Design of Seismic-Resistant Steel Building Structures-2. Moment Resisting Frames

mangjuhai4 0 views 231 slides Oct 13, 2025
Slide 1
Slide 1 of 231
Slide 1
1
Slide 2
2
Slide 3
3
Slide 4
4
Slide 5
5
Slide 6
6
Slide 7
7
Slide 8
8
Slide 9
9
Slide 10
10
Slide 11
11
Slide 12
12
Slide 13
13
Slide 14
14
Slide 15
15
Slide 16
16
Slide 17
17
Slide 18
18
Slide 19
19
Slide 20
20
Slide 21
21
Slide 22
22
Slide 23
23
Slide 24
24
Slide 25
25
Slide 26
26
Slide 27
27
Slide 28
28
Slide 29
29
Slide 30
30
Slide 31
31
Slide 32
32
Slide 33
33
Slide 34
34
Slide 35
35
Slide 36
36
Slide 37
37
Slide 38
38
Slide 39
39
Slide 40
40
Slide 41
41
Slide 42
42
Slide 43
43
Slide 44
44
Slide 45
45
Slide 46
46
Slide 47
47
Slide 48
48
Slide 49
49
Slide 50
50
Slide 51
51
Slide 52
52
Slide 53
53
Slide 54
54
Slide 55
55
Slide 56
56
Slide 57
57
Slide 58
58
Slide 59
59
Slide 60
60
Slide 61
61
Slide 62
62
Slide 63
63
Slide 64
64
Slide 65
65
Slide 66
66
Slide 67
67
Slide 68
68
Slide 69
69
Slide 70
70
Slide 71
71
Slide 72
72
Slide 73
73
Slide 74
74
Slide 75
75
Slide 76
76
Slide 77
77
Slide 78
78
Slide 79
79
Slide 80
80
Slide 81
81
Slide 82
82
Slide 83
83
Slide 84
84
Slide 85
85
Slide 86
86
Slide 87
87
Slide 88
88
Slide 89
89
Slide 90
90
Slide 91
91
Slide 92
92
Slide 93
93
Slide 94
94
Slide 95
95
Slide 96
96
Slide 97
97
Slide 98
98
Slide 99
99
Slide 100
100
Slide 101
101
Slide 102
102
Slide 103
103
Slide 104
104
Slide 105
105
Slide 106
106
Slide 107
107
Slide 108
108
Slide 109
109
Slide 110
110
Slide 111
111
Slide 112
112
Slide 113
113
Slide 114
114
Slide 115
115
Slide 116
116
Slide 117
117
Slide 118
118
Slide 119
119
Slide 120
120
Slide 121
121
Slide 122
122
Slide 123
123
Slide 124
124
Slide 125
125
Slide 126
126
Slide 127
127
Slide 128
128
Slide 129
129
Slide 130
130
Slide 131
131
Slide 132
132
Slide 133
133
Slide 134
134
Slide 135
135
Slide 136
136
Slide 137
137
Slide 138
138
Slide 139
139
Slide 140
140
Slide 141
141
Slide 142
142
Slide 143
143
Slide 144
144
Slide 145
145
Slide 146
146
Slide 147
147
Slide 148
148
Slide 149
149
Slide 150
150
Slide 151
151
Slide 152
152
Slide 153
153
Slide 154
154
Slide 155
155
Slide 156
156
Slide 157
157
Slide 158
158
Slide 159
159
Slide 160
160
Slide 161
161
Slide 162
162
Slide 163
163
Slide 164
164
Slide 165
165
Slide 166
166
Slide 167
167
Slide 168
168
Slide 169
169
Slide 170
170
Slide 171
171
Slide 172
172
Slide 173
173
Slide 174
174
Slide 175
175
Slide 176
176
Slide 177
177
Slide 178
178
Slide 179
179
Slide 180
180
Slide 181
181
Slide 182
182
Slide 183
183
Slide 184
184
Slide 185
185
Slide 186
186
Slide 187
187
Slide 188
188
Slide 189
189
Slide 190
190
Slide 191
191
Slide 192
192
Slide 193
193
Slide 194
194
Slide 195
195
Slide 196
196
Slide 197
197
Slide 198
198
Slide 199
199
Slide 200
200
Slide 201
201
Slide 202
202
Slide 203
203
Slide 204
204
Slide 205
205
Slide 206
206
Slide 207
207
Slide 208
208
Slide 209
209
Slide 210
210
Slide 211
211
Slide 212
212
Slide 213
213
Slide 214
214
Slide 215
215
Slide 216
216
Slide 217
217
Slide 218
218
Slide 219
219
Slide 220
220
Slide 221
221
Slide 222
222
Slide 223
223
Slide 224
224
Slide 225
225
Slide 226
226
Slide 227
227
Slide 228
228
Slide 229
229
Slide 230
230
Slide 231
231

