Electrical Power substation

8,322 views 46 slides Mar 03, 2018
Slide 1
Slide 1 of 46
Slide 1
1
Slide 2
2
Slide 3
3
Slide 4
4
Slide 5
5
Slide 6
6
Slide 7
7
Slide 8
8
Slide 9
9
Slide 10
10
Slide 11
11
Slide 12
12
Slide 13
13
Slide 14
14
Slide 15
15
Slide 16
16
Slide 17
17
Slide 18
18
Slide 19
19
Slide 20
20
Slide 21
21
Slide 22
22
Slide 23
23
Slide 24
24
Slide 25
25
Slide 26
26
Slide 27
27
Slide 28
28
Slide 29
29
Slide 30
30
Slide 31
31
Slide 32
32
Slide 33
33
Slide 34
34
Slide 35
35
Slide 36
36
Slide 37
37
Slide 38
38
Slide 39
39
Slide 40
40
Slide 41
41
Slide 42
42
Slide 43
43
Slide 44
44
Slide 45
45
Slide 46
46

About This Presentation

Its overview of electrical power substation, like what are the things are inside and what are the use of their inside a power substation.


Slide Content

Overview of Power
Substation

Table of Content
➢Objective
➢Introduction
➢Type of Substation
➢Supply line
➢Transformer
➢Bus bar
➢Switchgear
➢Protective Devices
➢Out coming Feeders
➢Switching Apparatus
➢Conductor
➢Insulator
➢Lightning Arrester
➢Surge Arrester
➢Grounding
➢Battery Bank
➢Capacitor Bank
➢Communication
➢HVAC System
➢Fire fighting System
➢Facility

Objective
This programmed is designed to have
overview on Electrical Power
Substation and it’s various types and
equipment or machines and their
fundamentals

Introduction
A substation is a part
of an electrical
generation,
transmission, and
distribution system.
Substations transform
voltage from high to
low, or the reverse, or
perform several other
important functions.
Typical Picture of Power substation

Type of Substations
The substations may be classified in numerous ways, such as by
nature of duties, operating voltage, functions, importance, and
design.
➢Classification based on function :-
Step-up Substation
Step-down Substation
Switching Substation
Distribution Substation
Sulfur Hexafluoride Substation (SF6) GIS

Type of Substations
A substation based on it’s function further can be sub
categorized based on by construction or arrangement. There
are some example of sub categorized substation based on
their construction below.
➢Classification based on Construction:-
Outdoor Substation
Indoor Substation
Underground Substation

Step-up Substation
➢Astep-up transmission substation
receives electric power from a
nearby generating facility and
uses a large power transformer
to increase the voltage for
transmission to distant locations.
➢These substation further can be
sub categorized based on their
construction as per requirement
such as Indoor, Outdoor, Gas
Insulated, Under Ground, Pole
Mounted.
Outdoor Step-up Transmission
Substation

Step-down Substation
➢The step-down substation can change
the transmission voltage to a sub
transmission voltage, usually 69 kV
by using step-down transformer.
➢The sub transmission voltage lines can
then serve as a source to distribution
substations.
➢Step-down transmission substations
are located at switching points in an
electrical grid.
➢These substation also further can be
sub categorized based on their
construction as per requirement such
as Indoor, Outdoor, Gas Insulated,
Under Ground, Pole Mounted.
Step-down outdoor Substation

Switching Substation
➢Aswitching stationis a
substationwithout transformers and
operating only at a single voltage
level.
➢Switchingstations are sometimes
used as collector and distribution
stations. Sometimes they are used
forswitchingthe current to back-up
lines or for parallelizing circuits in
case of failure.
➢A switching station may also be
known as a switchyard, and these
are commonly located directly
adjacent to or nearby apower
station.
Switchyard or Switching Substation

Distribution Substation
➢Distribution substations are
located near to the end-users.
➢Distribution substation
transformers change the
transmission or sub transmission
voltage to lower levels for use by
end-users.
➢From here the power is
distributed to industrial,
commercial, and residential
consumers.
Small Out Door Distribution
Substation

Gas Insulated Substation (SF6) GIS
➢Agas insulated substation(GIS) is
a high voltage substationin which
the major structures are contained in
a sealed environment with sulfur
hexafluoride SF6 gas as the
insulating medium.
➢The clearance required for phase to
phase and phase to ground for all
equipment is much lower than that
required in an air insulated
substation.
➢Although the initial cost of building a
GIS is higher than building an air
insulated substation, the operation
and maintenance costs of a GIS are
less.
Indoor GIS

