Closed loop control systems block diagrams

1,154 views 67 slides Mar 11, 2024
Slide 1
Slide 1 of 67
Slide 1
1
Slide 2
2
Slide 3
3
Slide 4
4
Slide 5
5
Slide 6
6
Slide 7
7
Slide 8
8
Slide 9
9
Slide 10
10
Slide 11
11
Slide 12
12
Slide 13
13
Slide 14
14
Slide 15
15
Slide 16
16
Slide 17
17
Slide 18
18
Slide 19
19
Slide 20
20
Slide 21
21
Slide 22
22
Slide 23
23
Slide 24
24
Slide 25
25
Slide 26
26
Slide 27
27
Slide 28
28
Slide 29
29
Slide 30
30
Slide 31
31
Slide 32
32
Slide 33
33
Slide 34
34
Slide 35
35
Slide 36
36
Slide 37
37
Slide 38
38
Slide 39
39
Slide 40
40
Slide 41
41
Slide 42
42
Slide 43
43
Slide 44
44
Slide 45
45
Slide 46
46
Slide 47
47
Slide 48
48
Slide 49
49
Slide 50
50
Slide 51
51
Slide 52
52
Slide 53
53
Slide 54
54
Slide 55
55
Slide 56
56
Slide 57
57
Slide 58
58
Slide 59
59
Slide 60
60
Slide 61
61
Slide 62
62
Slide 63
63
Slide 64
64
Slide 65
65
Slide 66
66
Slide 67
67

About This Presentation

Process control


Slide Content

UNIT II CLOSED LOOP CONTROL SYSTEMS Open loop system : Manual mode of Operation Closed loop system Auto mode of Operation Syllabus: Development of block diagram for feed-back control systems Servo and regulator problems in closed-loop control system Transfer function for controllers and final control element Principles of pneumatic and electronic controllers Transient response of closed-loop control systems Stability of closed-loop control system Transportation lag

Process m d y Process m d y Final Control Element Sensor/ transmitter Controller y sp y m c e Open loop system : Closed loop system : Controller Mechanism - + CONCEPT OF FEEDBACK CONTROL

Representation of a linear system System without controller(Open loop) Pictorial representation Mathematical representation N th order differential equation N first order differential equations matrix differential equation Transfer function Block diagram representation System with controller(Closed loop) Feed-back control systems Positive feed back Negative feedback

Process ( Stirred – tank heater ) Measuring element (thermometer) Controller(P,PI,PID Controllers) Final control element(Power driver/Control valve) Components of a control system Heating system with process control components:

Servo problem: No change in load [T i ] and Changes only in set point[T R ] Regulatory problem: No change in set point[T R ] and Changes only in set point load [T i ] Closed loop block diagram of a simple feed back control system: CONTinued … T R

Each block represents the functional relationship existing between the input and output of a particular component. Variables selected In block diagram representations of control systems are deviation variables The transfer function relating the input – output pair of variables are placed inside of each block Individual components blocks are combined to give the overall block diagram. Process have two input variables and one output variable. Procedure of developing transfer function for the process is similar to other components DEVELOPMENT OF BLOCK DIAGRAM

If there is a change in Q (t) only, then Ti’ (t) = 0 and the transfer function relating T’ to Q Energy balance on stirred tank heater If there is a change in Ti’ (t) only, then Q (t) = 0 and the transfer function relating T’ to Ti’

Measuring element: Block diagram of heating process: Summer: Error, ϵ = T R – T m Continued…

Controller and the final control element are combined into one block For the combined block, Input is error and output is heat Controller used in the block is proportional controller At steady state, Let ϵ’ be the deviation variable The relationship for a proportional controller Controller and Final Control Element(FCE): CONTinued …

At steady state, equation (1) becomes Taking Laplace on both sides Block diagram of Proportional controller and FCE: CONTinued …

Block diagram gives: Relationship among the process control components Feedback relationship between measured variable & desired variable Block diagram of servo and regulatory problem Summary of block diagram closed loop control system : CONTinued …

Pneumatic control valve: Control Valve (FINAL CONTROL ELEMENT) Selection of the type of valve is made based on safety considerations Example: air – to – close Control valve is used in controlling the inlet flow of cooling water to a cooling jacket on an exothermic chemical reactor Selection of the type of valve:

Electronic control valve: CONTinued … Control valve consists of an actuator and a valve. Control v alve itself is divided into the body and trim. The body consists of housing for mounting the actuator Valve Connections for attachment to a supply and delivery line.