About This Presentation

steel frame


Slide Content

Design of Seismic-Design of Seismic-
Resistant Steel Resistant Steel
Building StructuresBuilding Structures
Prepared by:
Michael D. Engelhardt
University of Texas at Austin
with the support of the
American Institute of Steel Construction.
Version 1 - March 2007
2. Moment Resisting Frames

Design of Seismic-Resistant Design of Seismic-Resistant
Steel Building StructuresSteel Building Structures
1 - Introduction and Basic Principles
2 - Moment Resisting Frames
3 - Concentrically Braced Frames
4 - Eccentrically Braced Frames
5 - Buckling Restrained Braced Frames
6 - Special Plate Shear Walls

2 - Moment Resisting Frames2 - Moment Resisting Frames
•Definition and Basic Behavior of Moment Resisting
Frames
•Beam-to-Column Connections: Before and After
Northridge
•Panel-Zone Behavior
•AISC Seismic Provisions for Special Moment Frames

Moment Resisting FramesMoment Resisting Frames
•Definition and Basic Behavior of Moment Resisting
Frames
•Beam-to-Column Connections: Before and After
Northridge
•Panel-Zone Behavior
•AISC Seismic Provisions for Special Moment Frames

MOMENT RESISTING FRAME (MRF)MOMENT RESISTING FRAME (MRF)
Advantages
•Architectural Versatility
•High Ductility and Safety
Disadvantages
•Low Elastic Stiffness
Beams and columns with moment resisting
connections; resist lateral forces by flexure and
shear in beams and columns
Develop ductility by:
- flexural yielding of beams
- shear yielding of column panel zones
- flexural yielding of columns

Moment Resisting Frame

Achieving Ductile Behavior:
•Choose frame elements ("fuses") that will
yield in an earthquake, i.e, choose plastic
hinge locations.
•Detail plastic hinge regions to sustain
large inelastic rotations prior to the onset
of fracture or instability.
•Design all other frame elements to be
stronger than the plastic hinge regions.
Understand and Control Inelastic Behavior:

Behavior of an MRF Under Lateral Load:
Internal Forces and Possible Plastic Hinge Locations

M V

Possible Plastic Hinge LocationsPossible Plastic Hinge Locations
Beam
(Flexural Yielding)
Panel Zone
(Shear Yielding)
Column
(Flexural & Axial
Yielding)

Plastic Hinges
In Beams

Plastic Hinges
In Column Panel Zones

Plastic Hinges
In Columns:
Potential for Soft
Story Collapse

Critical Detailing Area for Moment Resisting Frames:
Beam-to-Column Connections
Design Requirement:
Frame must develop large ductility
without failure of beam-to-column
connection.

Moment Resisting FramesMoment Resisting Frames
•Definition and Basic Behavior of Moment Resisting
Frames
•Beam-to-Column Connections: Before and After
Northridge
•Panel-Zone Behavior
•AISC Seismic Provisions for Special Moment Frames

Moment Connection Design Practice Prior to
1994 Northridge Earthquake:
Welded flange-bolted
web moment connection
widely used from early
1970’s to 1994

Pre-Northridge
Welded Flange – Bolted Web Moment Connection
Backup Bar
Beam Flange
Column Flange
Stiffener
Weld Access Hole

Experimental Data on “Pre-Northridge”
Moment Connection
Typical Experimental
Setup:

Initial Tests on Large Scale Specimens:
• Tests conducted at UC Berkeley ~1970
• Tests on W18x50 and W24x76 beams
• Tests compared all-welded connections
with welded flange-bolted web connections

All-Welded Detail

Welded Flange – Bolted Web Detail

Observations from Initial UC Berkeley Tests:Observations from Initial UC Berkeley Tests:
•Large ductility developed by all-welded
connections.
•Welded flange-bolted web connections developed
less ductility, but were viewed as still acceptable.

Subsequent Test Programs:Subsequent Test Programs:
•Welded flange-bolted web connections showed
highly variable performance.
•Typical failure modes: fracture at or near beam
flange groove welds.
•A large number of laboratory tested connections
did not develop adequate ductility in the beam
prior to connection failure.

-5000
-4000
-3000
-2000
-1000
0
1000
2000
3000
4000
5000
-0.04-0.03-0.02-0.01 0 0.01 0.02 0.03 0.04
Drift Angle (rad)
B
e
n
d
i
n
g

M
o
m
e
n
t

(
k
N
-
m
)
Brittle Fracture at Bottom
Flange Weld
M
p
M
p
Pre-Northridge Connection

Summary of Testing Prior to Summary of Testing Prior to
Northridge EarthquakeNorthridge Earthquake
•Welded flange – bolted web connection showed
highly variable performance
•Many connections failed in laboratory with little
or no ductility

