1.5
923
36.3
327.48317
4207
165.6
NOTE:
IT IS RECOMMENDED THAT THE SIDE LOCATIONS BE USED
A
ND FANS
REMOVED
THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.
TOP VIEW
WITH COILS
1.
 FOR POWER ENTRY WIRE SIZES LARGER THAN 350 MCM.
NOTE: 
WATER INCLUDED. SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE 
WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR 
LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS. MOUNTING 
FRONT AND RIGHT SIDE
POWER ENTRY POINTS
.875 KNOCKOUTS
[22]
00 D
334547143
AGZ-E 14 FANS - BRAZED PLATE EVAP
CG
CONTROL
BOX
[22]
.875 KNOCKOUTS
FIELD CONTROL
CONNECTIONS
1
2506
98.6
292
11.5
64
2.5
INCLUDE LIFTING BRACKETS
DIMENSION DOES NOT
88.0
2235
6.5
165
6.9
175
8.4213
92.7
2355
64
2.5
COMPRESSORS
CIRCUIT #2
M2 L6 M8
COMPRESSORS
L1
L8M4L2
ISOLATOR MOUNTING HOLE LOCATIONS ARE ON BOTTOM SURFACE OF UNIT.
M1
M3
L3
M5
L5 L7
M7
CIRCUIT #1
L4 M6
[152]
Ø6.0
VICTAULIC
CONN. TYP.
1711 67.4
12.4315
129.23281
1118
44.0
43.8
1114
QTY 8
95.8
2433
2743
108.0
.75
19
52 2.0
52 2.0
4617
181.8   w/o STRAINER OPTION
LBSKGLBSKGLBSKGLBSKGLBSKGLBSKGLBSKGLBSKGLBSKGLBSKGLBSKGLBSKGLBSKGLBSKGLBSKGLBSKG
AGZ226E
9413427096004354165975316407441296588128258210704851058480708321700318156470915467011281581126657411515221138516832377822373
AGZ241E
9501431096884394168376316717581309594129958910754881068484701318696316158671915747141292586128358211585251149521826375820372
L8 L1L5
KG
M1
UNIT 
MODEL
L2L3L4L6SHIP WEIGHTOPER. WEIGHT LBS
LIFTING (SHIPPING) WEIGHT BY CORNER
L7M7M8
MOUNTING (OPERATING) WEIGHT
KGLBS
M5M6 M3M4 M2
IN.MMIN.MMIN.MM
AGZ226E43.8111341.91064113.82891
AGZ241E43.8111341.91064113.22875
CG LOCATION
UNIT
MOD EL
XYZ

Dimensions and Weights - Heat Recovery Units
www.DaikinApplied.com 41 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Dimensions and Weights - Heat Recovery Units
Figure 41: AGZ075E - AGZ100E - Heat Recovery Option
X
Y
305
12.0127
5.0
80
3.1
51
2.0
Z
22
.875 KNOCKOUTS
POWER ENTRY KNOCKOUTS
ARE ON THE OPPOSITE SIDE 
OF THE CONTROL BOX
OUTLET
CIR 1
HRWATER
INLET
BACK OF UNIT (HEAT RECOVERY DETAIL)OUT
TYP.
CIR 2
DISCH.
WATER
DISCH.
IN TYP.
HR
1
47.1
1196
 REF.
20.4
519
 REF.
1118
44.0  REF.
CIRCUIT 2
REMOVED
HEAT
CIRCUIT 2
M1 - M4, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE.
M1
M3
M2
M4
L1
COMPR.
COILS AND FANS
TOP VIEW WITH
L3
L2
CIRCUIT 1
RECOVERY
L4
COMPR.
CIRCUIT 1
HEAT
RECOVERY
2433 95.8
52
19 .750
52
QTY. 4
A  (w/o STRAINER OPTION)
2.0
CONNECTIONS
315
12.4
984
38.7
2.0
1118
44.0
C/L FOR
ALL WATER
B
CONTROL
FRONT OF UNIT
BOX
[22]
.875 POWER ENTRY
KNOCKOUTS FRONT OR RIGHT SIDE
2
2.5
64
2.5
.875
QTY. 3
CONNECTIONS
FIELD CONTROL
 KNOCKOUTS
22
64
165
6.5
175 6.9
LIFTING BRACKETS
8.4
92.7
2355
213
98.6
2506
88.02235
DIMENSION DOES NOT INCLUDE
292
11.5
0A D
AGZ-E, 6 FANS w/ OPTIONAL HEAT RECOVERY 334547112
L1 L2
L4L3
OUTLET
WATER
EVAP.  WATER INLET
1
WYE-STRAINER REQUIRED (FACTORY OR FIELD
 INSTALLED OPTION)
1
HEAT RECOVERY
WATER INLET
EVAP. 
HEAT RECOVERY
WATER OUTLET
2
519 20.4
1.5
37
1196 47.1
49
1.9
24.0
609
147.0
3733
11.4
290
6.0
153
916
36.1
858
33.8
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
 MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR & HEAT RECOVERY WATER INCLUDED.  SHIPPING AND OPERATING WEIGHTS WITH HEAT RECOVERY DO NOT INCLUDE THE WEIGHTS OF ANY OTHER OPTIONS OR ACCESSORIES.
THAN 350 MCM.
BE USED FOR POWER ENTRY WIRE SIZES LARGER
2.
NOTE:
HEAT RECOVERY WATER CONNECTIONS 1.
FOR CIRCUIT 1 & 2 ARE CONNECTED WITH
A TEE AND HAVE ONE INLET & ONE OUTLET.
CONNECTION SIZES ARE 2.0 NOMINAL VICTAULIC.
IT IS RECOMMENDED THAT THE SIDE LOCATIONS
L1 - L4,
LIFTING 
LOCATIONS
I N . MM I N . MM I N . MM
AGZ075E45.5 1156 39.0 991 60.4 1534
AGZ080E44.5 1130 39.5 1003 59.5 1511
AGZ090E44.5 1130 39.5 1003 59.5 1511
AGZ100E44.0 1118 39.3 998 59.8 1519
CG LOCATION
UNIT
MOD EL
XYZ
LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG
AGZ075E4613 2092 4690 2127 1294 587 1388 630 932 423 1000 454 1129 512 1211 549 1134 514 1216 552
AGZ080E4734 2147 4817 2185 1385 628 1415 642 957 434 978 444 1210 549 1237 561 1172 532 1198 543
AGZ090E4764 2161 4847 2199 1393 632 1424 646 963 437 984 446 1218 552 1245 565 1179 535 1205 547
AGZ100E4936 2239 5039 2286 1452 659 1449 657 1019 462 1017 461 1273 577 1270 576 1250 567 1247 566
M2
OPER. WEIGHT
LBS KG LBS KG
M1M3 M4
MOUNTING (OPERATING) WEIGHT
L1
UNIT MODEL
L2L3L4
LIFTING (SHIPPING) WEIGHT BY CORNER SHIP WEIGHT
IN. MM IN. MM IN. MM
AGZ075E55.6 1412 27.1 688
AGZ080E54.4 1382 25.9 658
AGZ090E54.4 1382 25.9 658
AGZ100E51.6 1311 23.1 587
76
UNIT
MO D EL
AB
EVAP DIM'S
NOM. VICT AULIC 
CO NN.  SIZE
3.0

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 42 www.DaikinApplied.com
Dimensions and Weights - Heat Recovery Units
Figure 42: AGZ110E - AGZ130E - Heat Recovery Option
Y
X
51
2.0 80
3.1
305
12.0
127
5.0
22
.875 KNOCKOUTS
POWER ENTRY KNOCKOUTS
ARE ONTHE OPPOSITE SIDE
OF THE CONTROL BOX
Z
IN TYP.
DISCH.
DISCH.
TYP.
OUT
CIR 2
HR
OUTLET
WATER
INLET
WATER
CIR 1
HR
BACK OF UNIT (HEAT RECOVERY DETAIL)
1
1196 47.1  REF.
 REF. 44.0
1118
519
20.4  REF.
 SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.
 MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED.
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
NOTE:
1.
HEAT RECOVERY WATER CONNECTIONS FOR 
CIRCUIT 1 & 2 ARE CONNECTED WITH A TEE AND 
HAVE ONE INLET & ONE OUTLET. CONNECTION 
SIZES ARE 2.0 NOMINAL VICTAULIC.
2.
IT IS RECOMMENDED THAT THE SIDE LOCATIONS 
BE USED FOR POWER ENTRY WIRE SIZES LARGER 
THAN 350 MCM.
0A
D
334547122
AGZ-E 8 FANS w/ HEAT RECOVERY
FRONT OF UNIT
BOX
CONTROL
[22]
.875 POWER ENTRY
KNOCKOUTS
FRONT OR RIGHT SIDE
2
64
2.5
QTY. 3
CONNECTIONS
FIELD CONTROL
 KNOCKOUTS
.87522
8.4213
6.9
175
6.5
165
11.5
292
64
2.5
2355
92.7
98.6
2506
2235
88.0
DIMENSION DOES NOT INCLUDE
LIFTING BRACKETS
L2
L1
L4
L3
EVAP.  INLET WATER
OUTLET
LOCATIONS
LIFTING
L1 - L4,
WATER EVAP.
(FACTORY OR REQUIRED
OPTION)
FIELD INSTALLED
WATER INLET
HEAT RECOVERYWATER OUTLET
HEAT RECOVERY
WYE-STRAINER
1
1
2
519 20.4
1.5
37
47.1
1196
50
2.0
290
11.4
24.0
609
192.1
4879
39.2
996
6.0
153
858
33.8
HEAT
M1 - M6, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE.
M1
M3 M5
L1 L3
M 2L 2 M4 L4
CIRCUIT 1
CIRCUIT 2
M6
RECOVERY
CIR. 2 COMPR. CIR. 1
TOP VIEW WITH
COMPR.
REMOVED. COILS AND FANS
HEAT
RECOVERY
52 2.0
A  (w/o STRAINER OPTION)
12.4
315
95.8
2433
59.0
1499
24.8
630
2.052
QTY. 6
.75019
CONNECTIONS
1118
44.0
C/L FOR
ALL WATER
B
LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG
AGZ110E5697 2584 5807 2634 1739 789 1771 803 1083 491 1104 501 1400 635 1427 647 894 406 911 413 582 264 593 269
AGZ120E5952 2700 6071 2754 1884 855 1917 870 1066 484 1085 492 1524 691 1551 704 926 420 943 428 558 253 568 258
AGZ130E6061 2749 6196 2810 1911 867 1862 845 1159 526 1129 512 1546 701 1506 683 973 441 948 430 620 281 604 274
LBS
M5 M6
MOUNTING (OPERATING) WEIGHT
M3 M4 L1M2
KG
M1
UNIT 
MODEL
L2L3L4
LIFTING (SHIPPING) WEIGHT BY CORNER
SHIP WEIGHT OPER. WEIGHT LBS KG
IN.MMIN.MMIN.MM
AGZ110E44.4 1128 42.1 1069 73.5 1867
AGZ120E44.4 1128 43.3 1100 70.6 1793
AGZ130E43.4 1102 41.1 1044 72.7 1847
CG LOCATION
UNIT
MO D E L
XYZ
IN.MMIN.MMIN.MM
AGZ110E95.5 2426 69.1 1755
AGZ120E93.9 2385 67.5 1715
AGZ130E92.0 2337 65.5 1664
3.0 76
UNIT
MO D E L
AB
EVAP DIM'S
NO M .   VICT AULIC 
CO NN. SIZE

Dimensions and Weights - Heat Recovery Units
www.DaikinApplied.com 43 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Figure 43: AGZ140E - AGZ161E - Heat Recovery Option
X
Y
80
3.1
22
.875 KNOCKOUTS
POWER ENTRY KNOCKOUTS
ARE ON THE OPPOSITE SIDE
OF THE CONTROL BOX
51
2.0
305
12.0127
5.0
Z
COILS AND FANS
M1 - M4, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE.
M1
L1
M3
L3
M5
M 2L 2 M4 L 4M 6
REMOVED
TOP VIEW WITH
CIRCUIT 2
HEAT
RECOVERY
CIRCUIT 1
CIR. 1CIR. 2
COMPR.
COMPR.
HEAT
RECOVERY
1564
61.6
2.052
12.4
315
95.8
2433
19 .750
QTY. 6
67.4
1711
52 2.0
B
A   (w/o STRAINER OPTION)
1118
44.0
C/L FOR
ALL WATER
CONNECTIONS
334547132AGZ-E 10 FANS,
4 COMPRESSORS w/
OPTIONAL HEAT RECOVERY
 SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.
 MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED.
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
NOTE:
HEAT RECOVERY WATER CONNECTIONS FOR CIRCUIT 1 & 2 ARE CONNECTED WITH A TEE 1.
AND HAVE ONE INLET & ONE OUTLET. CONNECTION SIZES ARE 2.0 NOMINAL VICTAULIC.
IT IS RECOMMENDED THAT THE SIDE LOCATIONS BE USED FOR POWER ENTRY WIRE SIZES 2.
LARGER THAN 350 MCM.
BACK OF UNIT (HEAT RECOVERY DETAIL)
TYP.
OUT
DISCH.
IN TYP.
DISCH.
CIR 2
HR
CIR 1 HR
OUTLET
WATER
INLET
WATER
1
519 20.4  REF.
 REF. 47.1
1196
1118
44.0  REF.
FRONT OF UNIT
BOX
CONTROL
[22]
.875 
POWER ENTRY
KNOCKOUTS
FRONT OR
RIGHT SIDE
2
64
2.5
QTY. 3
CONNECTIONS
FIELD CONTROL
 KNOCKOUTS
.87522
6.5
165
6.9
175
64
2.5
2235
88.0
DIMENSION DOES NOT INCLUDE
LIFTING BRACKETS
98.6
2506
92.7
2355
8.4213
292
11.5
EVAP.  INLET
WATER 
L2 L1
L4 L3
OUTLET
LOCATIONS
LIFTING
L1 - L4
WATER 
REQUIRED WYE-STRAINER
INSTALLED OPTION)
(FACTORY OR FIELD
WATER INLET
HE
AT RECOVERY
WATER OUTLET
HEAT RECOVERY
EVAP. 
1
1
2
519 20.4
1.5
37
47.1
1196
50
2.0
1919
75.5
24.0
609
210
8.3
237.2
6025
11.4
290
858
33.8
LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG
AGZ140E6805 3087 6948 3152 1781 808 1810 821 1594 723 1620 735 1328 602 1349 612 1125 510 1143 518 994 451 1010 458
AGZ150E6880 3121 7036 3191 1804 818 1820 826 1620 735 1635 742 1346 611 1359 616 1143 518 1154 523 1013 459 1022 464
AGZ161E6968 3161 7130 3234 1826 828 1855 841 1631 740 1656 751 1365 619 1386 629 1154 523 1172 532 1019 462 1035 469
LBS
M5 M6
MOUNTING (OPERATING) WEIGHT
M3 M4 L1M2
KG
M1
UNIT 
MODEL
L2L3L4
LIFTING (SHIPPING) WEIGHT BY CORNER
SHIP WEIGHT OPER. WEIGHT LBS KG
I N . MM I N . MM I N . MM I N . MM I N . MM I N . MM
AGZ140E44.4 1128 42.3 1074 89.0 2261 122.1 3101 67.5 1715
AGZ150E44.2 1123 42.6 1082 89.2 2266 120.5 3061 65.9 1674
AGZ161E44.3 1125 42.5 1080 89.0 2261 120.5 3061 65.9 1674
UNIT
MO D E L
XYZ
EVAP DIM'S
AB
NO M .   VICT AUL IC 
CONN. SIZE
4.0 102
CG LOCATION
0A D