Block diagram of transducer, Controller and Converter in Electronic control valve: CONTinued … K v --  Steady state gain (Constant of proportionality between steady state flow rate and valve top pressure) is the time constant of the valve (T ime constant of the valve is very small, then it is negligible. Ideal Transfer functions of Pneumatic Control valve:

Difference between pneumatic and electronic controllers: The choice between electronic and pneumatic control will probably be decided by the relative costs of installation and maintenance and the reliability of the instruments. Pneumatic and Electronic controllers

Controllers: Input to the controller is error signal ( ϵ) Output of the controller is pneumatic signal (P) Transducer and converter are combined with the controller for simplicity Types of Controllers: Proportional control Proportional integral control Proportional derivative control Proportional integral derivative control CONVENTIONAL CONTROLLERS

Integral control mode is introduced to eliminate the residual error It is termed as PI or proportional-integral control The integral mode ultimately drives the error to zero The values of K c and τ I are both adjustable PROPORTIONAL – INTEGRAL (PI) CONTROL

To visualize the step response , Unit step change in error (ϵ =1) is given ‘p’ changes suddenly by an amount K c and linearly with Reciprocal of is called as reset rate Step response of PI Controller: CONTinued … Transfer function for this controller:

PROPORTIONAL – DERIVATIVE (PD) CONTROL Derivative control mode is introduced to reduce the process oscillations It is termed as PD or proportional- derivative control The values of K c and τ D are both adjustable

To visualize its response , a linear change in error is given [ ] ‘p’ changes suddenly by an amount AK C τ D and linearly with AK C. Step response of PD Controller: CONTinued … Transfer function for this controller:

Transfer function for this controller: Derivative control action is based on how rapidly the error is changing Rapidly changing error signal will induce a large derivative response. Derivative control should be avoided for “Noisy” error signals. Integral control action will give error free process output PROPORTIONAL – INTEGRAL - DERIVATIVE (PID) CONTROL It is a combination of the integral and derivative control mode It is termed as PID or proportional- integral - derivative control The values of K c , τ I and τ D are adjustable

A special case of proportional control is ON/OFF control For maximum gain K c , the valve will move from one extreme position to other even for a slight deviation in set point. i.e. the valve acts as a switch. In practice, a dead band is inserted into the controller. With a dead band, the error reaches some finite positive value before the controller “turns on”. Conversely, the error must fall to some finite negative value before the controller “turns off”. Step response of ON-OFF Controller: ON/OFF CONTROL

Step response of all type of Controllers: CONTinued …

Closed loop block diagram: ϵ = Error G C = Transfer function of controller G 1 = Transfer function of FCE G 2 = Transfer function of Process H = TF of measuring element CLOSED LOOP TRANSFER FUNCTIONS B = measured Variable M = Manipulated variable U = Load variable or disturbance R = Set point or desired value C = Controlled variable

Block diagram of servo problem : Several Transfer Functions in series are simplified as product of individual TF G = G C G 1 G 2 Block diagram reduction : Continued… Solving these three equations simultaneously , C in terms of R are obtained

Continued… Overall closed loop transfer function : Overall closed loop block diagram :

Continued… Block diagram of regulatory problem : Solving these four equations simultaneously , C in terms of U are obtained

Transfer function relating any pair of variables X, Y Where, π f = Product of transfer functions in the path between the locations of the signals X and Y. π l = Product of all transfer functions in the loop.( ie . π l = G C G 1 G 2 H) Overall Transfer Function based on the block diagram reduction rule Block diagram reduction rule