1994 Northridge Earthquake1994 Northridge Earthquake
Widespread failure of
welded flange - bolted
web moment
connections

1994 Northridge Earthquake1994 Northridge Earthquake
•January 17, 1994
•Magnitude = 6.8
•Epicenter at Northridge - San Fernando Valley
(Los Angeles area)
•Fatalities: 58
•Estimated Damage Cost: $20 Billion

Northridge - Ground AccelerationsNorthridge - Ground Accelerations
•Sylmar: 0.91g H 0.60g V
•Sherman Oaks: 0.46g H 0.18g V
•Granada Hills: 0.62g H 0.40g V
•Santa Monica: 0.93g H 0.25g V
•North Hollywood:0.33g H 0.15g V

Damage to Steel Buildings in the Damage to Steel Buildings in the
Northridge EarthquakeNorthridge Earthquake
•Large number of modern steel buildings
sustained severe damage at beam-to-column
connections.
•Primary Damage: Fracture in and around beam
flange groove welds
•Damage was largely unexpected by engineering
profession

Damage Observations:Damage Observations:
Steel Moment Steel Moment
ConnectionsConnections

Backup Bar
Beam Flange
Column Flange
Stiffener
Weld Access Hole
Pre-Northridge
Welded Flange – Bolted Web Moment Connection

Damage ObservationsDamage Observations
•A large number of steel moment frame buildings
suffered connection damage
•No steel moment frame buildings collapsed
•Typical Damage:
–fracture of groove weld
–“divot” fracture within column flange
–fracture across column flange and web

Observations from Studies of Fractured Observations from Studies of Fractured
ConnectionsConnections
•Many connections failed by brittle fracture with little or
no ductility
•Brittle fractures typically initiated in beam flange
groove welds

Response to Northridge Moment Connection Response to Northridge Moment Connection
DamageDamage
•Nearly immediate elimination of welded flange -
bolted web connection from US building codes and
design practice
•Intensive research and testing efforts to understand
causes of damage and to develop improved
connections
–AISC, NIST, NSF, etc.
–SAC Program (FEMA)

Causes of Moment Connection Causes of Moment Connection
Damage in NorthridgeDamage in Northridge
•Welding
•Connection Design
•Materials

Causes of Northridge Moment Connection Causes of Northridge Moment Connection
Damage:Damage:
Welding Factors
•Low Fracture Toughness of Weld Metal
•Poor Quality
•Effect of Backing Bars and Weld Tabs

Weld Metal ToughnessWeld Metal Toughness
•Most common Pre-Northridge welding electrode
(E70T-4) had very low fracture toughness.
Typical Charpy V-Notch: < 5 ft.-lbs at 70
0
F
(7 J at 21
0
C)

Welding QualityWelding Quality
•Many failed connections showed evidence of poor
weld quality
•Many fractures initiated at root defects in bottom
flange weld, in vicinity of weld access hole

Weld Backing Bars and Weld TabsWeld Backing Bars and Weld Tabs
•Backing Bars:
–Can create notch effect
–Increases difficulty of inspection
•Weld Tabs:
–Weld runoff regions at weld tabs contain
numerous discontinuities that can potentially
initiate fracture

Design Factors:
Stress/Strain Too High at Beam Flange Groove Weld
•Inadequate Participation of Beam Web Connection in
Transferring Moment and Shear
•Effect of Weld Access Hole
•Effect of Column Flange Bending
•Other Factors
Causes of Northridge Moment Connection Causes of Northridge Moment Connection
Damage:Damage:

M
p
Increase in Flange Stress Due to
Inadequate Moment Transfer Through Web Connection
F
l
a
n
g
e

S
t
r
e
s
s
F
y
F
u

V
flange
Increase in Flange Stress Due to Shear in Flange

Stress
Concentrations:
•Weld access
hole
•Shear in flange
•Inadequate
flexural
participation of
web connection

Causes of Moment Connection Damage in Causes of Moment Connection Damage in
Northridge:Northridge:
Material Factors (Structural Steel)
•Actual yield stress of A36 beams often
significantly higher than minimum
specified

Strategies for Improved Performance Strategies for Improved Performance
of Moment Connectionsof Moment Connections
•Welding
•Materials
•Connection Design and Detailing

Strategies for Improved Performance of Strategies for Improved Performance of
Moment Connections:Moment Connections:
WELDING
•Required minimum toughness for weld metal:
–Required CVN for all welds in SLRS:
20 ft.-lbs at 0
0
F
–Required CVN for Demand Critical welds:
20 ft.-lbs at -20
0
F and 40 ft.-lbs at 70
0
F

WELDING
•Improved practices for backing bars and weld tabs
Typical improved practice:
–Remove bottom flange backing bar
–Seal weld top flange backing bar
–Remove weld tabs at top and bottom flange welds
•Greater emphasis on quality and quality control (AISC
Seismic Provisions - Appendix Q and W)
Strategies for Improved Performance of Strategies for Improved Performance of
Moment Connections:Moment Connections:

