HP LP BYPASS SYSTEM
Presented by
A S GUPTA BE,MBA,BOE,EA,IPMA-D
Supdt(O)

HP & LP BYPASSSYSTEM
Purpose
Primarily meant to enable Boiler operation independent of
the turbine
Opening o HPBP & LPBP Valves ensures minimum steam
flow through superheater & reheater tubes during start-ups,
low load operation & sudden unloading of unit
Utilized or building up of steam parameters quickly before
starting of the turbine online
Avoiding the boiler trip on Reheat protection
No steam flow through Boiler steam tubes will lead to
starvation & thereby overheating and lead to premature
failure of tubes

HP & LP BYPASSSYSTEM

HP & LP BYPASSSYSTEM
Provides the alternative path for boiler operation
HP Bypass dumps steam into CRH inlet of reheater
LP Bypass bypasses IPT & LPT and dumps steam into
condenser
The capacity of HPLP bypass is 60% of full load turbine
steam flow
Reduces chances of opening of Boiler safety valves at
raised steam pressures

REHEATPROTECTION
RH protection (delay=10 sec) will act if
TURBINE HP V/V & HPBP CLOSED [ either turbine
HP stop v/v or HP CV in both HP line closed ] & [
both HP BP <2%] OR
TURBINE IP V/V & LP BP closed [ Either IP stop
v/v or IP CV v/v in both IP line closed ] & [ Either LP
BP stop v/v or LP BP C/V in both LP line is closed]
OR
Generator ckt bkr open & [both HP BP closed OR
both LP BP closed

HP BYPASSSYSTEM
Benefits
Boiler start-up without starving superheater & reheater
tubes, till the opening of turbine steam control valves
Raising the steam parameters (press& temp) quickly, to a
level acceptable for the starting of the turbine at an optimum
rate
Continued Boiler operation while tripping of turbine provided
boiler load <60%
Avoiding Reheat protection
Conservation of DM water, during start-up or Shut down (by
dumping steam into condenser instead of atmosphere)
Maintain sufficient steam pressure in the CRH line for
auxiliary steam supply purpose during low load condition

HP BYPASSSYSTEM

HP BYPASSSYSTEM
HP Bypass consists of:
Bypass Valves BP1 & BP2
Spray water pressure controller BD valve
Spray water temp. controller BPE1, BPE2 valves
2 nos Hydraulic Oil Supply units
MS press. ahead of HPT is maintained by proper
adjustment of BP valves
Steam temp in CRH line controlled by BPE valves

OILSUPPLYUNIT
OSU provides Energy for operation of steam valves
Consists of Filters, Axial piston pump, Relief valve, NRV, Oil
Accumulator, Press reducing valve, Ball Cocks
Axial Pump maintains Contant oil press. in the accumulator
by automatic operation
Gas filled bladder to retain oil press in accumulator or fairly
long duration
A safety valve protects the system from excessive pressure

HP BP HYDRAULICSYSTEM

OILSUPPLYUNITINTERLOCKS
Pump Auto off Oil Press high >160ksc
Pump Auto on Oil Press Low <120ksc
Pump Auto off Oil Temp high >70 DegC
Pump Auto off Oil Level low <18 Lit
Alarm Oil Press too high >170ksc
Alarm Oil Press too Low <90ksc

TEMPERATURECONTROL

HP BP PROTECTION
BP Valve Priority Close Conditions
Condenser Vacuum Low (<-0.6 ksc)
Bypass Downstream Temp very high (>380 degC)
Loss of Oil Pressure in Safety System Accumulator
<100 ksc (stage-1)
Under these conditions
Steam Press Controller Switches to Manual from
Auto
spray water valve will close
This protection will override the Fast opening signal
& open push button operation

HP BP PROTECTION
HP Bypass Fast Opening Conditions
Generator Circuit Breaker Opening & Boiler on
& no priority close
Turbine Trip & Boiler on & no priority close
Turbine Load Shedding Relay Operation
HP BP Pressure Controller Deviation > 8 ksc
Pressing the Fast Opening Button

HP BP PROTECTION
BP Valve Auto Blocking Conditions
Bypass valve priority close command
BP position transmitter failed
OSU-1 & 2 Oil Pressure <90 ksc
Main steam Pressure transmitter failed

HP BP INTERLOCKS
BPE Valve Conditions
Steam Bypass Valves BP1 or BP2<2 % Auto Close
Command to ensure positive shut off
Steam Bypass Valves BP1 or BP2<2 % Spray Water
Pressure Control Valve (BD Valve) close
Steam Bypass Valves BP1 or BP2>2 % Spray Water
System (BPE1, BPE2, BD Valve) will switch over to
Auto

HP BP INTERLOCKS
BPE Valve Auto Blocking Conditions
Bypass Downstream Temp very high (>380 degC)
BP auto command blocking
BPE valve position transmitter failed
BPE Temp transmitter deviation high
Therefore, it is necessary to make proper set
values for Spray Water Header Pressure &
HP BP downstream temperature before
operating the Steam Bypass Valves

LP BYPASS
Functions of LP Bypass System are:
Maintaining minimum Steam Flow through Re-heater
Maintaining desired Steam Pressure in the Re-heater
Providing an alternative path for dumping the steam (not
accepted by the IP & LP Turbines) into the condenser
LP BP System comprises of :
Steam Pressure Control Loop
Valve Position Control Loop
Automatic Control Interface (ACI)
Condenser Temperature Protection
Tracking Unit

LP BYPASS

LP BYPASS

LP BYPASS

LP BYPASS

LP BYPASS

LP BYPASSCONTROLLOGIC

SLIDINGSETPOINT

LP BYPASS SETPOINTS

AUTOMATICCONTROLINTERFACE

LP BYPASSEHC

LP BYPASSPROTECTIONS
Close LP Bypass under following conditions:
Condenser Vacuum Low (<-0.6 ksc)
Spray Water Pressure Low (<8 ksc)
Condenser Wall Temperature High ( > 90 DegC)
LPBP Down Steam Pressure High (>19 ksc)
Spray Water valve open command at Steam pressure before
bypass valve >6.8 ksc

LP BYPASSPROTECTIONS