Connection to the MV Utility Network Big loads need big supply.
Why MV? LV works for homes, but factories need more. MV = higher voltage, lower current, smaller cables. Analogy: Supplying a city through a garden hose → LV = hose, MV = water main. Story: A shopping mall with 200 shops on LV would need tree-trunk cables → utilities insist on MV.
If Mall Takes LV Supply (400 V) 💡 Too much current = too many cables. Total load: 2 MW @ pf 0.9 → ≈ 3,200 A at 400 V. Each 400 mm² Cu cable ≈ 630 A. Needs 6 parallel cables per phase (≈ 18 + N + PE). Bulky cable bundles, high losses, expensive.
If Mall Takes MV Supply (11 kV) 💡 Smaller current, simpler supply. Same load: 2 MW @ pf 0.9 → ≈ 117 A at 11 kV. Only 1 MV feeder cable needed. On-site transformer (2.5–3.15 MVA) → LV bus. Compact, efficient, cheaper copper, easier protection.
Extra Safety Interlocks: stop human mistakes (e.g., can’t open live cubicle).
LV Metering Substation Meter is on LV side (400 V). Typical for small sites.
Functions of LV Metering Substation Step down MV → LV. Protect system. Meter consumption.
MV Metering Substation Meter is on MV side. Used for big industrial loads.
Why MV Metering? LV currents too large → impractical. MV metering uses CT/PT to scale down. Story: Cement plant → LV meter would melt, CT/PTs make it possible.