Strategies for Improved Performance of Strategies for Improved Performance of
Moment Connections:Moment Connections:
Materials (Structural Steel)
•Introduction of “expected yield stress” into design
codes
F
y
= minimum specified yield strength
R
y= 1.5 for ASTM A36
= 1.1 for A572 Gr. 50 and A992
(See AISC Seismic Provisions - Section 6 for other values of R
y
)
Expected Yield Stress = R
y
F
y

Strategies for Improved Performance of Strategies for Improved Performance of
Moment Connections:Moment Connections:
Materials (Structural Steel)
•Introduction of ASTM A992 steel for wide flange
shapes
ASTM A992ASTM A992
Minimum F
y
= 50 ksi
Maximum F
y = 65 ksi
Minimum F
u
= 65 ksi
Maximum F
y
/ F
u
= 0.85

Strategies for Improved Performance of Strategies for Improved Performance of
Moment Connections:Moment Connections:
Connection Design
•Improved Weld Access Hole Geometry

Improved Weld Access
Hole
See Figure 11-1 in the
2005 AISC Seismic
Provisions for dimensions
and finish requirements

Strategies for Improved Performance of Strategies for Improved Performance of
Moment Connections:Moment Connections:
Connection Design
•Development of Improved Connection Designs
and Design Procedures
–Reinforced Connections
–Proprietary Connections
–Reduced Beam Section (Dogbone)
Connections
–Other SAC Investigated Connections

Proprietary ConnectionsProprietary Connections

SIDE PLATE
CONNECTION

SLOTTED WEB
CONNECTION

Connections Investigated Through Connections Investigated Through
SAC-FEMA Research ProgramSAC-FEMA Research Program

Reduced Beam
Section

Welded
Unreinforced
Flange - Bolted
Web

Welded
Unreinforced
Flange - Welded
Web

Free Flange
Connection

Welded Flange
Plate Connection

Bolted Unstiffened
End Plate

Bolted Stiffened
End Plate

Bolted Flange
Plate

Double Split Tee

Results of SAC-FEMA Research ProgramResults of SAC-FEMA Research Program
Recommended Seismic Design Criteria
for Steel Moment Frames
•FEMA 350
Recommended Seismic Design Criteria for New Steel Moment-
Frame Buildings
•FEMA 351
Recommended Seismic Evaluation and Upgrade Criteria for
Existing Welded Steel Moment-Frame Buildings
•FEMA 352
Recommended Postearthquake Evaluation and Repair Criteria
for Welded Steel Moment-Frame Buildings
•FEMA 353
Recommended Specifications and Quality Assurance
Guidelines for Steel Moment-Frame Construction for Seismic
Applications

FEMA 350

Moment Resisting FramesMoment Resisting Frames
•Definition and Basic Behavior of Moment Resisting
Frames
•Beam-to-Column Connections: Before and After
Northridge
•Panel-Zone Behavior
•AISC Seismic Provisions for Special Moment Frames

Column Panel Zone
Column Panel Zone:
- subject to high shear
- shear yielding and large
shear deformations possible
(forms “shear hinge”)
- provides alternate yielding
mechanism in a steel moment
frame

Joint deformation
due to panel zone
shear yielding

Plastic Shear Hinges
In Column Panel Zones

"kink" at corners of
panel zone

-400
-300
-200
-100
0
100
200
300
400
-0.08-0.06-0.04-0.02 0 0.02 0.04 0.06 0.08
Story Drift Angle (rad)
C
o
l
u
m
n

T
i
p

L
o
a
d

(
k
i
p
s
)
Composite RBS Specimen with
Weak Panel Zone

-1200
-800
-400
0
400
800
1200
-0.08-0.06-0.04-0.02 0 0.02 0.04 0.06 0.08
Panel Zone
g
(rad)
P
a
n
e
l

Z
o
n
e

S
h
e
a
r

F
o
r
c
e

(
k
i
p
s
)
Composite RBS Specimen with
Weak Panel Zone

Observations on Panel Zone BehaviorObservations on Panel Zone Behavior
•Very high ductility is possible.
•Localized deformations (“kinking”) at corners of panel
zone may increase likelihood of fracture in vicinity of
beam flange groove welds.
•Building code provisions have varied greatly on panel
zone design.
•Current AISC Seismic Provisions permits limited
yielding in panel zone.
•Further research needed to better define acceptable
level of panel zone yielding

Moment Resisting FramesMoment Resisting Frames
•Definition and Basic Behavior of Moment Resisting
Frames
•Beam-to-Column Connections: Before and After
Northridge
•Panel-Zone Behavior
•AISC Seismic Provisions for Special Moment Frames

2005 AISC Seismic Provisions2005 AISC Seismic Provisions
Section 9Special Moment Frames (SMF)
Section 10Intermediate Moment Frames (IMF)
Section 11Ordinary Moment Frames (OMF)

Section 9
Special Moment Frames (SMF)
9.1Scope
9.2Beam-to-Column Joints and Connections
9.3Panel Zone of Beam-to-Column Connections
9.4Beam and Column Limitations
9.5Continuity Plates
9.6Column-Beam Moment Ratio
9.7Lateral Bracing of at Beam-to-Column Connections
9.8Lateral Bracing of Beams
9.9Column Splices

AISC Seismic Provisions - SMF
9.1 Scope
Special moment frames (SMF) are expected to withstand
significant inelastic deformations when subjected to the
forces resulting from the motions of the design
earthquake.