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 44 www.DaikinApplied.com
Dimensions and Weights - Heat Recovery Units
Figure 44: AGZ170E - AGZ180E - Heat Recovery Option
80
3.1
22
.875 KNOCKOUTS
POWER ENTRY KNOCKOUTS
ARE ON THE OPPOSITE SIDE
OF THE CONTROL BOX
51
2.0
305
12.0127
5.0
Z
X
Y
WATER 
INLET
L1 L2
OUTLET
L3 L4
LIFTING
LOCATIONS
WATER  L1 - L4
WYE-STRAINER REQUIRED (FACTORY OR FIELD INSTALLED OPTION)
HEAT RECOVERY
WATER INLET
EVAP. 
1
EVAP. 
HEAT RECOVERY
WATER OUTLET
1
2
20.4519
2.0
50
1196 47.1
37
1.5
11.4
290
8.3
210
609
24.0
1919
75.5
6025
237.2
858
33.8
CONTROL
FRONT OF UNIT
BOX
[22]
.875 
POWER ENTRY KNOCKOUTS FRONT OR RIGHT SIDE
2
QTY. 3
CONNECTIONS
FIELD CONTROL
 KNOCKOUTS
22 .875
2.5
64
165
175
6.9
6.5
64
2.5
8.4213
LIFTING BRACKETS
DIMENSION DOES NOT INCLUDE
88.0
2235
2506
98.6
92.72355
292
11.5
HEAT
M1 - M4, ISOLATOR MOUNTING HOLE LOCATIONS ON BOTTOM SURFACE OF UNIT BASE.
M1
L1
M3
L3
M5
M 2L 2 M4 L4
CIRCUIT 2
M6
CIR. 1
CIRCUIT 1
RECOVERY
COMPR.
TOP VIEW WITH COILS AND FANS REMOVED
COMPR. CIR. 2
HEAT
RECOVERY
.75019
QTY. 6
A   (w/o STRAINER OPTION)
B
2.0
52
52 2.0
315
12.4
2433
95.8
1564
61.6
1711
67.4
1118
44.0
C/L FOR
ALL WATER
CONNECTIONS
WATER
BACK OF UNIT (HEAT RECOVERY DETAIL)
OUT
TYP.
DISCH.
DISCH.
IN TYP.
WATER
OUTLET HR CIR 2
INLET
HR CIR 1
1
 REF. 44.0
1118
 REF. 47.1
1196
519
20.4  REF.
NOTE: LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS.
 MOUNTING WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR WATER INCLUDED.  SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.
NOTE:
HEAT RECOVERY WATER CONNECTIONS FOR CIRCUIT 1 & 2 ARE CONNECTED WITH A TEE 1.
AND HAVE ONE INLET & ONE OUTLET. CONNECTION SIZES ARE 2.0 NOMINAL VICTAULIC.
IT IS RECOMMENDED THAT THE SIDE LOCATIONS BE USED FOR POWER ENTRY WIRE SIZES 2.
LARGER THAN 350 MCM.
LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG
AGZ170E7525 3413 7696 3491 1991 903 1942 881 1818 825 1773 804 1483 673 1446 656 1274 578 1242 563 1139 517 1111 504
AGZ180E7789 3533 7971 3616 2016 914 2042 926 1854 841 1878 852 1501 681 1520 689 1296 588 1312 595 1164 528 1179 535
KG
M1M5 M6
MOUNTING (OPERATING) WEIGHT
M3 M4 L1M2
UNIT 
MODEL
L2L3L4
LIFTING (SHIPPING) WEIGHT BY CORNER
SHIP WEIGHT OPER. WEIGHT LBS KG LBS
IN. MM IN. MM IN. MM IN. MM IN. MM IN. MM
AGZ170E43.5 1105 40.6 1031 89.7 2278 119 3023 64.3 1633
AGZ180E44.3 1125 39.9 1013 90.0 2286 117 2972 62.4 1585
B
NOM .   VICT AULIC 
CO NN.   SIZE
4.0 102
CG LOCATION
UNIT
MODEL
XYZ
EVAP DIM'S
A
334547132AGZ-E 10 FANS,
6 COMPRESSORS w/
OPTIONAL HEAT RECOVERY
0A D

Dimensions and Weights - Heat Recovery Units
www.DaikinApplied.com 45 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Figure 45: AGZ191E - AGZ211E - Heat Recovery Option
SIDE OF CONTROL BOX
ARE ON OPPOSITE
POWER ENTRY POINTS
 KNOCKOUTS .875
22
127
5.0
80
3.1
51
2.0
305 12.0
Z
2506
98.6
X
Y
WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR 
WATER INCLUDED. SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE 
THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.
2. IT IS RECOMMENDED THAT THE SIDE LOCATIONS BE USED FOR
LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS. MOUNTING 
NOTE: 
POWER ENTRY WIRE SIZES LARGER THAN 350 MCM.
NOTE:
HEAT RECOVERY WATER CONNECTIONS FOR CIRCUIT 1 & 2 ARE 1.
CONNECTED WITH A TEE AND HAVE ONE INLET & ONE OUTLET.
CONNECTION SIZES ARE 2.0 NOMINAL VICTAULIC.
00 D
334547154
AGZ-E 12 FANS - BRAZED PLATE EVAP WITH HEAT RECOVERY
HEAT
HEAT RECOVERY
L1
L2
L3
WATER
INLET
OUTLET
1
L5
CG
WATER
INLET
RECOVERY
WATER OUTLET
L4 L6
EVAP
1
WATER
2
47.11196
20.4
519
2436
95.9
2207
86.9
609 24.0
37
1.5
1919
75.5
7171
282.3
50
2.0
36.3
923
12.1
308
3167
124.7
CIRCUIT 1
HEAT RECOVERY
TOP VIEW
WITH COILS
M1
M 2L 2
L1
L4
L3
COMPRESSORS
L5
M3 M5 M7
M6 M8 L6
CIRCUIT #2
CIRCUIT #1
COMPRESSORS
M4
AND FANS
REMOVED
ISOLATOR MOUNTING HOLE LOCATIONS ARE ON BOTTOM SURFACE OF UNIT
CIRCUIT 2
HEAT RECOVERY
[152]
Ø6.0
VICTAULIC
CONN. TYP.
2.052 2.052
315
12.4
2433
95.8
1114
43.8
1596
62.9
1711
67.4
19
.75
QTY 8
1118
44.0
C/L FOR
WATER
CONNECTIONS
3577 140.8
  w/o STRAINER OPTION
88.2
2241
1118
44.0
CG
CONTROL
FRONT OF UNIT
BOX
2
2.564
FIELD CONTROL
22
CONNECTIONS
 KNOCKOUTS .875
2355
92.7
213 8.4
2235
88.0
DIMENSION DOES NOT
INCLUDE LIFTING BRACKETS
165
6.5
175
6.9
292
11.5
64
2.5
22 .875 KNOCKOUTS
POWER ENTRY POINTS
FRONT & RIGHT SIDE
WATER
OUT
TYP.
DISCH
DISCH
IN TYP.
BACK OF UNIT (HEAT RECOVERY DETAIL)
WATER
OUTLET
HR
CIR 2
INLET HR
CIR 1
1
 REF. 44.0
1118
 REF. 47.1
1196
519
20.4  REF.
LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG
AGZ191E8970 4069 9154 4152 1676 760 1664 755 1506 683 1495 678 1319 598 1310 594 1500 680 1490 676 1192 541 1184 537 1052 477 1044 474 849 385 843 382
AGZ211E9005 4085 9189 4168 1684 764 1679 762 1509 684 1505 683 1316 597 1313 596 1507 684 1503 682 1195 542 1192 541 1052 477 1049 476 847 384 844 383
UNIT 
MODEL
L2L3L4
LIFTING (SHIPPING) WEIGHT BY CORNER
L6
SHIP WEIGHT
M7 M8
MOUNTING (OPERATING) WEIGHT
KG LBS
M5 M6 L5
KG
M1M3 M4 M2
OPER. WEIGHT
LBS
L1
I N . MM I N . MM I N . MM
AGZ191E43.8 1113 40.8 1036 106.6 2708
AGZ211E43.9 1115 40.8 1036 106.4 2703
CG LOCAT ION
UNIT
MOD E L
XYZ

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 46 www.DaikinApplied.com
Dimensions and Weights - Heat Recovery Units
Figure 46: AGZ226E - AGZ241E - Heat Recovery Option
127
5.0
51
2.0
305
12.0
80
3.1
22 .875 KNOCKOUTS
POWER ENTRY POINTS
ARE ON OPPOSITE
SIDE OF CONTROL BOX
Z
X
Y
AND FANS
THE WEIGHTS OF ANY OPTIONS OR ACCESSORIES.
REMOVED
WATER INCLUDED. SHIPPING AND OPERATING WEIGHTS DO NOT INCLUDE 
WEIGHTS ARE BASED ON UNIT OPERATING WEIGHT WITH EVAPORATOR 
NOTE: 
WITH COILS
TOP VIEW
LIFTING WEIGHTS ARE BASED ON UNIT SHIPPING WEIGHTS. MOUNTING 
NOTE:
HEAT RECOVERY WATER CONNECTIONS FOR CIRCUIT 1 & 2 ARE  1.
 CONNECTED WITH A TEE AND HAVE ONE INLET & ONE OUTLET.
 CONNECTION SIZES ARE 2.0 NOMINAL VICTAULIC.
IT IS RECOMMENDED THAT THE SIDE LOCATIONS BE USED FOR 2.
POWER ENTRY WIRE SIZES LARGER THAN 350 MCM.
00
334547144
AGZ-E 14 FANS
- BRAZED PLATE
 EVAP w/ HEAT RECOVERY
D
WATER
OUTLET
L1
WATER
L4L2
INLET
L3 L5
HEAT
EVAP
1
L8
WATER
CG
1
L6
L7
RECOVERY
INLET
HEAT RECOVERY
WATER OUTLET
2
47.1
1196
2.0
50
4207 165.6
519 20.4
609
24.0
86.92207
1375 54.1
2207
86.9
75.51919
8317 327.4
1.537
308 12.1
923
36.3
CONTROL
CG
[22] POWER ENTRY POINTS FRONT AND RIGHT SIDE
BOX
.875 KNOCKOUTS
FRONT OF UNIT
[22]
.875 KNOCKOUTS
FIELD CONTROL
CONNECTIONS
2
92.7
2355
8.4
98.6
2506
11.5
292
2.5
64
2235
88.0
INCLUDE LIFTING BRACKETS
DIMENSION DOES NOT
165
6.5
6.9175
213
64
2.5
WATER
OUT
TYP.
BACK OF UNIT (HEAT RECOVERY DETAIL)
OUTLET
DISCH
IN TYP.
HR CIR 1
WATER
INLET
HR
CIR 2
DISCH
1
47.1
1196
 REF
20.4
519
 REF
1118
44.0  REF
M8
CIRCUIT 1
HEAT RECOVERY
COMPRESSORS
COMPRESSORS
CIRCUIT 2
HEAT RECOVERY
ISOLATOR MOUNTING HOLE LOCATIONS ARE ON BOTTOM SURFACE OF UNIT.
M1
L1
M3
L3
M5
L5
CIRCUIT #2
L7
L4 M6
M7
M2 L6M4
CIRCUIT #1
L2 L8
[152]
Ø6.0
VICTAULIC
CONN. TYP.
1711 67.4
CONNECTIONS
.75
44.0
C/L FOR
1118
WATER
1118
QTY 8
44.0
3281 129.2
2743
108.0
1114
43.8
2433
95.8
315 12.4
52 2.0 52 2.0
19
4617
181.8   w/o STRAINER OPTION
LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG LBS KG
AGZ226E
9784 4438 10012 4541 1573 713 1563 709 1309 594 1301 590 1145 519 1138 516 881 400 875 397 1489 675 1479 671 1304 591 1295 587 1219 553 1211 549 1011 459 1004 455
AGZ241E
9873 4478 10101 4582 1597 724 1593 723 1321 599 1318 598 1150 522 1147 520 874 396 872 396 1511 685 1507 684 1315 596 1312 595 1226 556 1223 555 1005 456 1003 455
M7 M8
MOUNTING (OPERATING) WEIGHT
KG LBS
M5 M6 M3 M4 M2
UNIT 
MODEL
L2L3L4
LIFTING (SHIPPING) WEIGHT BY CORNER
L6
SHIP WEIGHT OPER. WEIGHT LBS
L7L8 L1L5
KG
M1
I N . MM I N . MM I N . MM
AGZ226E
43.9 1115 42.1 1069 121.0 3073
AGZ241E
44.0 1118 42.2 1072 120.3 3056
CG LOCAT ION
UNIT
MO D E L
XYZ