TRANSIENT RESPONSE OF SIMPLE CONTROL SYSTEMS

For proportional control, Servo Response with P Controller Let,

Let, REGULATORY RESPONSE WITH P CONTROLLER In Proportional control, In regulatory problem,

Overall transfer function for load change: REGULATORY Response with PI Controller PI Controller transfer function is given as

Let, Substitute equation (3), (4) & (5) in equation (2) Continued…

For a unit step change in load{ } in equation (6) gives Eqn (7), response of the tank temperature to an impulse function of magnitude A 1 . The impulse response of this system for Continued…

One of the most important advantages of PI control is the elimination of offset. The effect of on the unit step response : Continued…

Concept of stability: If the system less (or) equal to second order, the response of system is inherently stable. If the system is higher than second order, the problem of stability in a control system is slightly more complicated. Stability criterion: A linear control system is unstable if any roots of its characteristic equation are on or to the right of the imaginary axis. Otherwise the system is stable. The characteristic equation is 1 + G = 0. Where, The characteristic equation of a control system determines its stability and is the same for set point or load changes. STABILITY OF CLOSED LOOP SYSTEM

. Continued… Closed loop block diagram and Transfer function: Location of the roots of the Characteristic equation of the system, 1 + GH = 0

Routh test is a purely algebraic method for determining how many roots of the characteristic equation have positive real parts In the characteristic equation, if there are no roots with positive real parts, the system is stable. The test is limited to systems that have polynomial characteristic equations and not suitable for the system with transportation lag. To check the roots of the given system , Write the characteristic equation in the form of , Where, a is positive. If any coefficient is negative, the system is definitely unstable and the Routh test is not needed to answer the question of stability. If all the coefficients are positive, the system may be stable (or) unstable. ROUTH TEST FOR STABILITY

Routh array table: Continued… Routh stability table:

Problems

Example: 1 Determine the transfer functions C/R, C/U 1 and B/U 2 for the system show in Fig. Also determine an expression for C in terms of R and U 1 for the situation when both set-point change and load change occur simultaneously. Using the rule given by equation (10) we obtain by inspection the results.

For separate changes in R and U 1 , we may obtain the response C from equation (12) & (13) If both R and U 1 occur simultaneously the principle of super position requires that the overall response be the sum of the individual responses Overall transfer function for Multi loop control systems: To illustrate how one obtains the overall transfer function for a multi loop system, in which the method used is to reduce the block diagram to a single –loop diagram by application of the rules summarized by positive feed back and negative feed back equation.

Step: 1 Reducing the inner loop and we may also combine G 2 & G 3 into a single block Step: 2 Single loop can be converted into single block. Example: 2 Determine the transfer functions C/R for the system show in Fig. This block diagram represents a cascade control system, which will be discussed later .

Problem: 3 A unit step change in error is introduced into a PID controller. If K C = 10, τ 1 =1 and τ D = 0.5. Plot the response of the controller P (t). Solution: WKT, the transfer function for PID controller is Given Data: K C = 10, τ 1 =1, τ D = 0.5 Substitute the above value in equation (1) Substitute the above value in equation (2) Taking inverse Laplace

Problem 1: The set point of the control system shown in Fig A is given a step change of 0.1 unit. Determine: ( i ) the maximum value of C and the time at which it occurs (ii) the offset (iii) the period of oscillation. Draw a sketch of C (t) as a function of time. ( NOVEMBER 2012 & R2007) The transfer function for the given system is

So the response equation is at under damped condition. Step change is

( i ) Maximum value of ‘C’ occurs at peak time t p : At , the maximum value of “C” can be substituted in equation (1) (iii) Period of oscillation: Period of oscillation, Graph is plotted between “t” Vs “C(t)” time units

Problem 2: The location of a load change in a control loop may affect the system response. In the block diagram shown in Fig C. a unit-step change in load enters at either location 1 or location 2. (a) What is the frequency of the transient response when the load enters at location 1 and when the load enters at location 2? (b) What is the offset when the load enters at location 1 and when it enters at location 2? (c) Sketch the transient response to a step change in U 1 and to a step change in U 2. (NOVEMBER 2013 & R2007, NOVEMBER 2012 & R2008, MAY 2012 & R 2008)

Apply step change Taking inverse Laplace

Unit step change in location 2.