Supply line
➢Substation is connected to a
transmission system via at least one
supply line, which is often called a
primary feeder.
➢A supply line can be an overhead line
or an underground feeder, depending
on the location of the substation,
underground cable lines mostly used in
urban areas and overhead lines in
desert or open area.
➢Supply lines are connected via high
voltage disconnecting switches in order
to isolate lines from substation to
perform maintenance or repair work.
Supply Line or Transmission Line

Transformer
➢Atransformeris an electrical
device that transfers electrical
energy from one coil called
primary coil to other coil
secondary coil
throughelectromagnetic
induction .
➢The coil connected to incoming
voltage called primary coil
while the coil connected to the
outgoing coil called
secondary coil
➢Transformers are used to
increase or decrease the
alternating current in electric
power applications.
Typical Diagram of Electrical
Transformer

Type of Transformer
There are various type of transformer based on
their functions and use.
Power transformer
Service Transformer
Voltage Transformer (PT -Potential Transformer)
Current Transformer (CT -Instrument Transformer)

Power Transformer
Power transformersare
used in the high voltage
transmission network to
step up and step down
the voltage.
Thesetransformersare
generally used for the
purpose of transmission
of heavy voltage and
rated in 69kva,115kva,
270kva,380kva etc.
Typical picture of Power
Transformer

Distribution Transformer
➢Adistribution transformeror
servicetransformeris a
transformerthat provides the
final voltage transformation
in the electric
powerdistribution
system, stepping down the
voltage used in
thedistributionlines to the
level used for lighting or
utility purpose in power
substation.
Typical picture of Service transformer or
distribution Transformer

Voltage Transformer
➢Potential transformer is quite
similar to the current transformer,
but it is used for taking samples
of high voltages of a system for
providing low-voltage to the
relays of protection system and
also to the low-rating meters for
voltage measurement.
➢From this low-voltage
measurement, the actual system’s
high voltage can be calculated
without measuring high voltages
directly to avoid the cost of the
measurement system.
Potential Transformer or
Voltage transformer

Current Transformer
➢Current transformer isused for the
measurement of the alternating
current by taking samples of the
higher currents of the system.
➢These reduced samples are in
accurate proportions with the
actual high currents of the system.
➢These are used for installation and
maintenance of the current relays
in substations for protection
purpose which are normally have
low-current ratings for their
operation.
Current Transformer

Bus bar
➢Bus bars also called buses can be
found throughout the entire power
system, from generation to industrial
plants to electrical distribution boards.
➢Bus bars are used to carry large
current and to distribute current to
multiple circuits within switchgear or
equipment.
➢Originally, bus bars consisted of
uncovered copper conductors
supported on insulators
➢Bus bar's conductors and current-
carrying parts can be either copper,
aluminum, or copper alloy rated for
the purpose.
Copper and aluminum bus bar

Switchgear
➢Switchgear is a general term
covering primary switching and
interrupting devices together with its
control and regulating equipment.
➢Power switchgear includes breakers,
disconnect switches, main bus
conductors, interconnecting wiring,
support structures with insulators,
enclosures, and secondary devices
for monitoring and control.
➢Power switchgear is used throughout
the entire power system, from
generation to industrial plants to
connect incoming power supply and
distribute power to consumers.
High Voltage Switchgear

Switchgear
➢One of the basic functions of switchgear
is protection, which is interruption of
short-circuit and overload fault currents
while maintaining service to unaffected
circuits. Switchgear also provides isolation
of circuits from power supplies.
Switchgear is also used to enhance
system availability by allowing more than
one source to feed a load.
➢switchgear has two types of component
1.Control systems -control panels, current
transformers, potential transformers,
protective relays, and associated
circuitry, that monitor, control, and protect
the power conducting components .
➢2. Power conducting components-such as
switches, circuit breakers, fuses, and
lightning arrestors, that conduct or
interrupt the flow of electrical power
Switchgear System Metering, Protective
and monitoring Device

Metal-Clad Switchgear
➢Metal-clad switchgears are
commonly used throughout the
industry for distributing supply
voltage service above 1,000 V.
➢The primary voltage breakers
and switches are mounted on a
removable mechanism to allow
for movement and proper
alignment.
➢All live parts are enclosed within
grounded metal compartments
➢Switchgear consist metering and
protective device in it such as
protective relay, watt meter,
ampere meter volt meter etc.
Metal Clad Switchgear

