BLT 122 BUILDING TECHNOLOGY II AR. RONNEL CARLOS T. RAMOS Course Facilitator UNIVERSITY OF NORTHERN PHILIPPINES College of Architecture
COURSE OUTLINE BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS MODULE 01 – BASIC WORKING DRAWINGS AND GRAPHICAL PRESENTATION TECHNIQUES MODULE 02 – REFLECTED CEILING PLANS AND DETAILS MODULE 03 – SCHEDULE OF DOORS AND WINDOWS MODULE 04 – SCHEDULE OF FINISHES MODULE 05 – KITCHEN AND T&B DETAILS MODULE 06 – STAIR DETAILS MODULE 07 – STRUCTURAL AND CIVIL WORK DRAWINGS MODULE 08 – PLUMBING AND SANITARY DRAWINGS MODULE 09 – ELECTRICAL AND AUXILIARY DRAWINGS
MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS 7.A. ELECTRICAL NOTES, LEGENDS & SYMBOLS, ELECTRICAL WIRING, CONDUIT AND ACCESSORIES 7.B. ELECTRICAL, POWER AND AUXILIARY LAYOUTS 7.C. LOAD COMPUTATION AND SCHEDULE, SINGLE LINE DIAGRAM AND RISER DIAGRAM BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
What is an ELECTRICAL PLAN? It is a type of technical drawing that delivers visual representation and describes circuits and electrical systems. It consists of symbols and lines that showcase the engineer's electrical design to its clients. BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS Also referred as “Electrical Drawing” or “ Wiring Diagram” . Composed of Lighting and Power Layouts and other electrical specifications.
What is an AUXILIARY PLAN? These are components related with Security Systems, Comfort Systems, Lighting Systems and Information Systems witch are very important to help the main system to perform according the specifications. BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS Provides supplementary or additional help and support to the basic systems of a building Composed of Electronic and Communications systems. PABX – Private Automatic Branch Exchange Also referred as “telephone system”, these are switchboards that connect to several devices.
ELECTRICAL NOTES REFERENCE: PHILIPPINE ELECTRICAL CODE (PEC) Parts 1 & 2, 2017 Edition Based from the 2017 National Electrical Code of USA. (NFPA 70, NEC) Regularly revised every three(3) years to reflect the evolution of products, materials, and installation techniques. The primary objective of the code is to establish basic materials quality and electrical works standards for the safe use of electricity for light, heat, power, communications, signaling and for other purposes. BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
LEGEND AND SYMBOLS BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
POWER SERVICE ENTRANCE Also referred to as “service drop” It is where the wires connected to the load side of the meter enter the house or building. BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
KILOWATT HOUR (Kwh) METER These are compact electronic monitoring devices that measure the consumed energy flowing through a circuit such as a standard 120V or 240V BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
ELECTRICAL PANELBOARD Also called, “distribution board”, “breaker panel” or “electric panel”. It is a component of an electricity supply system that divides an electrical power feed into subsidiary circuits while providing a protective fuse or circuit breaker for each circuit in a common enclosure. BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
CIRCUIT BREAKER It is an automatically operated electrical switch designed to protect an electrical circuit from damage caused by excess current from an overload or short circuit. Its basic function is to interrupt current flow after a fault is detected. CIRCUIT HOMERUN A home run is a wire that graphically represents the wiring of a circuit to a central location that acts as the distribution point for the power, typically, a panel. BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
GROUND ROD / GROUND CLAMP Also known as grounding electrodes. Used to connect the grounding system of electrical systems to earth ground. They are very good conductors of electricity and allow any dangerous electricity to flow to ground, taking the danger away from you and the electrical panel. BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
PULL BOX FOR TELEPHONE AND CATV They are used along with conduit to simplify wiring installation. They provide a way to pull conductors at long distances without placing excessive strain on the wire or insulation. BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
SWITCHES They are used to turn electrical current on or off for nearly any electrical device. BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