AISC Seismic Provisions - SMF
9.2 Beam-to-Column Connections
9.2aRequirements
9.2bConformance Demonstration
9.2cWelds
9.2dProtected Zones

AISC Seismic Provisions - SMF - Beam-to-Column Connections
9.2a Requirements
Beam-to-column connections shall satisfy the following three
requirements:
1.The connection shall be capable of sustaining an
interstory drift angle of at least 0.04 radians.
2.The measured flexural resistance of the
connection, determined at the column face, shall
equal at least 0.80 M
p of the connected beam at
an interstory drift angle of 0.04 radians.

9.2a Requirements
Beam-to-column connections shall satisfy the following three
requirements (cont):
3.The required shear strength of the connection
shall be determined using the following quantity
for the earthquake load effect E:
E = 2 [ 1.1 R
y M
p ] / L
h (9-1)
where:
R
y
= ratio of the expected yield strength to the
minimum specified yield strength
M
p = nominal plastic flexural strength
L
h = distance between plastic hinge locations

L
h
(1.2 + 0.2S
DS
) D + 0.5 L or (0.9-0.2S
DS
) D
1.1 R
y
M
p
1.1 R
y
M
p
V
u
= 2 [ 1.1 R
y
M
p
] / L
h
+ V
gravity
V
u
V
u
Required Shear Strength of Beam-to-Column Connection

AISC Seismic Provisions - SMF - Beam-to-Column Connections
9.2b Conformance Demonstration
Demonstrate conformance with requirements of Sect. 9.2a by one of
the following methods:
I.Conduct qualifying cyclic tests in accordance with Appendix S.
Tests conducted specifically for the project, with test specimens
that are representative of project conditions.
or
Tests reported in the literature (research literature or other
documented test programs), where the test specimens are
representative of project conditions.

9.2b Conformance Demonstration
Demonstrate conformance with requirements of Sect. 9.2a by one of
the following methods (cont):
II.Use connections prequalified for SMF in accordance with Appendix P
Use connections prequalified by the AISC Connection
Prequalification Review Panel (CPRP) and documented in Standard
ANSI/AISC 358 - "Prequalified Connections for Special and Intermediate
Steel Moment Frames for Seismic Applications"
or
Use connection prequalified by an alternative review panel that is
approved by the Authority Having Jurisdiction.

Test connection
in accordance
with Appendix S
9.2b Conformance Demonstration - by Testing

Appendix S
Qualifying Cyclic Tests of Beam-to-Column
and Link-to-Column Connections
Testing Requirements:
•Test specimens should be representative of prototype
(Prototype = actual building)
•Beams and columns in test specimens must be nearly full-scale
representation of prototype members:
- depth of test beam ≥ 0.90  depth of prototype beam
- wt. per ft. of test beam ≥ 0.75  wt. per ft. of prototype beam
- depth of test column ≥ 0.90  depth of prototype column
•Sources of inelastic deformation (beam, panel zone, connection
plates, etc) in the test specimen must similar to prototype.

Appendix S
Testing Requirements (cont):
•Lateral bracing in test specimen should be similar to prototype.
•Connection configuration used for test specimen must match
prototype.
•Welding processes, procedures, electrodes, etc. used for test
specimen must be representative of prototype.
See Appendix S for other requirements.

Typical Test Subassemblages
Exterior Subassemblage Interior Subassemblage

Typical Exterior Subassemblage
Δ
L
beam

Interstory Drift Angle  =
Δ
L
beam

Typical Exterior Subassemblage

Δ
H
column

Typical Interior Subassemblage
Interstory Drift Angle  =
Δ
H
column

Typical Interior Subassemblage

Typical Interior Subassemblage (with concrete floor slab)

Appendix S
Testing Requirements - Loading History
Apply the following loading history:
6 cycles at =  0.00375 rad.
6 cycles at =  0.005 rad.
6 cycles at =  0.0075 rad.
4 cycles at =  0.01 rad.
2 cycles at =  0.015 rad.
2 cycles at =  0.02 rad.
2 cycles at =  0.03 rad.
2 cycles at =  0.04 rad.
continue at increments of 0.01 rad, with
two cycles of loading at each step