Protective Device
➢The devices that are used to
protect the power systems from
faults are calledprotection
devices.
➢Advantages of protected devices
with these three basic components
include safety, economy, and
accuracy
➢There are three parts of protective
devices:
Instrument transformer current
or potential (CT or VT)
Relay
Circuit breaker
Combination of Protection device
(Digital multifunction relay)

Relay
➢Aprotective relayis adevice
designed to trip acircuit breaker
when a fault is detected and in
abnormal operating conditions
such as over-current, over-voltage,
reversepowerflow, over-
frequency, and under-frequency.
➢Electromechanical protective relays
operate by electromagnetic
induction.
➢protective relays have well-
established, selectable, and
adjustable time and current or
other operating parameter
characteristics.
Numeric Multifunction
relay
Electromechanical relay

Out coming Feeders
➢A number of out coming feeders
are connected to the substation
bus to carry power from the
substation to points of service
➢Feeders can be run overhead
along streets, or beneath streets,
and carry power to distribution
transformers at or near consumer
premises.
➢The feeders breaker and isolator
are part of the substation low
voltage switchgear and are
typically the metal-clad type.
Out Coming Feeder

Switching Apparatus
In Electrical power Substation switching apparatus are needed
to connect or disconnect elements of the power system to or
from other elements of the system. Switching apparatus
includes.
➢Disconnector
➢Fuses
➢Circuit Breakers

Disconnectoror Isolator
➢Adisconnecter or disconnect
switchorisolator switchis used to
ensure that an electrical circuit is
completely de-energized for
service or maintenance.
➢High-voltage isolation switches
are used in electrical substations
to allow isolation of apparatus
such ascircuit breakers,
transformer and transmission
lines, for maintenance.
➢Disconnectors can be operated
either manually or automatically.
Manually Operated
Disconnector
Automatic knee type
Disconnector

Fuses
➢afuseis an electrical safety device
that operates to provideover current
protection of an electrical circuit.
➢Its essential component is a metal wire
or strip that melts when too much
current flows through it, thereby
interrupting the current.
➢It is a sacrificial device, once a fuse
has operated it is an open circuit, and
it must be replaced or rewired,
depending on type.
➢A fuse is an automatic means of
removing power from a faulty system
often abbreviated to ADS (Automatic
Disconnection of Supply).
High Voltage Fuse

Circuit Breaker
➢Acircuit breakeris an automatically operated electrical
switch designed to protect an electrical circuit from
damage caused by over current, Fault, Short Circuit etc.
➢There are various types of circuit breakers which are
based on their operation voltage level like low voltage
circuit breakers, medium voltage circuit breakers and
high voltage circuit breakers. High voltage circuit
breakers are used in power substations.
Oil Circuit breakers (OCB)
Air blast Circuit breakers (ACB)
Gas Insulated Circuit breakers (SF6)
Vacuum Circuit Breakers (VCB)

Oil Circuit Breaker
Oil circuit breakeror
OCB is types of circuit
breakerswhereoilis
used as arc quenching
media as well as
insulating media
between current
carrying contacts and
earthed parts of
thebreaker. The oilused
here is same as
transformer
insulatingoil.
Oil Circuit Breaker

Air Blast Circuit breaker
➢This type ofcircuit breakers, is
those kind ofcircuit
breakerwhich operates inairat
atmospheric pressure
➢Air blast circuit breakerused
compressed air or gas as the arc
interrupting medium.
➢In theair blast circuit
breakercompressed air is stored
in a tank and released through a
nozzle to produce a high-velocity
jet. this is used to extinguish the
arc.
➢Air blast circuit breakersare
used for indoor services in the
medium, high voltage
Air Blast Circuit Breaker Actual Picture

Vacuum Circuit Breaker
➢A breaker in which vacuum is
used as an arc extinguish medium
is called a vacuumcircuit
breaker.
➢In this circuit breaker, the fixed
and moving contact is enclosed in
a permanently sealed vacuum
interrupter. The arc is extinguish
as the contacts are separated in
high vacuum.
➢Vacuumcircuit breakerhas a
high insulating medium for arc
extinguish as compared to the
othercircuit breaker.