Taking inverse Laplace Yes, the response equation will vary depend on the load variations in location 1 or location 2. (a) Frequency of response is same for both location, because the denominator has second order differential equation in both, So

(b) Offset: For location 1 For location 2 So offset is different for the location 1 & location 2. (c) Graph for “t” Vs “C(t)”

Problem 3: A PD controller is used in a control system having a first order process and a measurement lag as shown in Fig. (a) Find the expressions for for the closed loop response. , find K C so that for the two cases; ( i ) (ii) © Compare the offset and period realized for both cases and comment on the advantage of adding the derivative mode.

Solve the above equation algebraically, we have (a) The expressions for for the closed – loop response is

(b) Given For Solve the above equation algebraically, we have For Solve the above equation algebraically, we have (c) Offset:

Step change is applied For Thus adding the derivative mode to the proportional action, the offset is decreased.

Problem 4: For the control system in Fig. Obtain the closed loop transfer C/U. Find the value of proportional gain for which closed loop has a damping coefficient is 2.3. Find the offset for a unit step change in U if K C = 4. The transfer function for closed loop Solve the above equation algebraically, we have

( a) The transfer function for the closed loop system is (b) Find the value of K C at from equation (1) Solve the above equation we have

Problem 5: For the control system shown in Fig with R = 2/s, Determine ( i ) C (s) / R (s) (ii) C(∞) (iii) offset (iv) C(0.5) (v) Whether closed loop response is oscillatory? (MAY 2013 & R2007, NOVEMBER 2012 & R2008, NOVEMBER 2011 & R2007) ( i ) The transfer function for closed loop

Solve the above equation algebraically, we have We know R(s) = 2/s

The response equation is Therefore, The closed loop response is oscillatory behavior. Stability: A stable system will be defined as one for which the output response is bounded for all bounded inputs. A system exhibiting an unbounded response to a bounded input is unstable. This definition although somewhat loose is adequate for most of the linear systems and simple inputs. Bounded is an input that always remains between an upper and a lower limit.

Example 1: In terms of fig, a control system has the transfer functions We have suggested a physical element by the components placed in parentheses. Find the characteristic equation and its rots and determine the system is stable. Step 1: Open loop transfer function Step 2: The characteristic equation, 1 + G = 0 Solving by the quadratic formula Since the real part of S 1 & S 2 is negative (-3/2), the system is stable.

Example:1 Given the characteristic equation Determine the stability by the Routh criterion. Solution: Since all the coefficients are positive, the system may be stable. To test this, form the Routh array Row Since there is no change in sign in the first column, there are no roots having positive real parts, and the system is stable.

Example: 2 Using determine the values for K C for which the control system is stable. (b) For the value of K C for which the system is on the threshold of instability, determine the roots of the characteristic equation with the help of theorem 3. Solution: The characteristic equation, 1 + G = 0 becomes Substituting the time constants and solving algebraically , Routh array table: Row

Since the proportional sensitivity of the controller is a positive quantity, we see that the fourth entry in the first column, 6(1+ K C ) is positive. According to Theorem 1, all the elements of the first column must be positive for stability. Hence It is concluded that the system will be stable only if the system is on the verge of instability and the element in the nth row of the array is zero. According to Theorem 3, the location of the imaginary roots is obtained by solving. Where C and D are the elements in the (n-1) st row. For this problem with we obtain, Therefore, two of the roots on the imaginary axis are located at and The third root can be found by expressing eqn (2) in factored form Where s 1 , s 2 & s 3 are the roots. Introducing the two imaginary roots into eqn (3) and multiplying out the terms give

Comparing eqn (1) & (4), we see that S 3 = - 6. The roots of the characteristic equation are therefore