Appendix S
Testing Requirements - Loading History
-0.05
-0.04
-0.03
-0.02
-0.01
0
0.01
0.02
0.03
0.04
0.05
0.06
I
n
t
e
r
s
t
o
r
y

D
r
i
f
t

A
n
g
l
e


Acceptance Criteria for SMF Beam-to-Column Connections:
After completing at least one loading cycle at  0.04 radian, the measured flexural
resistance of the connection, measured at the face of the column, must be at least
0.80 M
p
of the connected beam

Example of Successful Conformance Demonstration Test
per Appendix S:
-40000
-30000
-20000
-10000
0
10000
20000
30000
40000
-0.08 -0.06 -0.04 -0.02 0 0.02 0.04 0.06 0.08
Interstory Drift Angle (rad)
B
e
a
m

M
o
m
e
n
t

a
t

F
a
c
e

o
f

C
o
l
u
m
n

(
i
n
-
k
i
p
s
)
0.8 Mp
- 0.8 Mp
M0.04

0.8 Mp
M0.04

0.8 Mp

A Prequalified connection is one that has undergone sufficient
testing (per Appendix S)
analysis
evaluation and review
so that a high level of confidence exists that the connection can
fulfill the performance requirements specified in Section 9.2a for
Special Moment Frame Connections
9.2b Conformance Demonstration
........by use of Prequalified Connection

Requirements for Prequalification of Connections:
Appendix P - Prequalification of Beam-to-Column
and Link-to-Column Connections
9.2b Conformance Demonstration .....
by use of Prequalified Connection
Authority to Prequalify of Connections:
AISC Connection Prequalification Review Panel (CPRP)
Information on Prequalified Connections:
Standard ANSI/AISC 358 - "Prequalified Connections for
Special and Intermediate Steel Moment Frames for Seismic
Applications"

ANSI/AISC 358 - "Prequalified Connections for Special and
Intermediate Steel Moment Frames for Seismic Applications"
Connections Prequalified in ANSI/AISC 358 (1st Ed - 2005)
•Reduced Beam Section (RBS) Connection
•Bolted Unstiffened and Stiffened Extended End-
Plate Connection

RBS Concept:
•Trim Beam Flanges Near
Connection
•Reduce Moment at
Connection
•Force Plastic Hinge Away
from Connection
Reduced Beam Section (RBS) Moment Connection

Example of laboratory performance of an RBS connection:

Whitewashed connection prior to testing:

Whitewashed connection prior to testing:

Connection at   0.02 radian......

Connection at   0.02 radian......

Connection at   0.03 radian......

Connection at   0.04 radian......

-5000
-4000
-3000
-2000
-1000
0
1000
2000
3000
4000
5000
-0.05-0.04-0.03-0.02-0.010 0.010.020.030.040.05
Drift Angle (radian)
B
e
n
d
i
n
g

M
o
m
e
n
t

(
k
N
-
m
)
RBS Connection
M
p
M
p

ANSI/AISC 358:
Prequalification Requirements for RBS in SMF
•Beam depth: up to W36
•Beam weight: up to 300 lb/ft
•Column depth:up to W36 for wide-flange
up to 24-inches for box columns
•Beam connected to column flange
(connections to column web not prequalified)
•RBS shape: circular
•RBS dimensions:per specified design procedure

ANSI/AISC 358:
Prequalification Requirements for RBS in SMF
cont......
Beam flange welds:- CJP groove welds
- Treat welds as Demand Critical
- Remove bottom flange backing and provide
reinforcing fillet
weld
- Leave top flange backing in-place; fillet weld
backing to column
flange
- Remove weld tabs at top and bottom flanges
Beam web to column connection:
- Use fully welded web connection (CJP weld
between beam
web and column flange)
See ANSI/AISC 358 for additional requirements (continuity plates, beam
lateral bracing, RBS cut finish req'ts., etc.)

RBS with welded web
connection:

ANSI/AISC 358:
Prequalification Requirements for RBS in SMF
cont.......
Protected Zone

Lateral brace at center of RBS - violates Protected Zone

Examples of RBS Connections.....

AISC Seismic Provisions - SMF
9.3 Panel Zone of Beam-to-Column Connections
9.3aShear Strength
9.3bPanel Zone Thickness
9.3cPanel Zone Doubler Plates

AISC Seismic Provisions - SMF - Panel Zone Requirements
9.3a Shear Strength
The minimum required shear strength, R
u
, of the panel zone shall be
taken as the shear generated in the panel zone when plastic hinges form
in the beams.
To compute panel zone shear.....
Determine moment at beam plastic hinge locations
(1.1 R
y
M
p
or as specified in ANSI/AISC 358)
Project moment at plastic hinge locations to the face
of the column (based on beam moment gradient)
Compute panel zone shear force.

