this presentation includes description on generator capability curve and droop control
Size: 810.74 KB
Language: en
Added: May 08, 2024
Slides: 14 pages
Slide Content
GENERATOR EXCITATION CAPABILITY CURVE DROOP CONTROL ASHWIN NARAYAN
GENERATOR AND GRID CURRENT FLOW E=V+IZ E= GEN INDUCED EMF V= GRID VOLTAGE I =CURRENT FLOW Z= TOTAL IMPEDANCE= R+L+C I E V GENERATOR GRID R L C
Phasor diagram for synchronous generator Grid voltage Field voltage Load angle Phase angle Stator current
What is the difference between phase angle and load angle PHASE ANGLE : Angle between Grid voltage and Stator current LOAD ANGLE: Angle between Excitation field voltage and Grid voltage
PHASOR DIAGRAM INTO GENERATOR CAPABILITY CURVE Phase angle. Multiplying by V/x
GENERATOR CAPABILITY CURVE VI MEGAWATT MEGAVAR LEADING PF LAGGING PF HEATING LIMITS
GENERATOR HEATING LIMITS
HERE OPERATING MW ASSUMED 240 DROOP SETTING AT +/-4% ON MAX SPEED (3000 RPM) OVERSPEED LIMIT AT 3300 RPM MW SETTING 17% OF EACH 1% SPEED DROP MW BIAS CLAMP +/-120 MW