Isolators
www.DaikinApplied.com 47 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Isolators
Figure 47: Spring Isolator
Figure 48: Rubber-in-Shear (RIS) Isolator
Transfer the unit as indicated in the current AGZ-E Installation
and Operation Manual, which can be found on www.
DaikinApplied.com. In all cases, set the unit in place and level.
If antiskid pads are used, do not use hold down bolts. If hold
down bolts are used, do not use anti-skid pads.
When spring isolators are required, install springs running
under the main unit supports. Unit should be installed on
blocks or shims at the listed free height. Isolator springs should
not be loaded until the installation is complete, then adjust the
springs to the vendor listed compression gap for the load point.
When securing the isolator, do not over-tighten the mounting
bolts. Over-tightening may result in cracking of the cast isolator
housing and will have a negative impact on the isolation effect.
Installation of spring isolators requires flexible piping
connections and at least three feet of flexible electrical conduit
to avoid straining the piping and transmitting vibration and
noise.
Mounting locations for each model can be found in the
Dimensions and Weights section, starting on page 33
Neoprene waffle pads, supplied by customers, should be
mounted at the defined mounting point locations along the rail
length.
9.25 [235.0]
10.5 [266.7]
.56 [14.3]
7.75 [196.9]
3
[76.2]
.62 [15.8]
6.25
[127.0]
FREE HT.
5\X [127.0]
OPER. HT.
.5 [12.7] DIA.
POSITIONING
PIN
.25 [6.4]
ELASTOMERIC PAD
ADJ. BOLT
ELASTOMERIC
SNUBBER
.625
[15.9]
.25 TO .5 GAP
[6.4 to 12.7]

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 48 www.DaikinApplied.com
Electrical Data
Electrical Data
Electrical Data Notes
1. Power wiring connections to the chiller may be done with
either copper or aluminum wiring. Wire should be sized
per NEC and/or local codes. Wire sizing and wire count
must fit in the power connection lug sizing shown in the
Electrical Data tables starting on page 53.
2. Unit wire size ampacity (MCA) is equal to 125% of the
largest compressor-motor RLA plus 100% of RLA of all
other loads in the circuit.
3. Recommended Fuse Sizes are selected at approximately
175% of the largest compressor RLA, plus 100% of all
other loads in the circuit.
4. Maximum Fuse or breaker size is equal to 225% of the
largest compressor RLA, plus 100% of all other loads.
5. The control transformer is furnished and no separate
115V power is required. For both single and multi-point
power connections, the control transformer is in circuit
#1 with control power wired from there to circuit #2. In
multi-point power, disconnecting power to circuit #1
disconnects control power to the unit.
6. Wire sizing amps is 15 amps if a separate 115V power
supply is used for the control circuit.
7. Single-point power supply requires a single disconnect
to supply electrical power to the unit. This power supply
must either be fused or use a circuit breaker.
8. All field wire lug range values given in the Electrical Data
tables starting on page 53 apply to 75°C rated wire per
NEC.
9. Must be electrically grounded according to national and
local electrical codes.
Circuit Breakers
Factory installed compressor circuit breakers are standard on
units with single point power supply only. This option provides
compressor short circuit protection and makes servicing easier
Voltage Limitations:
1. Within 10 percent of nameplate rating.
2. Voltage unbalance not to exceed 2% with a resultant
current unbalance of 6 to 10 times the voltage unbalance
per NEMA MG-1, 2009 Standard Rev. 1-2010.
Table 30: Standard and HSCCR Panel Ratings
Panel Type 208V / 230V380V / 400V / 460V 575V
Standard 5kA 5kA 5kA
HSCCR 65kA 65kA 25kA
Electrical Control Center
Operating and equipment protection controls and motor
starting components are separately housed in a centrally
located, weather resistant control panel with hinged and
tool-locked doors. In addition to the MicroTech
®
III controller
described in the next sections, the following components are
housed in the panel:
• Power terminal blocks, multi-point connection standard
• Control, input, and output terminal block
• Control transformer
• Optional disconnect switch (through-the-door handle)
• Compressor motor inherent thermal and overload
protection is standard
• Optional phase voltage monitor with under/over voltage
and phase reversal protection
• Fan contactors with short circuit protective devices.
• Optional ground fault protection
• FanTrol
®
fan staging head pressure control system
• Power connections are per Table 31
Power Connections
Table 31: Power Connection Availability
Power Connection
Power
Block
Disc.
Swt.
Comp.
Circuit
Breakers
Panel High
Short Circuit
Current Rating
Optional Single PointStd. Opt. Std. Opt.
Standard Multi-PointStd. Opt. Not Avail. Not Avail.
Definitions:
1. Power Block: An electrical device to directly accept field wiring without any disconnecting means.
2. Disconnect Switch: A molded case switch that accepts
field wiring and disconnects main power to the entire
unit or each main power supply if the multi-point power
supply option is selected. This option does not provide
overcurrent protection.
3. Compressor Circuit Breakers: A manually reset circuit
breaker for each compressor, providing compressor
only short circuit protection and located ahead of the
contactor.
4. Control Panel High Short Circuit Current Rating:
(Previously known as “withstand rating”). The entire
control panel is designed for short circuit current rating
as shown in Table 30. In the event of a short circuit, the
damage is contained within the control panel enclosure.

Electrical Data
www.DaikinApplied.com 49 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Figure 49: Typical Field Wiring Diagram (Single-Point Connection)
NOCOM
BELL
4-20MA FOR
DEMAND LIMIT
(BY OTHERS)
4-20MA FOR
EVAP. - LWT RESET
(BY OTHERS)
DOUBLE SET POINT/MODE
SWITCH
(BY OTHERS)
TIME
CLOCK
OFF
MANUAL
ON
AUTO
585
IF REMOTE STOP
CONTROL IS USED
REMOVE LEAD 585
FROM TERM
TB2-52 TO TB2-72
TIME CLOCK
OFF
MANUAL
ON
AUTO
71
TB2
70 TB2
69
TB2
68 TB2
TB122
TB1
1A
TO
COMPRESSOR(S)
AND FAN MOTORS
ALARM BELL
RELAY
120
VAC
FU5
T1
FU6
CONTROL CIRCUIT
FUSE
SEE NOTE 2
FU4
REMOTE
STOP SWITCH
(BY OTHERS)
TB2
TB2
43
83
UNIT ALARM
120 VAC
TB1
TB1
TB2
TB2
TB2
TB2
54
52
34
74
72
32A
ALARM
BELL OPTION
3 PHASE
POWER
SOURCE
DISCONNECT SWITCH
OR
POWER BLOCK
CIRCUIT BREAKER
(BY OTHERS)
12
TB2
TB2
45
67
EXTERNAL
ALARM/
EVENT
DISCONNECT
(BY OTHERS)
N
120 VAC
OPTIONAL
FIELD SUPPLIED
CONTROL POWER
FU
15A for 1.5 KVA
30A for 3.0KVA
(BY OTHERS)
Notes:
1.) ALL FIELD WIRING TO BE INSTALLED AS
NEC CLASS 1 WIRING SYSTEM WITH
CONDUCTOR RATED 600 VOLTS.
2.) IF FIELD SUPPLIED, CONTROL POWER USER
MUST REMOVE FU6, AND WIRE NUMBERS
299, 301A INSIDE CONTROL PANEL
3.) ** = USE 'DRY CONTACTS' ONLY
4.) DO NOT SUPPLY FIELD POWER TO
24VAC OR 120VAC CONTROL CIRCUITS.
301A
301 299
ABR
555A
IF EXTERNAL
ALARM/EVENT
IS USED
REMOVE LEAD 555A
FROM TERM
TB2-45 TO TB2-67
N
24 VAC
FIELD WIRING DIAGRAM
WITH MICROTECH CONTROLLER
ALARM BELL RELAY
120VAC @ 1.0AMP MAX
EARTH
GROUND
ABR
**
**
**
24VAC @ 0.4AMP MAX.
**
**
**
CHW FLOW SWITCH
-MANDATORY-
(BY OTHERS)
NOR. OPEN PUMP
AUX. CONTACTS
(OPTIONAL)
61
TB2
TB2
44
**
**
N
120 VAC
TB1
TB1
CHWR1
PUMP NO.1 RELAY
(BY OTHERS)
120VAC @ 1.0AMP MAX
35
33
CHWR2
PUMP NO.2 RELAY
(BY OTHERS)
120VAC @ 1.0AMP MAX
N
120 VAC
TB1
TB1
P2+
31
_
+
_
+
GND
(317)
T3
T2
T1
L3
L2
L1
PANEL
/(655)
/(652)
/(645)
/(637)
/(629)
/(225)
/
(235)
(630)
/(542)
/(649)
/(626)
/(714)
NOTE: Use dry contacts only. DO NOT supply Field
Power to this circuit. For Factory Supplied Thermal
Dispersion Flow Switch wiring, see wiring instruction in
Kit.

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 50 www.DaikinApplied.com
Electrical Data
Figure 50: Typical Field Wiring Diagram (Multi-Point Connection)
NOCOM
BELL
4-20MA FOR
DEMAND LIMIT
(BY OTHERS)
4-20MA FOR
EVAP. - LWT RESET
(BY OTHERS)
DOUBLE SET POINT/MODE
SWITCH
(BY OTHERS)
TIME
CLOCK
OFF
MANUAL
ON
AUTO
585
IF REMOTE STOP
CONTROL IS USED
REMOVE LEAD 585
FROM TERM
TB2-52 TO TB2-72
TIME CLOCK
OFF
MANUAL
ON
AUTO
71
TB2
70 TB2
69
TB2
68 TB2
TB122
TB1
TO CIRCUIT 1
COMPRESSOR(S)
AND FAN MOTORS
ALARM BELL
RELAY
120
VAC
FU5
T1
FU6
CONTROL CIRCUIT
FUSE
SEE NOTE 2
FU4
REMOTE
STOP SWITCH
(BY OTHERS)
TB2
TB2
43
83
ALARM BELL
OPTION
TB2
TB2
TB2
TB2
54
52
74
72
3 PHASE
POWER
SOURCE
DISCONNECT SWITCH
OR
POWER BLOCK
CIRCUIT BREAKER 1
(BY OTHERS)
12
TB2
TB2
45
67
EXTERNAL
ALARM/
EVENT
DISCONNECT
(BY OTHERS)
N
120 VAC
OPTIONAL
FIELD SUPPLIED
CONTROL POWER
FU
TO CIRCUIT 2
COMPRESSOR(S)
AND FAN MOTORS
3 PHASE
POWER
SOURCE
DISCONNECT SWITCH
OR
POWER BLOCK
CIRCUIT BREAKER 2
(BY OTHERS) 15A for 1.5 KVA
30A for 3.0KVA
(BY OTHERS)
1A
301A
301 299
ABR
555A
IF EXTERNAL
ALARM/EVENT
IS USED
REMOVE LEAD 555A
FROM TERM
TB2-45 TO TB2-67
N
24 VAC
120 VAC
TB1 TB1
34
32A
ALARM
BELL OPTION ALARM BELL RELAY
120VAC @ 1.0AMP MAX
FIELD WIRING DIAGRAM
WITH MICROTECH CONTROLLER
EARTH
GROUND
ABR
**
**
**
**
**
1.) ALL FIELD WIRING TO BE INSTALLED AS
NEC CLASS 1 WIRING SYSTEM WITH
CONDUCTOR RATED 600 VOLTS.
2.) IF FIELD SUPPLIED, CONTROL POWER USER
MUST REMOVE FU6, AND WIRE NUMBERS
299, 301A INSIDE CONTROL PANEL
3.) ** = USE 'DRY CONTACTS' ONLY
4.) DO NOT SUPPLY FIELD POWER TO
24VAC OR 120VAC CONTROL CIRCUITS.
Notes:
24VAC @ 0.4AMP MAX.
**
CHW FLOW SWITCH
-MANDATORY-
(BY OTHERS)
NOR. OPEN PUMP
AUX. CONTACTS
(OPTIONAL)
TB2
TB2
44
61
/(649)
**
**
N
120 VAC
TB1
TB1
CHWR1
PUMP NO.1 RELAY
(BY OTHERS)
120VAC @ 1.0AMP MAX
35
33
CHWR2
PUMP NO.2 RELAY
(BY OTHERS)
120VAC @ 1.0AMP MAX
N
120 VAC
TB1 TB1
P2+
31
_
+
_
+
T3
T2
T1
L3
L2
L1
T3
T2
T1
L3
L2
L1
GND
(317)
PANEL
/(652)
/(655)
/(637)
/(629)
/(231)
/(645)
/
(240)
(630)
/(540)
/(626)
/(714)
NOTE: Use dry contacts only. DO NOT supply Field
Power to this circuit. For Factory Supplied Thermal
Dispersion Flow Switch wiring, see wiring instruction
in Kit.
Note: Separate grounding is
required if fed from different
transformers. Otherwise a
single ground is acceptable.