M
pr-2
M
pr1
V
beam-2
V
beam-1
Beam 1 Beam 2
Plastic Hinge Location
Plastic Hinge Location
s
h
s
h
M
f1 M
f2
M
pr = expected moment at plastic hinge = 1.1 R
y M
p or as specified in ANSI/AISC 358
V
beam = beam shear (see Section 9.2a - beam required shear strength)
s
h = distance from face of column to beam plastic hinge location (specified in
ANSI/AISC 358)
Panel Zone Shear Strength (cont)

M
pr-2
M
pr1
V
beam-2
V
beam-1
Beam 1 Beam 2
Plastic Hinge Location
Plastic Hinge Location
s
h
s
h
M
f1 M
f2
Panel Zone Shear Strength (cont)
M
f = moment at column face
M
f = M
pr + V
beam  s
h

Panel Zone Shear Strength (cont)
 
c
fb
f
u V
td
M
R 



Panel Zone Required Shear Strength =

Panel Zone Shear Strength (cont)
Panel Zone Design Requirement:
R
u  
v R
v where 
v = 1.0
R
v
= nominal shear strength, based
on a limit state of shear yielding, as
computed per Section J10.6 of the
AISC Specification

Panel Zone Shear Strength (cont)
To compute nominal shear strength, R
v
, of panel zone:
When P
u
 0.75 P
y
in column:









pcb
2
cfcf
pcyv
tdd
tb3
1tdF6.0R
(AISC Spec EQ J10-11)
Where:d
c
=column depth
d
b
=beam depth
b
cf
=column flange width
t
cf
=column flange thickness
F
y
=minimum specified yield stress of column web
t
p
=thickness of column web including doubler plate

Panel Zone Shear Strength (cont)
To compute nominal shear strength, R
v
, of panel zone:
When P
u
> 0.75 P
y
in column (not recommended):


















y
u
pcb
2
cfcf
pcyv
P
P2.1
9.1
tdd
tb3
1tdF6.0R (AISC Spec EQ J10-12)

If shear strength of panel zone is inadequate:
- Choose column section with larger web area
- Weld doubler plates to column
Options for Web Doubler Plates

AISC Seismic Provisions - SMF
9.4 Beam and Column Limitations
Beam and column sections must satisfy the width-
thickness limitations given in Table I-8-1
y
s
f
f
F
E
30.0
t2
b

Beam Flanges
Beam Web
y
s
w F
E
45.2
t
h

b
f
t
f
h
tw

Column Flanges
y
s
f
f
F
E
30.0
t2
b

Column Web
125.0
P
P
y
u

 







y
u
y
s
w
P
P
54.11
F
E
14.3
t
h


125.0
P
P
y
u


y
s
y
u
y
s
w
F
E
49.1
P
P
33.2
F
E
12.1
t
h











Note: Column flange and web slenderness limits can be taken as 
p
in AISC
Specification Table B4.1, if the ratio for Eq. 9-3 is greater than 2.0
9.4 Beam and Column Limitations

Continuity Plates
AISC Seismic Provisions - SMF
9.5 Continuity Plates

Continuity Plates
9.5 Continuity Plates

AISC Seismic Provisions - SMF
9.5 Continuity Plates
Continuity plates shall be consistent with the
requirements of a prequalified connection as specified in
ANSI/AISC 358 (Prequalified Connections for Special and
Intermediate Steel Moment Frames for Seismic Applications)
or
As determined in a program of qualification testing in
accordance with Appendix S

ANSI/AISC 358 - Continuity Plate Requirements
Continuity Plates
For Wide-Flange Columns:
Continuity plates are required, unless:
ycyc
ybyb
bfbfcf
FR
FR
tb8.14.0t
6
b
t
bf
cf

and
t
cf
=column flange thickness
b
bf
=beam flange width
t
bf
=beam flange thickness

ANSI/AISC 358 - Continuity Plate Requirements
Continuity Plates
For Box Columns:
Continuity plates must be provided.

ANSI/AISC 358 - Continuity Plate Requirements
Required thickness of continuity plates
a)For one-sided (exterior) connections, continuity plate thickness shall be
at least one-half of the thickness of the beam flange.
b)For two-sided (interior) connections, continuity plate thickness shall be at
least equal to the thicker of the two beam flanges on either side of the
column
For other design, detailing and welding requirements for
continuity plates - See ANSI/AISC 358

t
cp
t
bf t
cp ≥ 1/2  t
bf
ANSI/AISC 358 - Continuity Plate Requirements

t
cp
t
bf-2
t
bf-1
t
cp ≥ larger of (t
bf-1 and t
bf-2 )
ANSI/AISC 358 - Continuity Plate Requirements

AISC Seismic Provisions - SMF
9.6 Column-Beam Moment Ratio
Section 9.6 requires strong column - weak girder
design for SMF (with a few exceptions)
Purpose of strong column -
weak girder requirement:
Prevent Soft Story Collapse