SF6 Circuit Breaker
➢Acircuit breakerin which
SF
6under pressure gas is used to
extinguish the arc is called
SF
6circuit breaker. SF
6gas has
excellent dielectric, arc quenching,
chemical and other physical
properties which have proved its
superiority over other arc
quenching mediums such as oil or
air.
➢SF6 is colorless, odorless, non-
toxic, and non-inflammable gas.
➢It has high thermal conductivity
better than air and assists in better
cooling current carrying parts.
SF6 Circuit Breaker

Conductor
An
electricalconductoris a
substance in which allow
electrical charge to
move, usually electrons
move easily from atom
to atom with the
application of voltage
which is called electric
current. Copper, silver,
iron aluminum are the
example of electrical
conductor.
Conductor

Insulator
➢The material which does not allow
free movement of electrons or
electric charge is called as an
insulator.
➢Hence, insulators resist electricity with
their high resisting property.
➢Insulators are used for insulation
purpose while erectingelectric poles
with conductors to avoid short circuit
and for other insulation requirements.
➢There are different types of
insulators such as suspension type,
strain type, stray type, shackle, pin
type and so on.
Different Type of Insulators

Lightning Arrester
➢lightning arresteris a device used
on electrical power systems and
telecommunications systems to
protect the insulation and conductors
of the system from the damaging
effects oflightning.
➢The typicallightning arresterhas a
high-voltage terminal and a ground
terminal.
➢Whenever light surges occur then, a
high-voltage pass through these
electrical components causing
damage to themTherefore, to avoid
this difficulty, lightening arresters are
placed to pass the entire lightening
surges to earth.

Surge Arrester
➢Asurge arresteris a device to
protect electrical equipment from
over-voltage transients caused by
external (lightning) or internal
(switching) events.
➢Surge arrestorgives the protection
againstsurge currents or voltages in
a circuit.
➢Surgescan be produced because of
short circuit,lightning, sparking etc.
➢A surge arrestor can also be used as
a lightning arrestor but a lightning
arrestor can't be used as a surge
arrestor in case of short circuits.
Surge Arrester

Grounding
➢Grounding is an important aspect of
every substation. The function of a
grounding system is to ensure the
safety of personnel and the public,
to minimize hazard from transferred
potential, to protect equipment, to
provide a discharge path for
lightning strikes, and to provide a
low-resistance path to ground.
➢A good grounding system has a low
resistance to remote earth to
minimize the ground potential rise
➢In order to a grounding design to be
safe, it needs to provide a way to
carry the electric currents into the
ground under both normal and
faulted conditions.
Substation Grounding System

Battery Bank
➢In Substations we use battery bank to
provide anuninterrupted & reliable
power supplyto control the switch
gears & Monitor the status of Feeders
in case of power failure. and the
Operations of breakers, relays,
communication system an emergency
lights.
➢Battery banks in substation for
switchgear and control applications
are made up of many cells. These cells
are typically wired in series to
achievea desired voltage and may
also be wired in parallel to achieve
additional ampere capacity. Substation Battery Bank

Capacitor Bank
➢Normally capacitor bank is
used in distribution
Substation to control the
level of the voltage
supplied to the consumer by
reducing or eliminating the
voltage drop in the system
caused by inductive
reactive loads by improving
power factor.
Capacitor Bank

Communication System
➢Power-system automationis the
act of automatically controlling
the power system via
instrumentation and control
devices.
➢Substationautomation refers to
using data fromIntelligent
electronic devices(IED), control
and automation capabilities
within the substation, and control
commands from remote users to
control power-system devices.
Power Communication System

HVAC System
➢Substations require special
attention toventilation in order to
dissipate heat losses from
electrical equipment. Wherever
possible, Forced ventilation
should be used where natural
ventilation is not practicable
forced ventilation means fan(s)
HVAC System must be installed
➢The ventilation must be sufficient
to maintain a maximum room
temperature of 35 degrees
Celsius.
HVAC system and Equipment

Fire Fighting System
➢Substations contain components
and materials that constitute a fire
risk. And due to overheat or arcing
its cause fire causing dangerous
situation to the personnel and
property.
➢For preventing fire, fire systems
are installed in substations on the
sensitive area which give signal or
alarm in case of fire such as fire
alarm, water sprinkler, smoke
detector heat detector.
➢Not all possible fire protection
measures are necessary for every
substation
Typical fire fighting system

Facility
The substation building are
surrounded by the fence or
concrete wall to prevent the
unauthorized person or
animals to get in and have
facility of washrooms, drinking
water, parking workshop for
small maintenance work and
some distribution substation
premises have residential
compound for it’s staff as
needed.
Typical substation premises

Thank You

Presented By
Emran Ali