Electrical Data
www.DaikinApplied.com 51 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Figure 51: Typical Field Wiring Diagram for Partial Heat Recovery (Single-Point Connection)
4-20MA FOR
DEMAND LIMIT
(BY OTHERS)
4-20MA FOR
EVAP. - LWT RESET
(BY OTHERS)
DOUBLE SET POINT/MODE
SWITCH
(BY OTHERS)
**TIME CLOCK
OFF
MANUAL **
ON
AUTO
585
IF REMOTE STOP
CONTROL IS USED
REMOVE LEAD 585
FROM TERM
TB2-52 TO TB2-72
** TIME CLOCK
OFF
MANUAL **
ON
AUTO
71
TB2
70
TB2
69
TB2
68
TB2
TB1
22
TB1
1A
TO
COMPRESSOR(S)
AND FAN MOTORS
120
VAC
T1
FU6
CONTROL
CIRCUIT
FUSE
SEE NOTE 2
FU4
REMOTE
STOP SWITCH
(BY OTHERS)
120 VAC
TB1
TB1
TB2
TB2
TB2
TB2
54
52
34
74
72
32A
ALARM
BELL OPTION
3 PHASE
POWER
SOURCE
DISCONNECT SWITCH
OR
POWER BLOCK
CIRCUIT BREAKER
(BY OTHERS)
DISCONNECT
(BY OTHERS)
N
120 VAC
OPTIONAL
FIELD SUPPLIED
CONTROL POWER
FU
15A for 1.5 KVA
30A for 3.0KVA
(BY OTHERS)
301A
301 299
FIELD WIRING DIAGRAM
WITH MICROTECH CONTROLLER
ALARM BELL RELAY
120VAC @ 1.0AMP MAX
EARTH
GROUND
ABR
NOCOM
BELL
ALARM BELL
RELAY
UNIT ALARM
1 2
EXTERNAL
ALARM/
EVENT
ABR
24VAC @ 0.4AMP MAX.
**
**
TB2
TB2
43
83
TB2
TB2
45
67
555A
N
24 VAC
IF EXTERNAL
ALARM/EVENT
IS USED
REMOVE LEAD 555A
FROM TERM
TB2-45 TO TB2-67
FU5
Notes:
1.) ALL FIELD WIRING TO BE INSTALLED AS
NEC CLASS 1 WIRING SYSTEM WITH
CONDUCTOR RATED 600 VOLTS.
2.) IF FIELD SUPPLIED, CONTROL POWER USER
MUST REMOVE FU6, AND WIRE NUMBERS
299, 301A INSIDE CONTROL PANEL
3.) ** = USE 'DRY CONTACTS' ONLY. DO NOT
SUPPLY FIELD POWER TO THIS CIRCUIT
4.) DO NOT SUPPLY FIELD POWER TO
24VAC OR 120VAC CONTROL CIRCUITS.
CHWR2
PUMP NO.2 RELAY
(BY OTHERS)
120VAC @ 1.0AMP MAX
N
N
120 VAC
120 VAC
TB1
TB1
TB1
TB1
P2+
CHWR1
PUMP NO.1 RELAY
(BY OTHERS)
120VAC @ 1.0AMP MAX
35
31
33
TO/FROM BAS
(CUSTOMER
CONNECTION)
(+)
(-)
REF
CONNECT TO GROUND
AT ONE END ONLY.
BACNET-MSTP
GND
120V
N
TB7
TB7
TB7
TB2
100B
TB7
TB7
TB7
TB7
M
M
M
3
5
4
1
TB2
32
TB2
102
**Heat Recovery
Request Switch
HEAT RECOVERY
PUMP RELAY
120VAC @ 1.0 AMP MAX
**Flo HR
Heat Recovery
Pump Relay
Heat Recovery
Flow Switch
Heat Recovery
0-10 VDC Pump VFD
or 3-Way Valve
Heat Recovery
4-20mA Pump VFD
or 3-Way Valve
Heat Recovery
Pump
1 2
SVHR1
120VAC
120-
TBHR
120+
TBHR
FIELD POWER SUPPLY
TO HEAT RECOVERY
FREEZE PROTECTION
HEATERS (BY OTHERS)
120V
N
TB2
44
61
TB2
DI2
MFlow Switch Contacts
Use dry contacts only. DO NOT
supply Field Power to this circuit
NOTE: For Factory Supplied Thermal
Dispersion Flow Switch wiring,
see wiring instruction kit.
To UC DI2
_
+
_
+
GND
T3
T2
T1
L3
L2
L1
PANEL
HEAT RECOVERY JUNCTION BOX
+
_

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 52 www.DaikinApplied.com
Electrical Data
Figure 52: Typical Field Wiring Diagram for Partial Heat Recovery (Multi-Point Connection)
4-20MA FOR
DEMAND LIMIT
(BY OTHERS)
4-20MA FOR
EVAP. - LWT RESET
(BY OTHERS)
DOUBLE SET POINT/MODE
SWITCH
(BY OTHERS)
** TIME CLOCK
OFF
MANUAL **
ON
AUTO
585
IF REMOTE STOP
CONTROL IS USED
REMOVE LEAD 585
FROM TERM
TB2-52 TO TB2-72
** TIME CLOCK
OFF
MANUAL **
ON
AUTO
71
TB2
70
TB2
69
TB2
68
TB2
TB1
22
TB1
TO CIRCUIT 1
COMPRESSOR(S)
AND FAN MOTORS
120
VAC
FU5
T1
FU6
CONTROL CIRCUIT
FUSE
SEE NOTE 2
FU4
REMOTE
STOP SWITCH
(BY OTHERS)
TB2
TB2
TB2
TB2
54
52
74
72
3 PHASE
POWER
SOURCE
DISCONNECT SWITCH
OR
POWER BLOCK
CIRCUIT BREAKER 1
(BY OTHERS)
DISCONNECT
(BY OTHERS)
N
120 VAC
OPTIONAL
FIELD SUPPLIED
CONTROL POWER
FU
TO CIRCUIT 2
COMPRESSOR(S)
AND FAN MOTORS
3 PHASE
POWER
SOURCE
DISCONNECT SWITCH
OR
POWER BLOCK
CIRCUIT BREAKER 2
(BY OTHERS) 15A for 1.5 KVA
30A for 3.0KVA
(BY OTHERS)
1A
301A
301 299
120 VAC
TB1
TB1
34
32A
ALARM
BELL OPTION
ALARM BELL RELAY
120VAC @ 1.0AMP MAX
FIELD WIRING DIAGRAM
WITH MICROTECH CONTROLLER
EARTH
GROUND
ABR
NOCOM
BELL
ALARM BELL
RELAY
ALARM BELL
OPTION
1 2
EXTERNAL
ALARM/
EVENT
ABR
**
24VAC @ 0.4AMP MAX.
**
TB2
TB2
43
83
TB2
TB2
45
67
555A
IF EXTERNAL
ALARM/EVENT
IS USED
REMOVE LEAD 555A
FROM TERM
TB2-45 TO TB2-67
N
24 VAC
Notes:
1.) ALL FIELD WIRING TO BE INSTALLED AS
NEC CLASS 1 WIRING SYSTEM WITH
CONDUCTOR RATED 600 VOLTS.
2.) IF FIELD SUPPLIED, CONTROL POWER USER
MUST REMOVE FU6, AND WIRE NUMBERS
299, 301A INSIDE CONTROL PANEL
3.) ** = USE 'DRY CONTACTS' ONLY. DO NOT
SUPPLY FIELD POWER TO THIS CIRCUIT
4.) DO NOT SUPPLY FIELD POWER TO
24VAC OR 120VAC CONTROL CIRCUITS.
N
120 VAC
TB1
TB1
CHWR1
PUMP NO.1 RELAY
(BY OTHERS)
120VAC @ 1.0AMP MAX
35
33
CHWR2
PUMP NO.2 RELAY
(BY OTHERS)
120VAC @ 1.0AMP MAX
N
TB1
31
120 VAC P2+
TB1
61
TB2
TB2
44 M
DI2Flow Switch Contacts
Use dry contacts only. DO NOT
supply Field Power to this circuit
NOTE: For Factory Supplied Thermal
Dispersion Flow Switch wiring,
see wiring instruction kit.
**Heat Recovery
Request Switch
HEAT RECOVERY
PUMP RELAY
120VAC @ 1.0 AMP MAX
**Flo HR
Heat Recovery
Pump Relay
Heat Recovery
Flow Switch
120V
N
TB7
TB7
TB7
TB2
100B
TB7
TB7
TB7
TB7
Heat Recovery
0-10 VDC Pump VFD
or 3-Way Valve
Heat Recovery
4-20mA Pump VFD
or 3-Way Valve
M
M
M
3
5
4
1
Heat Recovery
Pump
1 2
SVHR1
120VAC
TB2
32
TB2
102
(+)
(-)
REF
TO/FROM BAS
(CUSTOMER
CONNECTION)
CONNECT TO GROUND
AT ONE END ONLY.
120-
TBHR
120+
TBHR
FIELD POWER SUPPLY
TO HEAT RECOVERY
FREEZE PROTECTION
HEATERS (BY OTHERS)
120V
N
_
+
_
+
T3
T2
T1
L3
L2
L1
T3
T2
T1
L3
L2
L1
GND
PANEL
BACNET-MSTP
GND
HEAT RECOVERY JUNCTION BOX
+
_
To UC DI2

Electrical Data
www.DaikinApplied.com 53 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Table 32: Electrical Data - Single Point (60/50Hz) Table 33: Electrical Data - Single Point (60/50Hz)
Model
Size
Voltage /
Freq.
Single Point Field Data
Ratings Lug Range
MCARFSMFS Power Block
Disconnect
Switch
030E
208V/60 149175175(1) 2-600MCM(1) 6-350MCM
230V/60 149175175(1) 2-600MCM(1) 6-350MCM
380V/60 87 100100(1) 2-600MCM (1) 12-1/0
460V/60 74 80 80 (1) 14-2/0 (1) 12-1/0
575V/60 64 70 70 (1) 14-2/0 (1) 12-1/0
400V/50 77 90 90 (1) 14-2/0 (1) 12-1/0
035E
208V/60 163175175(1) 2-600MCM(1) 6-350MCM
230V/60 163175175(1) 2-600MCM(1) 6-350MCM
380V/60 96 110110(1) 2-600MCM(1) 4-300MCM
460V/60 77 90 90 (1) 14-2/0 (1) 12-1/0
575V/60 64 70 70 (1) 14-2/0 (1) 12-1/0
400V/50 80 90 90 (1) 14-2/0 (1) 12-1/0
040E
208V/60 168200200(1) 2-600MCM(1) 6-350MCM
230V/60 168200200(1) 2-600MCM(1) 6-350MCM
380V/60 107125125(1) 2-600MCM(1) 4-300MCM
460V/60 80 90 90 (1) 14-2/0 (1) 12-1/0
575V/60 67 80 80 (1) 14-2/0 (1) 12-1/0
400V/50 83 100100 (1) 14-2/0 (1) 12-1/0
045E
208V/60 228250250(1) 2-600MCM(1) 6-350MCM
230V/60 228250250(1) 2-600MCM(1) 6-350MCM
380V/60 117125125(1) 2-600MCM(1) 4-300MCM
460V/60 90 100100(1) 2-600MCM (1) 12-1/0
575V/60 75 90 90 (1) 14-2/0 (1) 12-1/0
400V/50 94 110110(1) 2-600MCM(1) 4-300MCM
050E
208V/60 241250250(1) 2-600MCM(2) 3/0-500MCM
230V/60 241250250(1) 2-600MCM(2) 3/0-500MCM
380V/60 131150150(1) 2-600MCM(1) 4-300MCM
460V/60 109125125(1) 2-600MCM(1) 4-300MCM
575V/60 97 110110(1) 2-600MCM(1) 4-300MCM
400V/50107125125(1) 2-600MCM(1) 4-300MCM
055E
208V/60 251300300(1) 2-600MCM(2) 3/0-500MCM
230V/60 251300300(1) 2-600MCM(2) 3/0-500MCM
380V/60 147175175(1) 2-600MCM(1) 6-350MCM
460V/60 118125125(1) 2-600MCM(1) 4-300MCM
575V/60 105125125(1) 2-600MCM(1) 4-300MCM
400V/50 119125125(1) 2-600MCM(1) 4-300MCM
060E
208V/60 260300300(1) 2-600MCM(2) 3/0-500MCM
230V/60 260300300(1) 2-600MCM(2) 3/0-500MCM
380V/60 161175175(1) 2-600MCM(1) 6-350MCM
460V/60 126150150(1) 2-600MCM(1) 4-300MCM
575V/60 113125125(1) 2-600MCM(1) 4-300MCM
400V/50129150150(1) 2-600MCM(1) 4-300MCM
NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.
Model
Size
Voltage /
Freq.
Single Point Field Data
Ratings Lug Range
MCARFSMFS Power Block
Disconnect
Switch
065E
208V/60 268300300(1) 2-600MCM(2) 3/0-500MCM
230V/60 268300300(1) 2-600MCM(2) 3/0-500MCM
380V/60 161175175(1) 2-600MCM(1) 6-350MCM
460V/60 129150150(1) 2-600MCM(1) 4-300MCM
575V/60 113125125(1) 2-600MCM(1) 4-300MCM
400V/50129150150(1) 2-600MCM(1) 4-300MCM
070E
208V/60 306350350(1) 2-600MCM(2) 3/0-500MCM
230V/60 306350350(1) 2-600MCM(2) 3/0-500MCM
380V/60 164200200(1) 2-600MCM(1) 6-350MCM
460V/60 138150150(1) 2-600MCM(1) 4-300MCM
575V/60 117125125(1) 2-600MCM(1) 4-300MCM
400V/50138150150(1) 2-600MCM(1) 4-300MCM
075E
208V/60 338400400(1) 2-600MCM(2) 3/0-500MCM
230V/60 338400400(1) 2-600MCM(2) 3/0-500MCM
380V/60 173200200 (1) 14-2/0(1) 6-350MCM
460V/60 149175175 (1) 14-2/0(1) 6-350MCM
575V/60 125150150 (1) 14-2/0(1) 4-300MCM
400V/50149175175 (1) 14-2/0(1) 6-350MCM
080E
208V/60 355400400(1) 2-600MCM(2) 3/0-500MCM
230V/60 355400400(1) 2-600MCM(2) 3/0-500MCM
380V/60 187225225(1) 2-600MCM(1) 6-350MCM
460V/60 153175175 (1) 14-2/0(1) 6-350MCM
575V/60 126150150 (1) 14-2/0(1) 4-300MCM
400V/50153175175 (1) 14-2/0(1) 6-350MCM
090E
208V/60 384450450(1) 2-600MCM(2) 3/0-500MCM
230V/60 384450450(1) 2-600MCM(2) 3/0-500MCM
380V/60 218250250(1) 2-600MCM(1) 6-350MCM
460V/60 168200200 (1) 14-2/0(1) 6-350MCM
575V/60 147175175 (1) 14-2/0(1) 6-350MCM
400V/50168200200 (1) 14-2/0(1) 6-350MCM
100E
208V/60 442500500(2) 6-500MCM(2) 3/0-500MCM
230V/60 442500500(2) 6-500MCM(2) 3/0-500MCM
380V/60 268300300(1) 2-600MCM(2) 3/0-500MCM
460V/60 203250250(1) 2-600MCM(1) 6-350MCM
575V/60 184225225(1) 2-600MCM(1) 6-350MCM
400V/50203250250(1) 2-600MCM(1) 6-350MCM
110E
208V/60 490600600(2) 6-500MCM(2) 3/0-500MCM
230V/60 490600600(2) 6-500MCM(2) 3/0-500MCM
380V/60 294350350(1) 2-600MCM(2) 3/0-500MCM
460V/60 227250250(1) 2-600MCM(1) 6-350MCM
575V/60 204250250(1) 2-600MCM(1) 6-350MCM
400V/50227250250(1) 2-600MCM(1) 6-350MCM