AISC Seismic Provisions - SMF
9.6 Column-Beam Moment Ratio
The following relationship shall be satisfied at beam-to-
column connections:
0.1
M
M
*
pb
*
pc



Eqn. (9-3)

9.6 Column-Beam Moment Ratio
0.1
M
M
*
pb
*
pc



 
*
pc
M the sum of the moments in the column above and below the joint at
the intersection of the beam and column centerlines.
∑M
*
pc is determined by summing the projections of the nominal
flexural strengths of the columns above and below the joint to the
beam centerline with a reduction for the axial force in the column.
It is permitted to take ∑M
*
pc = ∑Z
c ( F
yc - P
uc/A
g)
 
*
pb
M the sum of the moments in the beams at the intersection of the beam
and column centerlines.
∑M
*
pb
is determined by summing the projections of the expected
flexural strengths of the beams at the plastic hinge locations to the
column centerline.

C Column
L
C Beam
L
M*
pc-top
M*
pc-bottomM*
pb-left
M*
pb-right
0.1
M
M
*
pb
*
pc



Note:
M*
pc is based on minimum specified yield
stress of column
M*
pb is based on expected yield stress of beam
and includes allowance for strain hardening

M
pr-right
M
pr-left
V
beam-right
V
beam-left
Left Beam Right Beam
Plastic Hinge Location
Plastic Hinge Location
s
h
+d
col
/2
M
pr = expected moment at plastic hinge = 1.1 R
y M
p or as specified in ANSI/AISC 358
V
beam = beam shear (see Section 9.2a - beam required shear strength)
s
h = distance from face of column to beam plastic hinge location (specified in
ANSI/AISC 358)
M*
pb-leftM*
pb-right
s
h
+d
col
/2
M*
pb
= M
pr
+ V
beam
(s
h
+ d
col
/2 )
Computing M*
pb

Top Column
Bottom Column
M
pc
= nominal plastic moment capacity of column, reduced for presence of axial force; can
take M
pc = Z
c (F
yc - P
uc / A
g) [or use more exact moment-axial force interaction
equations for a fully plastic cross-section]
V
col
= column shear - compute from statics, based on assumed location of column inflection
points (usually midheight of column)
M*
pc-bottom
M*
pc
= M
pc
+ V
col
(d
beam
/2 )
Computing M*
pc
M
pc-bottom
M
pc-top
M*
pc-top
d
beam
V
col-top
V
col-bottom

AISC Seismic Provisions - SMF
9.8 Lateral Bracing of Beams
Must provide adequate lateral bracing of beams in SMF
so that severe strength degradation due to lateral
torsional buckling is delayed until sufficient ductility is
achieved
(Sufficient ductility = interstory drift angle of at least 0.04
rad is achieved under Appendix S loading protocol)

Lateral Torsional BucklingLateral Torsional Buckling
Lateral torsional
buckling controlled by:
y
b
r
L
L
b
= distance between beam lateral braces
r
y
= weak axis radius of gyration
L
b
L
b
Beam lateral braces (top & bottom flanges)

M

M
p
Increasing L
b / r
y
Effect of Lateral Torsional Buckling on Flexural Strength and Ductility:Effect of Lateral Torsional Buckling on Flexural Strength and Ductility:
M

 ksi50Fforr50r
F
E
086.0L
yyy
y
b










AISC Seismic Provisions - SMF
9.8 Lateral Bracing of Beams
Both flanges of beams shall be laterally braced, with a maximum
spacing of L
b = 0.086 r
y E / F
y
Note:
For typical SMF beam: r
y
 2 to 2.5 inches.
and L
b  100 to 125 inches (approx. 8 to 10 ft)

AISC Seismic Provisions - SMF
9.8 Lateral Bracing of Beams
In addition to lateral braces provided as a maximum spacing
of L
b = 0.086 r
y E / F
y :
Lateral braces shall be placed near concentrated forces, changes in cross-
section and other locations where analysis indicates that a plastic hinge
will form.
The placement of lateral braces shall be consistent with that specified in
ANSI/AISC 358 for a Prequalified Connection, or as otherwise determined
by qualification testing.

ANSI/AISC 358 - Lateral Bracing Requirements for the RBS
For beams with an RBS connection:
When a composite concrete floor slab is present, no additional
lateral bracing is required at the RBS.
When a composite concrete floor slab is not present, provide an
additional lateral brace at the RBS. Attach brace just outside of
the RBS cut, at the end farthest from the column face.

Section 9
Special Moment Frames (SMF)
9.1Scope
9.2Beam-to-Column Joints and Connections
9.3Panel Zone of Beam-to-Column Connections
9.4Beam and Column Limitations
9.5Continuity Plates
9.6Column-Beam Moment Ratio
9.7Lateral Bracing of at Beam-to-Column
Connections
9.8Lateral Bracing of Beams
9.9Column Splices
Tags