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 54 www.DaikinApplied.com
Electrical Data
Table 34: Electrical Data - Single Point (60/50Hz) Table 35: Electrical Data - Single Point (60/50Hz)
Model
Size
Voltage /
Freq.
Single Point Field Data
Ratings Lug Range
MCARFSMFS Power Block
Disconnect
Switch
120E
208V/60 534600600(2) 6-500MCM(2) 3/0-500MCM
230V/60 534600600(2) 6-500MCM(2) 3/0-500MCM
380V/60 330400400(1) 2-600MCM(2) 3/0-500MCM
460V/60 261300300(1) 2-600MCM(2) 3/0-500MCM
575V/60 234250250(1) 2-600MCM(2) 3/0-500MCM
400V/50261300300(1) 2-600MCM(2) 3/0-500MCM
130E
208V/60 569700700(2) 6-500MCM(3) 2/0-400MCM
230V/60 569700700(2) 6-500MCM(3) 2/0-400MCM
380V/60 358400450(1) 2-600MCM(2) 3/0-500MCM
460V/60 284350350(1) 2-600MCM(2) 3/0-500MCM
575V/60 239250250(1) 2-600MCM(2) 3/0-500MCM
400V/50284350350(1) 2-600MCM(2) 3/0-500MCM
140E
208V/60 612700700(2) 6-500MCM(3) 2/0-400MCM
230V/60 612700700(2) 6-500MCM(3) 2/0-400MCM
380V/60 388450450(1) 2-600MCM(2) 3/0-500MCM
460V/60 309350350(1) 2-600MCM(2) 3/0-500MCM
575V/60 248300300(1) 2-600MCM(2) 3/0-500MCM
400V/50309350350(1) 2-600MCM(2) 3/0-500MCM
150E
208V/60 640700700(2) 6-500MCM(3) 2/0-400MCM
230V/60 640700700(2) 6-500MCM(3) 2/0-400MCM
380V/60 410500500(1) 2-600MCM(2) 3/0-500MCM
460V/60 328400400(1) 2-600MCM(2) 3/0-500MCM
575V/60 252300300(1) 2-600MCM(2) 3/0-500MCM
400V/50328400400(1) 2-600MCM(2) 3/0-500MCM
161E
208V/60 668800800(2) 6-500MCM(3) 2/0-400MCM
230V/60 668800800(2) 6-500MCM(3) 2/0-400MCM
380V/60 432500500(1) 2-600MCM(2) 3/0-500MCM
460V/60 346400400(1) 2-600MCM(2) 3/0-500MCM
575V/60 255300300(1) 2-600MCM(2) 3/0-500MCM
400V/50346400400(1) 2-600MCM(2) 3/0-500MCM
170E
208V/60 734800800(2) 6-500MCM(4) 4/0-500MCM
230V/60 734800800(2) 6-500MCM(4) 4/0-500MCM
380V/60 442500500(2) 6-500MCM(2) 3/0-500MCM
460V/60 355400400(1) 2-600MCM(2) 3/0-500MCM
575V/60 309350350(1) 2-600MCM(2) 3/0-500MCM
400V/50355400400(1) 2-600MCM(2) 3/0-500MCM
180E
208V/60 87510001000 -- (4) 4/0-500MCM
230V/60 87510001000 -- (4) 4/0-500MCM
380V/60 479500500(2) 6-500MCM(2) 3/0-500MCM
460V/60 394450450(1) 2-600MCM(2) 3/0-500MCM
575V/60 339350350(1) 2-600MCM(2) 3/0-500MCM
400V/50394450450(1) 2-600MCM(2) 3/0-500MCM
NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.
Model
Size
Voltage /
Freq.
Single Point Field Data
Ratings Lug Range
MCARFSMFS Power Block
Disconnect
Switch
191E
208V/60 84810001000(4) 2-600MCM(4) 4/0-500MCM
230V/60 84810001000(4) 2-600MCM(4) 4/0-500MCM
380V/60 508600600(2) 6-500MCM(2) 3/0-500MCM
460V/60 424500500(2) 6-500MCM(2) 3/0-500MCM
575V/60 348400400(2) 6-500MCM(2) 3/0-500MCM
400V/50424500500(1) 2-600MCM(2) 3/0-500MCM
211E
208V/60 89010001000(4) 2-600MCM(4) 4/0-500MCM
230V/60 89010001000(4) 2-600MCM(4) 4/0-500MCM
380V/60 525600600(2) 6-500MCM(2) 3/0-500MCM
460V/60 443500500(2) 6-500MCM(2) 3/0-500MCM
575V/60 351400400(2) 6-500MCM(2) 3/0-500MCM
400V/50443500500(1) 2-600MCM(2) 3/0-500MCM
226E
208V/60 94310001000(4) 2-600MCM(4) 4/0-500MCM
230V/60 94310001000(4) 2-600MCM(4) 4/0-500MCM
380V/60 551600600(2) 6-500MCM(3) 2/0-400MCM
460V/60 469500500(2) 6-500MCM(2) 3/0-500MCM
575V/60 359400400(2) 6-500MCM(2) 3/0-500MCM
400V/50469500500(1) 2-600MCM(2) 3/0-500MCM
241E
208V/60 107112001200(4) 2-600MCM(4) 4/0-500MCM
230V/60 107112001200(4) 2-600MCM(4) 4/0-500MCM
380V/60 602700700(2) 6-500MCM(3) 2/0-400MCM
460V/60 525600600(2) 6-500MCM(2) 3/0-500MCM
575V/60 367400400(2) 6-500MCM(2) 3/0-500MCM
400V/50525600600(1) 2-600MCM(2) 3/0-500MCM

Electrical Data
www.DaikinApplied.com 55 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Table 36: Electrical Data - Multiple Point (60/50 Hz)
NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.
Model
Size
Voltage /
Frequency
Multiple Point Field Data - Circuit #1 Multiple Point Field Data - Circuit #2
Ratings Lug Range Ratings Lug Range
MCA RFS MFS Power Block
Disconnect
Switch
MCA RFS MFS Power Block
Disconnect
Switch
030E
208V/60 78 100 100 (1) 14-2/0 (1) 12-1/0 78 100 100 (1) 14-2/0 (1) 4-300MCM
230V/60 78 100 100 (1) 14-2/0 (1) 12-1/0 78 100 100 (1) 14-2/0 (1) 4-300MCM
380V/60 46 60 60 (1) 14-2/0 (1) 12-1/0 46 60 60 (1) 14-2/0 (1) 12-1/0
460V/60 39 50 50 (1) 14-2/0 (1) 12-1/0 39 50 50 (1) 14-2/0 (1) 12-1/0
575V/60 34 40 45 (1) 14-2/0 (1) 12-1/0 34 40 45 (1) 14-2/0 (1) 12-1/0
400V/50 40 50 50 (1) 14-2/0 (1) 12-1/0 40 50 50 (1) 14-2/0 (1) 12-1/0
035E
208V/60 82 100 110 (1) 14-2/0 (1) 4-300MCM 88 110 110 (1) 14-2/0 (1) 4-300MCM
230V/60 82 100 110 (1) 14-2/0 (1) 4-300MCM 88 110 110 (1) 14-2/0 (1) 4-300MCM
380V/60 44 60 60 (1) 14-2/0 (1) 12-1/0 56 70 70 (1) 14-2/0 (1) 12-1/0
460V/60 39 50 50 (1) 14-2/0 (1) 12-1/0 42 50 50 (1) 14-2/0 (1) 12-1/0
575V/60 32 40 40 (1) 14-2/0 (1) 12-1/0 35 45 45 (1) 14-2/0 (1) 12-1/0
400V/50 40 50 50 (1) 14-2/0 (1) 12-1/0 44 60 60 (1) 14-2/0 (1) 12-1/0
040E
208V/60 88 110 110 (1) 14-2/0 (1) 4-300MCM 88 110 110 (1) 14-2/0 (1) 4-300MCM
230V/60 88 110 110 (1) 14-2/0 (1) 4-300MCM 88 110 110 (1) 14-2/0 (1) 4-300MCM
380V/60 56 70 70 (1) 14-2/0 (1) 12-1/0 56 70 70 (1) 14-2/0 (1) 12-1/0
460V/60 42 50 50 (1) 14-2/0 (1) 12-1/0 42 50 50 (1) 14-2/0 (1) 12-1/0
575V/60 35 45 45 (1) 14-2/0 (1) 12-1/0 35 45 45 (1) 14-2/0 (1) 12-1/0
400V/50 44 60 60 (1) 14-2/0 (1) 12-1/0 44 60 60 (1) 14-2/0 (1) 12-1/0
045E
208V/60 120 150 150 (1) 14-2/0 (1) 4-300MCM 120 150 150 (1) 14-2/0 (1) 6-350MCM
230V/60 120 150 150 (1) 14-2/0 (1) 4-300MCM 120 150 150 (1) 14-2/0 (1) 6-350MCM
380V/60 62 80 80 (1) 14-2/0 (1) 12-1/0 62 80 80 (1) 14-2/0 (1) 12-1/0
460V/60 48 60 60 (1) 14-2/0 (1) 12-1/0 48 60 60 (1) 14-2/0 (1) 12-1/0
575V/60 39 50 50 (1) 14-2/0 (1) 12-1/0 39 50 50 (1) 14-2/0 (1) 12-1/0
400V/50 49 60 60 (1) 14-2/0 (1) 12-1/0 49 60 60 (1) 14-2/0 (1) 12-1/0
050E
208V/60 127 150 175 (1) 14-2/0 (1) 6-350MCM 127 150 175 (1) 14-2/0 (1) 6-350MCM
230V/60 127 150 175 (1) 14-2/0 (1) 6-350MCM 127 150 175 (1) 14-2/0 (1) 6-350MCM
380V/60 69 90 90 (1) 14-2/0 (1) 12-1/0 69 90 90 (1) 14-2/0 (1) 12-1/0
460V/60 58 70 80 (1) 14-2/0 (1) 12-1/0 58 70 80 (1) 14-2/0 (1) 12-1/0
575V/60 51 60 70 (1) 14-2/0 (1) 12-1/0 51 60 70 (1) 14-2/0 (1) 12-1/0
400V/50 56 70 70 (1) 14-2/0 (1) 12-1/0 56 70 70 (1) 14-2/0 (1) 12-1/0
055E
208V/60 127 150 175 (1) 14-2/0 (1) 6-350MCM 137 175 175 (1) 14-2/0 (1) 6-350MCM
230V/60 127 150 175 (1) 14-2/0 (1) 6-350MCM 137 175 175 (1) 14-2/0 (1) 6-350MCM
380V/60 69 90 90 (1) 14-2/0 (1) 12-1/0 85 110 110 (1) 14-2/0 (1) 4-300MCM
460V/60 58 70 80 (1) 14-2/0 (1) 12-1/0 66 80 90 (1) 14-2/0 (1) 12-1/0
575V/60 51 60 70 (1) 14-2/0 (1) 12-1/0 59 70 80 (1) 14-2/0 (1) 12-1/0
400V/50 56 70 70 (1) 14-2/0 (1) 12-1/0 68 80 90 (1) 14-2/0 (1) 12-1/0
060E
208V/60 137 175 175 (1) 14-2/0 (1) 6-350MCM 137 175 175 (1) 14-2/0 (1) 6-350MCM
230V/60 137 175 175 (1) 14-2/0 (1) 6-350MCM 137 175 175 (1) 14-2/0 (1) 6-350MCM
380V/60 85 110 110 (1) 14-2/0 (1) 4-300MCM 85 110 110 (1) 14-2/0 (1) 4-300MCM
460V/60 66 80 90 (1) 14-2/0 (1) 12-1/0 66 80 90 (1) 14-2/0 (1) 12-1/0
575V/60 59 70 80 (1) 14-2/0 (1) 12-1/0 59 70 80 (1) 14-2/0 (1) 12-1/0
400V/50 68 80 90 (1) 14-2/0 (1) 12-1/0 68 80 90 (1) 14-2/0 (1) 12-1/0

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 56 www.DaikinApplied.com
Electrical Data
Table 37: Electrical Data - Multiple Point (60/50 Hz)
NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.
Model
Size
Voltage /
Frequency
Multiple Point Field Data - Circuit #1 Multiple Point Field Data - Circuit #2
Ratings Lug Range Ratings Lug Range
MCA RFS MFS Power Block
Disconnect
Switch
MCA RFS MFS Power Block
Disconnect
Switch
065E
208V/60 141 175 175 (1) 14-2/0 (1) 6-350MCM 141 175 175 (1) 14-2/0 (1) 6-350MCM
230V/60 141 175 175 (1) 14-2/0 (1) 6-350MCM 141 175 175 (1) 14-2/0 (1) 6-350MCM
380V/60 85 110 110 (1) 14-2/0 (1) 4-300MCM 85 110 110 (1) 14-2/0 (1) 4-300MCM
460V/60 68 80 90 (1) 14-2/0 (1) 12-1/0 68 80 90 (1) 14-2/0 (1) 12-1/0
575V/60 59 70 80 (1) 14-2/0 (1) 12-1/0 59 70 80 (1) 14-2/0 (1) 12-1/0
400V/50 68 80 90 (1) 14-2/0 (1) 12-1/0 68 80 90 (1) 14-2/0 (1) 12-1/0
070E
208V/60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM
230V/60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM
380V/60 86 110 110 (1) 14-2/0 (1) 4-300MCM 86 110 110 (1) 14-2/0 (1) 4-300MCM
460V/60 73 90 100 (1) 14-2/0 (1) 12-1/0 73 90 100 (1) 14-2/0 (1) 4-300MCM
575V/60 62 80 80 (1) 14-2/0 (1) 12-1/0 62 80 80 (1) 14-2/0 (1) 12-1/0
400V/50 73 90 100 (1) 14-2/0 (1) 12-1/0 73 90 100 (1) 14-2/0 (1) 4-300MCM
075E
208V/60 186 225 250 (1) 2-600MCM (1) 6-350MCM 170 225 225 (1) 14-2/0 (1) 6-350MCM
230V/60 186 225 250 (1) 2-600MCM (1) 6-350MCM 170 225 225 (1) 14-2/0 (1) 6-350MCM
380V/60 92 110 125 (1) 14-2/0 (1) 4-300MCM 91 110 125 (1) 14-2/0 (1) 4-300MCM
460V/60 80 100 110 (1) 14-2/0 (1) 4-300MCM 76 100 100 (1) 14-2/0 (1) 4-300MCM
575V/60 66 80 90 (1) 14-2/0 (1) 12-1/0 65 80 90 (1) 14-2/0 (1) 12-1/0
400V/50 80 100 110 (1) 14-2/0 (1) 4-300MCM 76 100 100 (1) 14-2/0 (1) 4-300MCM
080E
208V/60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 3/0-500MCM
230V/60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 3/0-500MCM
380V/60 98 125 125 (1) 14-2/0 (1) 4-300MCM 98 125 125 (1) 14-2/0 (1) 6-350MCM
460V/60 80 100 110 (1) 14-2/0 (1) 4-300MCM 80 100 110 (1) 14-2/0 (1) 4-300MCM
575V/60 66 80 90 (1) 14-2/0 (1) 12-1/0 66 80 90 (1) 14-2/0 (1) 4-300MCM
400V/50 80 100 110 (1) 14-2/0 (1) 4-300MCM 80 100 110 (1) 14-2/0 (1) 4-300MCM
090E
208V/60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 3/0-500MCM
230V/60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 3/0-500MCM
380V/60 115 150 150 (1) 14-2/0 (1) 4-300MCM 115 150 150 (1) 14-2/0 (1) 6-350MCM
460V/60 89 110 125 (1) 14-2/0 (1) 4-300MCM 89 110 125 (1) 14-2/0 (1) 4-300MCM
575V/60 78 100 110 (1) 14-2/0 (1) 4-300MCM 78 100 110 (1) 14-2/0 (1) 4-300MCM
400V/50 89 110 125 (1) 14-2/0 (1) 4-300MCM 89 110 125 (1) 14-2/0 (1) 4-300MCM
100E
208V/60 215 300 300 (1) 2-600MCM (2) 3/0-500MCM 248 300 350 (1) 2-600MCM (2) 3/0-500MCM
230V/60 215 300 300 (1) 2-600MCM (2) 3/0-500MCM 248 300 350 (1) 2-600MCM (2) 3/0-500MCM
380V/60 129 175 175 (1) 14-2/0 (1) 6-350MCM 152 200 200 (1) 14-2/0 (2) 3/0-500MCM
460V/60 96 125 125 (1) 14-2/0 (1) 4-300MCM 117 150 150 (1) 14-2/0 (1) 6-350MCM
575V/60 87 110 110 (1) 14-2/0 (1) 4-300MCM 105 150 150 (1) 14-2/0 (1) 6-350MCM
400V/50 96 125 125 (1) 14-2/0 (1) 4-300MCM 117 150 150 (1) 14-2/0 (1) 6-350MCM
110E
208V/60 259 350 350 (1) 2-600MCM (2) 3/0-500MCM 259 350 350 (1) 2-600MCM (2) 3/0-500MCM
230V/60 259 350 350 (1) 2-600MCM (2) 3/0-500MCM 259 350 350 (1) 2-600MCM (2) 3/0-500MCM
380V/60 156 200 225 (1) 14-2/0 (1) 6-350MCM 156 200 225 (1) 14-2/0 (2) 3/0-500MCM
460V/60 120 150 175 (1) 14-2/0 (1) 6-350MCM 120 150 175 (1) 14-2/0 (1) 6-350MCM
575V/60 108 150 150 (1) 14-2/0 (1) 4-300MCM 108 150 150 (1) 14-2/0 (1) 6-350MCM
400V/50 120 150 175 (1) 14-2/0 (1) 6-350MCM 120 150 175 (1) 14-2/0 (1) 6-350MCM

Electrical Data
www.DaikinApplied.com 57 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Table 38: Electrical Data - Multiple Point (60/50Hz)
NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.
Model
Size
Voltage /
Frequency
Multiple Point Field Data - Circuit #1 Multiple Point Field Data - Circuit #2
Ratings Lug Range Ratings Lug Range
MCA RFS MFS Power Block
Disconnect
Switch
MCA RFS MFS Power Block
Disconnect
Switch
120E
208V/60 281 350 350 (1) 2-600MCM (2) 3/0-500MCM 281 350 350 (1) 2-600MCM (2) 3/0-500MCM
230V/60 281 350 350 (1) 2-600MCM (2) 3/0-500MCM 281 350 350 (1) 2-600MCM (2) 3/0-500MCM
380V/60 174 225 225 (1) 14-2/0 (1) 6-350MCM 174 225 225 (1) 14-2/0 (2) 3/0-500MCM
460V/60 137 175 175 (1) 14-2/0 (1) 6-350MCM 137 175 175 (1) 14-2/0 (1) 6-350MCM
575V/60 123 150 150 (1) 14-2/0 (1) 4-300MCM 123 150 150 (1) 14-2/0 (1) 6-350MCM
400V/50 137 175 175 (1) 14-2/0 (1) 6-350MCM 137 175 175 (1) 14-2/0 (1) 6-350MCM
130E
208V/60 281 350 350 (1) 2-600MCM (2) 3/0-500MCM 316 400 450 (1) 2-600MCM (2) 3/0-500MCM
230V/60 281 350 350 (1) 2-600MCM (2) 3/0-500MCM 316 400 450 (1) 2-600MCM (2) 3/0-500MCM
380V/60 174 225 225 (1) 14-2/0 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 3/0-500MCM
460V/60 137 175 175 (1) 14-2/0 (1) 6-350MCM 160 200 225 (1) 14-2/0 (2) 3/0-500MCM
575V/60 123 150 150 (1) 14-2/0 (1) 4-300MCM 128 175 175 (1) 14-2/0 (1) 6-350MCM
400V/50 137 175 175 (1) 14-2/0 (1) 6-350MCM 160 200 225 (1) 14-2/0 (2) 3/0-500MCM
140E
208V/60 324 400 450 (1) 2-600MCM (2) 3/0-500MCM 324 400 450 (1) 2-600MCM (2) 3/0-500MCM
230V/60 324 400 450 (1) 2-600MCM (2) 3/0-500MCM 324 400 450 (1) 2-600MCM (2) 3/0-500MCM
380V/60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 3/0-500MCM
460V/60 164 200 225 (1) 14-2/0 (1) 6-350MCM 164 200 225 (1) 14-2/0 (2) 3/0-500MCM
575V/60 131 175 175 (1) 14-2/0 (1) 6-350MCM 131 175 175 (1) 14-2/0 (1) 6-350MCM
400V/50 164 200 225 (1) 14-2/0 (1) 6-350MCM 164 200 225 (1) 14-2/0 (2) 3/0-500MCM
150E
208V/60 324 400 450 (1) 2-600MCM (2) 3/0-500MCM 351 450 450 (1) 2-600MCM (2) 3/0-500MCM
230V/60 324 400 450 (1) 2-600MCM (2) 3/0-500MCM 351 450 450 (1) 2-600MCM (2) 3/0-500MCM
380V/60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 3/0-500MCM
460V/60 164 200 225 (1) 14-2/0 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 3/0-500MCM
575V/60 131 175 175 (1) 14-2/0 (1) 6-350MCM 134 175 175 (1) 14-2/0 (1) 6-350MCM
400V/50 164 200 225 (1) 14-2/0 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 3/0-500MCM
161E
208V/60 358 450 450 (1) 2-600MCM (2) 3/0-500MCM 358 450 450 (1) 2-600MCM (2) 3/0-500MCM
230V/60 358 450 450 (1) 2-600MCM (2) 3/0-500MCM 358 450 450 (1) 2-600MCM (2) 3/0-500MCM
380V/60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 3/0-500MCM
460V/60 165 200 200 (1) 14-2/0 (1) 6-350MCM 165 200 200 (1) 14-2/0 (2) 3/0-500MCM
575V/60 146 175 175 (1) 14-2/0 (1) 6-350MCM 146 175 175 (1) 14-2/0 (1) 6-350MCM
400V/50 165 200 200 (1) 14-2/0 (1) 6-350MCM 165 200 200 (1) 14-2/0 (2) 3/0-500MCM
170E
208V/60 358 450 450 (1) 2-600MCM (2) 3/0-500MCM 405 500 500 (1) 2-600MCM (2) 3/0-500MCM
230V/60 358 450 450 (1) 2-600MCM (2) 3/0-500MCM 405 500 500 (1) 2-600MCM (2) 3/0-500MCM
380V/60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 3/0-500MCM
460V/60 165 200 200 (1) 14-2/0 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 3/0-500MCM
575V/60 146 175 175 (1) 14-2/0 (1) 6-350MCM 176 200 225 (1) 2-600MCM (1) 6-350MCM
400V/50 165 200 200 (1) 14-2/0 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 3/0-500MCM
180E
208V/60 453 500 500 (2) 6-500MCM (2) 3/0-500MCM 453 500 500 (2) 6-500MCM (2) 3/0-500MCM
230V/60 453 500 500 (2) 6-500MCM (2) 3/0-500MCM 453 500 500 (2) 6-500MCM (2) 3/0-500MCM
380V/60 248 300 300 (1) 2-600MCM (2) 3/0-500MCM 248 300 300 (1) 2-600MCM (2) 3/0-500MCM
460V/60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 3/0-500MCM
575V/60 176 200 225 (1) 2-600MCM (1) 6-350MCM 176 200 225 (1) 2-600MCM (2) 3/0-500MCM
400V/50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 3/0-500MCM

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 58 www.DaikinApplied.com
Electrical Data
Table 39: Electrical Data - Multiple Point (60/50Hz)
Model
Size
Voltage /
Frequency
Multiple Point Field Data - Circuit #1 Multiple Point Field Data - Circuit #2
Ratings Lug Range Ratings Lug Range
MCA RFS MFS Power Block
Disconnect
Switch
MCA RFS MFS Power Block
Disconnect
Switch
191E
208V/60 413 500 500 (1) 2-600MCM (2) 3/0-500MCM 464 600 600 (2) 6-500MCM (3) 2/0-400MCM
230V/60 413 500 500 (1) 2-600MCM (2) 3/0-500MCM 464 600 600 (2) 6-500MCM (3) 2/0-400MCM
380V/60 252 300 300 (1) 2-600MCM (2) 3/0-500MCM 274 350 350 (1) 2-600MCM (2) 3/0-500MCM
460V/60 208 250 250 (1) 2-600MCM (1) 6-350MCM 231 300 300 (1) 2-600MCM (2) 3/0-500MCM
575V/60 179 225 225 (1) 2-600MCM (1) 6-350MCM 182 225 225 (1) 2-600MCM (2) 3/0-500MCM
400V/50 208 250 250 (1) 2-600MCM (1) 6-350MCM 231 300 300 (1) 2-600MCM (2) 3/0-500MCM
211E
208V/60 464 600 600 (2) 6-500MCM (2) 3/0-500MCM 464 600 600 (2) 6-500MCM (3) 2/0-400MCM
230V/60 464 600 600 (2) 6-500MCM (2) 3/0-500MCM 464 600 600 (2) 6-500MCM (3) 2/0-400MCM
380V/60 274 350 350 (1) 2-600MCM (2) 3/0-500MCM 274 350 350 (1) 2-600MCM (2) 3/0-500MCM
460V/60 231 300 300 (1) 2-600MCM (2) 3/0-500MCM 231 300 300 (1) 2-600MCM (2) 3/0-500MCM
575V/60 182 225 225 (1) 2-600MCM (2) 3/0-500MCM 182 225 225 (1) 2-600MCM (2) 3/0-500MCM
400V/50 231 300 300 (1) 2-600MCM (1) 6-350MCM 231 300 300 (1) 2-600MCM (2) 3/0-500MCM
226E
208V/60 483 600 600 (2) 6-500MCM (2) 3/0-500MCM 494 600 600 (2) 6-500MCM (3) 2/0-400MCM
230V/60 483 600 600 (2) 6-500MCM (2) 3/0-500MCM 494 600 600 (2) 6-500MCM (3) 2/0-400MCM
380V/60 278 350 350 (1) 2-600MCM (2) 3/0-500MCM 295 350 350 (1) 2-600MCM (2) 3/0-500MCM
460V/60 235 300 300 (1) 2-600MCM (2) 3/0-500MCM 253 300 300 (1) 2-600MCM (2) 3/0-500MCM
575V/60 185 225 225 (1) 2-600MCM (2) 3/0-500MCM 187 225 225 (1) 2-600MCM (2) 3/0-500MCM
400V/50 235 300 300 (1) 2-600MCM (1) 6-350MCM 253 300 300 (1) 2-600MCM (2) 3/0-500MCM
241E
208V/60 555 700 700 (2) 6-500MCM (3) 2/0-400MCM 555 700 700 (2) 6-500MCM (3) 2/0-400MCM
230V/60 555 700 700 (2) 6-500MCM (3) 2/0-400MCM 555 700 700 (2) 6-500MCM (3) 2/0-400MCM
380V/60 312 400 400 (1) 2-600MCM (2) 3/0-500MCM 312 400 400 (1) 2-600MCM (2) 3/0-500MCM
460V/60 272 300 300 (1) 2-600MCM (2) 3/0-500MCM 272 300 300 (1) 2-600MCM (2) 3/0-500MCM
575V/60 190 225 225 (1) 2-600MCM (2) 3/0-500MCM 190 225 225 (1) 2-600MCM (2) 3/0-500MCM
400V/50 272 300 300 (1) 2-600MCM (1) 6-350MCM 272 300 300 (1) 2-600MCM (2) 3/0-500MCM
NOTE: MCA = Minimum Current Ampacity, RFS = Recommended Fuse Size, MFS = Maximum Fuse Size.
For RFS, use the given values for intended standard ambient operation. If the operating ambient is intended to be above
105°F, MFS must be used.

Options and Accessories
www.DaikinApplied.com 59 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Options and Accessories
Controls Options & Accessories
RapidRestore
®
and Fast Loading
Allows the unit to restart and to reach full load more quickly
than standard in case of a power interruption. After a power
loss duration of up to 180 seconds, once power is restored, the
time for a Trailblazer
®
chiller to restart is less than 125 seconds
with the chiller reaching full load within 220 seconds from
power restoration.
Fast Loading Stand-By Chiller
Gives the system greater response time by starting a stand-by
chiller and reaching full load capacity in 115 seconds (assumes
conditions require full load capacity).
Hot Gas Bypass (Factory Installed)
Hot gas bypass permits unit operation down to 10% of full
load capacity. This option includes a factory-mounted hot
gas bypass valve, solenoid valve, and manual shutoff valve
(models 075-241 only) for each circuit.
High Efficiency Variable Speed Condenser Fans
High efficiency adds variable speed drives to the condenser
fans on the chiller. The MicroTech® III controller adjusts the
speed of the condenser fans using the VFDs to optimize chiller
efficiency and maintain proper head pressure. This feature
improves part load efficiency substantially and offers the ability
to operate in low ambient conditions down to -10F. (Available
on 75-241 ton models)
Low Ambient Control (Factory Installed)
Optional fan VFD control allows unit operation down to -10°F
(-23°C). Not available on 380 volt (60 Hz) units.
High Ambient Control Panel
Includes an exhaust fan with rain hood, two inlet screens with
filters, necessary controls and wiring. Required for operation
from 105°F to 125°F (40°C to 52°C) ambient temperature. This
panel is included on units with Low Ambient Control, regardless
of ambient temperature, to dissipate additional VFD heat.
Power Factor Correction Capacitors
Option to add power factor correction capacitors to improve the
chiller’s power factor. Compressor power factor is corrected to
approximately 0.95 at standard conditions.
Water Flow Switch (Field Installed)
A thermal dispersion water flow switch is available for field
installation in the chilled water piping to avoid evaporator
freeze-up under low or no flow conditions. Terminals are
provided in the unit control center for field hook-up of the water
flow switch. If this option is not ordered with the unit, then a
field supplied water flow switch must be installed.
Water Flow Switch (Factory Installed)
A factory-mounted and wired thermal dispersion flow switch to
avoid evaporator freeze-up under low or no flow conditions.
Alarm Bell (Field Installed)
Field installed and wired to the control panel to provide remote
indication of unit alarm condition.
Remote Operator Interface Panel (Field
Installed)
A remote interface panel, field wired to the unit, providing
all the data viewable on the unit’s controller, including alarm
clearing and setpoint change capability. See “Optional Remote
Interface Panel” on page 5 for details.
BAS Interface - Open Choices

(Field Installed)
The preferred module is shipped loose for field installation
on the Microtech
®
III controller to provide the interface to the
following standard protocols:
• BACnet
®
/IP
• Modbus
®
• BACnet
®
Ethernet
• LonMark
®
Intelligent Equipment
®
Intelligent Equipment (IE) from Daikin Applied is a secure,
cloud-based controls solution that enables delivery equipment
and/or system information to customers via web or mobile
devices. A power measurement module and communications
gateway installed on Daikin equipment enables the unit to
be directly connected to the Internet via wireless (cellular,
Wi-Fi) or local area network (LAN), providing management,
monitoring control analysis and decision-making functionality
for Daikin chiller systems and the facility.
Electrical Options and Accessories
Single-Point Electrical Connection
Provides a single power connection to the unit power block
with compressor circuit breakers or to a disconnect switch
with compressor circuit breakers. Either option also available
without circuit breakers.
Multi-Point with Disconnect Switch
Provides a disconnect switch mounted inside the power
section of the control box with a through-the-door handle for
each circuit and no compressor circuit breakers Requires field-
installed circuit protection.
Phase Loss/Voltage Protection
Phase loss with under/over voltage protection and multiple
LED indication of fault type is available as a factory installed
option to guard against compressor motor burnout.
Convenience Outlet
10.0 amp, 115 volt Ground Fault Circuit Interruption (GFCI)
outlet in control panel for servicing unit.

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 60 www.DaikinApplied.com
Options and Accessories
Ground Fault Protection
Protects equipment from damage from line-to-ground fault
currents less than those required for conductor protection.
High Short Circuit Current Rating (HSCCR)
Provides control panel with high short circuit current rating with
a single-point disconnect breaker switch.
Table 40: Standard and HSCCR Panel Ratings
Panel Type 208V / 230V380V / 400V / 460V 575V
Standard 5kA 5kA 5kA
HSCCR 65kA 65kA 25kA
Electronic Expansion Valve
An electronic expansion valve is optional on models 030-070,
which have thermal expansion valves as standard.
Unit Options and Accessories
Remote Evaporators
Trailblazer® models have an evaporator shipped separately
for field installation and piping to the outdoor unit. Available
for models AGZ030-70E that have condensing units built with
tube and fin coils and AGZ075-241E with microchannel coils.
Information on models with remote evaporators can be found
in the current product Installation and Operation Manual,
available at www.DaikinApplied.com.
Pump Packages
The on-board, integrated chilled water pump package is
available with single or dual pump configurations. See
page 5 for general information, and refer to the current
product Installation and Operation Manual, available on www.
DaikinApplied.com, for detailed information.
Partial Heat Recovery
Partial heat recovery (available on 75-241 ton models) adds
optional factory-installed heat exchangers and control logic
to provide hot water for many uses such as dehumidification
and pre-heating water for a boiler. See page 14 for general
information, and refer to the current product Installation and
Operation Manual, available on www.DaikinApplied.com, for
detailed information.
IBC/OSHPD Seismic Certification
Daikin models AGZ030-241E have been tested and certified
by an independent agency — experts in seismic analysis and
design — to meet IBC seismic and OSHPD pre-approval.
The SDS (design spectral response acceleration at short
period) level varies by model size and other factors. The chiller
must be installed with either the seismic rated springs, or the
neoprene pads provided with the unit. Find more information
about seismic requirements and HVAC systems at www.
DaikinApplied.com. Seismic option not available with select
options. Contact your local sales representative for more
details.
Vibration Isolators (Field Installed)
Spring or neoprene-in-shear vibration isolators are available for
field installation to reduce vibration transmission through the
unit base. Seismic rated spring isolators are available for units
requiring seimic certification.
Wind Load Rated
AGZ-E models have been tested and proven to withstand up
to 186 mph winds when ordered with this option. Contact the
local Daikin Applied sales representative with your specific
installation requirements.
Protective Base Guards
Optional factory-installed, vinyl-coated, welded-wire base
guards provide around lower section protection on ground level
installations.
Figure 53: Unit with Base Guards
Louvers (Base and/or Coil)
Available for the upper portion or both the upper and lower
portions of unit (upper not required on Models 030 and 035).
Selecting both will completely enclose the unit with louvers.
The louvers protect the coils from hail damage.
Figure 54: Unit with Louvered Panels

Options and Accessories
www.DaikinApplied.com 61 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
Copper Tube/Aluminum Fin Condenser Coils
Aluminum fin condenser coils are an option on 30-70 models.
Copper Tube/Copper Fin Condenser Coils
Copper fin condenser coils are an option on 30-70 models only.
Copper Tube/BlackFin

Coils
Aluminum fin stock pre-coated with a phenolic coating with
1000-hour salt spray resistance (ASTM B117-90) available on
30-70 models only.
Epoxy Coated Fins
Copper or aluminum fins coated with baked epoxy protective
coating with 6000-hour salt spray resistance (ASTM B117-90).
Evaporator Insulation
Double insulation thickness (total of 1½ inch) for high humidity
areas or low fluid temperatures.
Sound Reduction
Acoustical blankets are factory-installed on each compressor.
They are also available for retrofit field installation.
Shut-off Valves
Suction valves (one per circuit), liquid line shutoff valves, and
discharge shutoff valves can be factory mounted.
Chicago Code Relief Valves
Unit will be provided with factory-mounted relief valves to meet
Chicago code requirements.
Evaporator Inlet Strainer
Evaporator water strainer kit consisting of Y-type strainer,
blowdown valve, pipe extension with two Schrader fittings and
two grooved couplings; field installed. Details on page 12.
Replaceable Core Filter-Drier
Factory installed filter drier with a replaceable core allows for
fast replacement of filter element and easier serviceability.

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 62 www.DaikinApplied.com

TRAILBLAZER

AIR-COOLED SCROLL COMPRESSOR CHILLERS
PART 1 - GENERAL
1.01 SUMMARY
A. Section includes design, performance criteria,
refrigerants, controls, and installation requirements for
air-cooled scroll compressor chillers.
1.02 REFERENCES
A. Comply with applicable Standards/Codes of AHRI
550/590, ANSI/ASHRAE 15, ETL, cETL, NEC, and
OSHA as adopted by the State.
B. Units shall meet the efficiency standards of the current
version of ASHRAE Standard 90.1, and FEMP standard
2012.
1.03 SUBMITTALS
A. Submit shop drawings and product data in accordance
with the specifications.
B. Submittals shall include the following:
1. Dimensioned plan and elevation view drawings,
required clearances, and location of all field
connections.
2. Single-line schematic drawing of the power field
hookup requirements, indicating all items that are
furnished.
3. Schematic diagram of control system indicating points
for field interface/connection.
4. Diagram shall fully delineate field and factory wiring.
5. Installation manuals.
1.04 QUALITY ASSURANCE
A. Qualifications: Equipment manufacturer must specialize
in the manufacture of the products specified and have
five years experience with the type of equipment and
refrigerant offered.
B. Regulatory Requirements: Comply with the codes and
standards specified.
C. Chiller manufacturer’s plant must be ISO registered.
1.05 DELIVERY AND HANDLING
A. [Packaged Chillers Only: Chiller shall be delivered to
the job site completely assembled and charged with
refrigerant and oil by the manufacturer.] [030-070 models
only: The outdoor unit shall be delivered to the job site
with condensing section completely assembled and a
holding charge of inert gas.
B. Comply with the manufacturer’s instructions for rigging
and handling equipment.
1.06 WARRANTY
A. The refrigeration equipment manufacturer’s guarantee
shall be for a period of one year from date of equipment
start-up but not more than 18 months from shipment. The
guarantee shall provide for repair or replacement due to
failure by material and workmanship that prove defective
within the above period, excluding refrigerant.
1.07 MAINTENANCE
A. Maintenance of the chillers shall be the responsibility
of the owner and performed in accordance with the
manufacturer’s instructions.
PART 2--PRODUCTS
2.01 ACCEPTABLE MANUFACTURERS
A. Daikin Applied
B. (Approved Equal)
2.02 UNIT DESCRIPTION
A. Provide and install as shown on the plans factory
assembled, factory-charged air-cooled packaged chillers
in the quantity specified. Each chiller shall consist of
hermetic dual or triple scroll compressor sets (total four
or six compressors), brazed plate evaporator, air-cooled
condenser section, microprocessor-based control
system and all components necessary for controlled unit
operation.
B. Chiller shall be functionally tested at the factory to ensure
trouble free field operation.
2.03 DESIGN REQUIREMENTS
A. General:[Packaged Chillers: Provide a complete scroll
compressor packaged chiller as specified herein and as
shown on the drawings. The unit shall be in accordance
with the standards referenced in section 1.02 and any
local codes in effect.] [030-241 remote models: Provide
a complete scroll compressor chiller system consisting of
an outdoor compressor-condenser section and a remote
indoor evaporator as specified herein and as shown on
the drawings. The unit shall be in accordance with the
standards referenced in section 1.02 and any local codes
in effect.]
B. Performance: Refer to the schedule of performance
on the drawings. The chiller shall be capable of stable
operation to a minimum percentage of full load (without
hot gas bypass) of 25%. [17% for 6 compressor units].
Performance shall be in accordance with AHRI Standard
550/590.
C. Flow Range: The chiller shall have the ability to support
variable flow range down to 40% of nominal design
(based on AHRI conditions).
D. Operating Range: The chiller shall have the ability to
control leaving chilled fluid tem
perature from 15°F to 65°F.


www.DaikinApplied.com 63 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
E. Acoustics: Sound pressure levels for the unit shall not
exceed the following specified levels. The manufacturer
shall provide the necessary sound treatment to meet
these levels if required. Sound data shall be provided
with the quotation. Test shall be in accordance with AHRI
Standard 370.
2.04 CHILLER COMPONENTS
A. Compressors
1. The compressors shall be sealed hermetic, scroll
type with crankcase oil heater and suction strainer.
The compressor motor shall be refrigerant gas
cooled, high torque, hermetic induction type, two-
pole, with inherent thermal protection on all three
phases and shall be mounted on RIS vibration isolator
pads. The compressors shall be equipped with an
internal module providing compressor protection and
communication capability.
[Optional] Provide power factor correction capacitors
for each compressor in order to raise compressor
power factor to 0.95 at standard rating conditions.
Capacitors shall be housed in a separate NEMA 3R
rated enclosure and shall having fusing to protect the
capacitors from over current. Fuse indicator lights
shall be provided to provide visual indication that a
fuse has blown.
B. Evaporators
1. The evaporator shall be a compact, high efficiency,
dual circuit, brazed plate-to-plate type heat exchanger
consisting of parallel stainless steel plates.
2. The evaporator shall be protected with an external,
electric resistance heater plate and insulated with 3/4”
(19 mm) thick closed-cell polyurethane insulation. This
combination shall provide freeze protection down to
-20°F (-29°C) ambient air temperature.
3. The water-side working pressure shall be a minimum
of 653 psig (4502 kPa). Vent and drain connections
shall be provided in the inlet and outlet chilled water
piping by the installing contractor. Evaporators shall
be designed and constructed according to, and listed
by, Underwriters Laboratories (UL).
[OPTIONAL] The evaporator shall have 1.5-inch
(19 mm) closed cell polyurethane insulation.
C. Condenser
1. Condenser fans shall be propeller type arranged for
vertical air discharge and individually driven by direct-
drive fan motors. The fans shall be equipped with
a heavy-gauge vinyl-coated fan guard. Fan motors
shall be TEAO type with permanently lubricated ball
bearings, inherent overload protection, three-phase,
direct-drive, 1140 rpm. Each fan section shall be
partitioned to avoid cross circulation.
2. Coil Options
a. [Standard Microchannel] Coil shall be
microchannel design and shall have a series
of flat tubes containing multiple, parallel flow
microchannels layered between the refrigerant
manifolds. Tubes shall be 9153 aluminum alloy.
Tubes made of 3102 alloy or other alloys of lower
corrosion resistance shall not be accepted. Coils
shall consist of a two-pass arrangement. Each
condenser coil shall be factory leak tested with
high-pressure air under water.
• [Standard Micro-Channel Coil] Coils shall
withstand 1000+ hour acidified synthetic sea
water fog (SWAAT) test (ASTM G85-02) at
120°F (49°C) with 0% fin loss and develop no
leaks.
• [Epoxy-coated Micro-Channel Option]
Condenser coils shall include baked epoxy
coating providing 6000+ hour salt spray
resistance (ASTM B117-90) applied to both the
coil and the coil frames.
b. [030-070 models only] The condenser coils shall
consist of 3/8 inch (10 mm) seamless copper tubes
mechanically bonded into plate-type fins. The fins
shall have full drawn collars to completely cover
the tubes. A subcooling coil shall be an integral
part of the main condenser coil.
• [Black-Fin Cu/Al Option] Condenser coils
shall include aluminum fins pre-coated with
a phenolic epoxy coating with 1000 hour salt
spray rating (ASTM B117-90)
• [Epoxy-coated Cu/Al Option] Condenser coils
shall include baked epoxy coating providing
6000+ hour salt spray resistance (ASTM B117-
90) applied to both the coil and the coil frames
c. [030-070 models only] - The condenser coils shall
consist of 3/8 inch (10 mm) seamless copper tubes
mechanically bonded into plate-type fins. The fins
shall have full drawn collars to completely cover
Sound Pressure (at 30 feet)
63
Hz
125
Hz
250
Hz
500
Hz
1000
Hz
2000
Hz
4000
Hz
8000
Hz
Overall
dBA
75% Load
dBA
50% Load
dBA
25% Load
dBA
Sound Power
63
Hz
125
Hz
250
Hz
500
Hz
1000
Hz
2000
Hz
4000
Hz
8000
Hz
Overall
dBA
75% Load
dBA
50% Load
dBA
25% Load
dBA

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 64 www.DaikinApplied.com
Engineering Guide Specifications
the tubes. A subcooling coil shall be an integral
part of the main condenser coil. Condenser coils
shall include copper fins.
• [Epoxy-coated Cu/Cu Option] Condenser coils
shall include baked epoxy coating providing
6000+ hour salt spray resistance (ASTM B117-
90) applied to both the coil and the coil frames.
D. Refrigerant Circuit
1. Each of the two refrigerant circuits shall include
a refrigerant filter-drier, sight glass with moisture
indicator, liquid line solenoid valve (no exceptions),
expansion valve, and insulated suction line.
2. [Optional] Each of the two refrigerant circuits shall
include a replaceable-core refrigerant filter-drier,
sight glass with moisture indicator, liquid line solenoid
valve (no exceptions), expansion valve, and insulated
suction line.
E. Construction
1. Unit casing and all structural members and rails shall
be fabricated of pre-painted or galvanized steel.
Painted parts shall be able to meet ASTM B117, 1000-
hour salt spray test.
2. Options
a. Painted steel wraps enclosing the coil end sections
and piping
b. Protective, 12 GA, PVC-coated, wire coil guards
for the vertical upper coil section of the unit
c. Protective, 12 GA, PVC-coated, wire base guards
for the lower section of the unit
d. Protective and decorative louvers for upper section
of the unit, covering the coils and unit end
e. Protective and decorative louvers for lower section
of the unit
F. Control System
1. A centrally located weatherproof control panel shall
contain the field power connection points, control
interlock terminals, and control system. Box shall be
designed in accordance with NEMA 3R rating. Power
and starting components shall include factory circuit
breaker for fan motors and control circuit, individual
contactors for each fan motor, solid-state compressor
three-phase motor overload protection, inherent fan
motor overload protection and two power blocks
(one per circuit) for connection to remote, contractor
supplied disconnect switches. Hinged access
doors shall be lockable. Barrier panels or separate
enclosures are required to protect against accidental
contact with line voltage when accessing the control
system.
2. Options
a. [Shall include standard multi-point power blocks. ]
b. [Shall include single-point power connection to
power block with compressor circuit breakers
(Customer-supplied disconnect required).]
c. [Shall include single-point connection to a non-
fused disconnect switch with through-the-door
handle and compressor circuit breakers. ]
d. [Shall include multi-point disconnect switches (one
per circuit).]
e. [Shall include high short circuit current rating
of 65,000 amps (25,000 amps at 575 Volt) with
single-point disconnect switch.][Shall include multi-
point disconnect switches (one per circuit).]
G. An advanced DDC microprocessor unit controller with a
5-line by 22-character liquid crystal display provides the
operating and protection functions. The controller shall
take preemptive limiting action in case of high discharge
pressure or low evaporator pressure. The controller shall
contain the following features as a minimum:
1. Equipment Protection
a. The unit shall be protected in two ways: (1) by
alarms that shut the unit down and require manual
reset to restore unit operation and (2) by limit
alarms that reduce unit operation in response to
some out-of-limit condition. Shut down alarms shall
activate an alarm signal.
b. Shutdown Alarms
• No evaporator water flow
• Sensor failures
• Low evaporator pressure
• Evaporator freeze protection
• High condenser pressure
• Outside ambient temperature (auto-restart)
• Motor protection system
• Phase voltage protection (Optional)
c. Limit Alarms
• Condenser pressure stage down, unloads unit
at high discharge pressures
• Low ambient lockout, shuts off unit at low
ambient temperatures
• Low evaporator pressure hold, holds stage #1
until pressure rises
• Low evaporator pressure unload, shuts off one
compressor
d. Unit Enable Selection
• Enables unit operation from either local
keypad, digital input, or BAS
e. Unit Mode Selection
• Selects standard cooling, ice, glycol, or test
operation mode
f. Analog Inputs
• Reset of leaving water temperature, 4-20 mA
• Current Limit
g. Digital Inputs
Engineering Guide Specifications

Engineering Guide Specifications
www.DaikinApplied.com 65 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS
• Unit off switch
• Remote start/stop
• Flow switch
• Ice mode switch, converts operation and
setpoints for ice production
• Motor protection
h. Digital Outputs
• Shutdown alarm; field wired, activates on an
alarm condition, off when alarm is cleared
• Evaporator pump; field wired, starts pump
when unit is set to start
i. Condenser Fan Control
• The unit controller shall provide control
of condenser fans based on compressor
discharge pressure.
j. Building Automation System (BAS) Interface
• Factory mounted DDC controller(s) shall
support operation on a BACnet
®
, Modbus
®
or
LonMark
®
network via one of the data link /
physical layers listed below as specified by the
successful Building Automation System (BAS)
supplier.
––BACnet
®
MS/TP master (Clause 9)
––BACnet
®
IP, (Annex J)
––BACnet
®
ISO 8802-3, (Ethernet)
––LonMark
®
FTT-10A. The unit controller
shall be LonMark
®
certified.
• The information communicated between the
BAS and the factory mounted unit controllers
shall include the reading and writing of data
to allow unit monitoring, control and alarm
notification as specified in the unit sequence of
operation and the unit points list.
• For chillers communicating over a LonMark
®

network, the corresponding LonMark
®

External Interface File (XIF) shall be provided
with the chiller submittal data.
• All communication from the chiller unit
controller as specified in the points list shall
be via standard BACnet
®
objects. Proprietary
BACnet
®
objects shall not be allowed.
BACnet
®
communications shall conform to the
BACnet
®
protocol (ANSI/ASHRAE135-2001).
A BACnet
®
Protocol Implementation
Conformance Statement (PICS) shall be
provided along with the unit submittal.
2.05 OPTIONS AND ACCESSORIES
A. The following optional items shall be furnished:
1. RapidRestore
®
and Fast Loading: The chiller shall
be equipped with the capability to restart and to
reach full load more quickly than standard in case of
a power interruption. The chiller shall be capable of
rapidly restarting after power loss duration of up to
180 seconds. The time to restart the chiller shall be
a maximum of 125 seconds, and full load shall be
achieved in 220 seconds from power restoration.
2. Fast Loading Stand-By Chiller: The chiller shall be
equipped with the capability to start and to reach full
load more quickly than standard in the event that the
primary chiller system is disabled. The chiller shall be
capable of rapidly achieving full capacity. The time to
full load shall be achieved in 115 seconds.
3. [075-241 models only] Partial Heat Recovery: An
auxilliary braze-plate heat exchanger shall be added in
each unit refrigerant circuit between the compressors
and the condenser coils. The heat exchangers shall
transfer the compressor discharge gas heat to a
separate water loop to be used for various heating
applications. Water temperature sensors and piping
connections shall be factory installed. The amount of
heat produced is dependent on the requested cooling
load, the operating temperatures, and the water flow
rate through the auxilliary heat exchangers. Chiller
controller shall supply 0-10V DC or 4-20ma signal for
control of a field provided 3-way valve or pump VFD.
4. Optional Seismic Certification: Provide chiller with
seismic rating based on site SDS and importance
factor levels. Seismic rating shall consist of OSHPD
pre-approval for the model and configuration provided.
Ensure rated SDS level is adequate for the installed
location. Provide [seismic rated spring isolators]
[neoprene pads] for secure mounting of the chiller to
the base. Chiller shall be marked with a label showing
the applicable OSHPD pre-approval number.
5. Wind Load Rated: Tested and rated to withstand wind
speeds up to 186 mph. Provide engineer-stamped
certificate that equipment has been evaluated and
built to meet the required wind velocity.
6. Hot Gas Bypass: allows unit operation to 10 percent
of full load. Includes factory-mounted hot gas bypass
valve, solenoid valve, and manual shutoff valve for
each circuit. Shall be ready for field piping according
to manufacturer instructions.
7. Low Ambient Control: Fan VFD allows unit operation
down to -10°F (-23°C).
8. High ambient control box for operation in ambient
temperatures from 105°F (40°C) to 125°F (52°C).
9. Ground Fault Protection: Factory installed circuit
breaker to protect equipment from damage from line-
to-ground fault currents less than those required for
conductor protection.
10. Phase loss with under/over voltage protection and
with LED indication of the fault type to guard against
compressor motor burnout.
11. Factory-mounted thermal dispersion flow switch
12. Field-mounted, paddle type, chilled water flow switch
field wired to the control panel
13. Evaporator inlet strainer, minimum of 0.063”

CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS 66 www.DaikinApplied.com
Engineering Guide Specifications
perforations for brazed plate evaporators with
extension pipe and grooved couplings (factory
mounted or field installed).
14. Spring vibration isolators (field installed)
15. Rubber-in-shear vibration isolators (field installed)
16. Seismic rated spring isolators (field installed)
17. Compressor sound reduction package
18. Remote operator interface panel (field-wired)
19. 115V GFI convenience outlet
20. BAS interface module, factory mounted
2.06 OPTIONAL FACTORY-INSTALLED
PUMP PACKAGE
A. The pump package shall be factory mounted and wired
on the chiller. The chiller controller shall provide a pump
start/stop signal when operation is required. On dual
pump systems, the chiller shall also provide automatic
alternating of pump starts and duty/standby functionality.
The package shall be equipped with:
1. Single Pump Model 4380: single spring inside-seal,
vertical, in-line, radially split-case pump, serviceable
without breaking pipe connections. The motor and
pump rotating assembly shall be serviceable without
removing the pump casing from the line - OR -
2. Dual Pumps in a Single Casting Model 4392: single-
spring inside-seal vertical, in-line, radially split-case
pumps, mounted in a common casing with a common
inlet connection and outlet connection and including
a flapper valve to prevent recirculation when only
one pump is operating. An isolation valve shall be
included to allow one pump to operate when the other
is removed. The pumps shall be designed for duty/
standby, not parallel operation.
B. Pump package shall also be equipped with:
1. “Y” type inlet strainer
2. Combination triple-duty outlet valve having a drip-tight
discharge shutoff valve, non-slam check valve, and
flow throttling valve
3. Combination suction guide with flow stabilizing outlet
vanes and stainless steel strainer with a disposable
fine-mesh strainer for start-up
4. Factory power and control wiring from the AGZ chiller
to the pump package control panel
5. Flow switch mounted and wired
6. Interconnecting schedule 40 piping with grooved
couplings
7. Insulation of all cold surfaces
C. Pump Package Options
1. Water pressure gauges on the pump suction and
discharge
2. Expansion tank with size increments from 4.4 to 90
gallons, field installed (small sizes can be factory
mounted)
3. Air separator with air vent, field installed
4. Storage tanks, vertical, insulated, 150, 300, 600,
1000 gallon sizes with optional immersion heater, field
installed.
5. Pump VFD for variable chilled water flow capability.
[075-241 models only] Optional Variable Frequency
Drive: Flow control through the pump VFD without
external pressure sensors. There shall be four selectable
operating modes:
a. Sensorless Operation
b. BAS Input: The pump speed and system flow will
be controlled from a customer-supplied BAS input
signal.
c. Remote Sensor Control: The VFD is wired to
a pressure sensor mounted in the chilled water
piping system. This is the standard VFD control
when a sensorless VFD is not used.
d. Locally Selected Constant Speed Control:
Provides manual control of the pump speed,
overriding any current automatic speed control.
Control software shall provide automatic speed control
in variable volume systems without the need for pump
mounted (internal/external) or remotely mounted
differential pressure system feedback sensor. Control
mode setting and minimum / maximum head and
flow set-points shall be set at the factory and be user
adjustable via the built-in programming interface.
PART 3 - EXECUTION
3.01 INSTALLATION
A. Install in strict accordance with manufacturer’s
requirements, shop drawings, and contract documents.
B. Adjust and level chiller in alignment on supports.
C. Coordinate electrical installation with electrical contractor.
D. Coordinate controls with control contractor.
E. Install a required cleanable, field-supplied strainer in the
chilled water return line at the evaporator inlet per the
guidelines in the installation manual.
3.02 START-UP
A. Provide testing and starting of machine, and instruct the
Owner in its proper operation and maintenance.

Engineering Guide Specifications
www.DaikinApplied.com 67 CAT 624-16 • TRAILBLAZER MODEL AGZ CHILLERS

Daikin Applied Training and Development
Now that you have made an investment in modern, efficient Daikin Applied equipment, its care should
be a high priority. For training information on all Daikin Applied HVAC products, please visit us at
www.DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department.
Warranty
All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale, including
Limited Product Warranty. Consult your local Daikin Applied representative for warranty details. To find
your local Daikin Applied representative, go to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.
Products manufactured in an ISO Certified Facility.
CAT 624-16 (02/18) ©2018 Daikin Applied | (800) 432–1342 | www.DaikinApplied.com
Daikin Applied Training and Development
Now that you have made an investment in modern, efficient Daikin Applied equipment, its care should
be a high priority. For training information on all Daikin Applied HVAC products, please visit us at
www.DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department.
Warranty
All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale, including
Limited Product Warranty. Consult your local Daikin Applied representative for warranty details. To find
your local Daikin Applied representative, go to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.
Products manufactured in an ISO Certified Facility.
Tags