CONVENIENCE OUTLETS A receptacle in a wall or baseboard for connection to lamps or other electrical appliances. BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
ELECTRICAL WIRING THHN AND THWN THW TW BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS THERMOPLASTIC HIGH HEAT-RESISTANT NYLON COATED (THHN) & THERMOPLASTIC WATER-RESISTANT NYLON COATED (THWN) Suitable for wet or dry locations at temperatures not to exceed 90 degrees Celsius or at 75 degrees Celsius when exposed to oil and gasoline
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS THERMOPLASTIC HEAT AND WATER RESISTANT INSULATED WIRE (THW) It is a solid or stranded, soft annealed copper conductor insulated with Polyvinylchloride (PVC). Maximum conductor temperature does not exceed 75 degrees Celsius, 600V
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS THERMOPLASTIC HEAT AND WATER RESISTANT INSULATED WIRE (TW) It is a solid or stranded, soft annealed copper conductor insulated with Polyvinylchloride (PVC). Maximum conductor temperature does not exceed 60 degrees Celsius, 600V
BASIC ELECTRICAL CONDUITS RIGID METAL CONDUIT (RMC) RIGID POLYVINYL CHLORIDE (PVC) FLEXIBLE POLYVINYL CHLORIDE (PVC) BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS RIGID METAL CONDUIT (RMC) For outdoor applications
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS RIGID POLYVINYL CHLORIDE (PVC) Used in corrosive environments For outdoor and indoor uses, typically in walls and slabs
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS FLEXIBLE POLYVINYL CHLORIDE (PVC) Used in corrosive environments For indoor uses, typically in ceilings and slabs
ELECTRICAL FITTINGS REFER TO ATTACHED PDF BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS LIGHTING LAYOUT SCALE 1:100M GRIDLINES DIMENSIONS (General and Grid to Grid) REFER TO RCP FOR CEILING DESIGN AND LIGHTING FIXTURE ARRANGEMENT WITH FIXTURE AND FURNITURE (hidden lines) LIGHTS AND SWITCH CONNECTIONS CIRCUIT HOMERUNS LIGHTING FIXTURE LABELS (alphabets-small caps, same letter for lights with one switch) SWITCH LABELS
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS LIGHTING LAYOUT
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS POWER LAYOUT SCALE 1:100M GRIDLINES DIMENSIONS (General and Grid to Grid) WITH FIXTURE AND FURNITURE (hidden lines) CONVENIENCE OUTLETS WITH PROPER DESIGNATIONS SERVICE ENTRANCE, KILOWATT HOUR METER AND PANEL BOARD LOCATIONS CONVENIENCE OUTLET CONNECTIONS CIRCUIT HOMERUNS (single circuit for REFRIGERATOR and AIRCONDITIONING UNITS)
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS POWER LAYOUT
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS AUXILIARY LAYOUT SCALE 1:100M GRIDLINES DIMENSIONS (General and Grid to Grid) WITH FIXTURE AND FURNITURE (hidden lines) TELEPHONE and CATV OUTLETS CCTV (if any) PULL BOX (TELEPHONE and CATV) and DVR LOCATIONS DOORBELL AND BUZZER LOCATIONS OUTLET CONNECTIONS
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS AUXILIARY LAYOUT
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS LOAD COMPUTATION AND SCHEDULE
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS LOAD COMPUTATION AND SCHEDULE WATTS PER OUTLET: LIGHTING OUTLET = 100W CONVENIENCE OUTLET = 180W CONVENIENCE OUTLET (REF) = 1000W CONVENIENCE OUTLET (1hp, ACU) = 1840W Note: 1hp = 18 to 22sqm FORMULAS: NO. OF OUTLETS PER CIRCUIT X WATTS PER OUTLET = WATTS PER CIRCUIT WATTS PER CIRCUIT / 230V = AMPERE LOAD TOTAL AMPERE LOAD X 0.80 = DEMAND FACTOR @ 80% DEMAND FACTOR X 1.20 = LOAD GROWTH @ 20%
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS ELECTRICIAN’S GUIDE TABLE
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS SINGLE LINE DIAGRAM Shows a correct power distribution path from the incoming power source to each downstream load – including the ratings and sizes of each piece of electrical equipment, their circuit conductors, and their protective devices. NOT TO SCALE REPLICATE DRAWING but indicate correct ampere trip, wire and conduit sizes as per the LOAD COMPUTATION AND SCHEDULE
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS RISER DIAGRAM Two-dimensional representation in a vertical plane the distribution components of an electrical system such as bus risers, bus plugs, panel boards, and transformers from the point of entry up to the small branch circuits on each level. NOT TO SCALE REPLICATE DRAWING but indicate correct ampere trip and circuit loads as per the LOAD COMPUTATION AND SCHEDULE
BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS VICINITY MAP For reference of the concerned electric company on the exact location of electrical tapping points. NOT TO SCALE REPLICATE VICINITY MAP in the FRONT PAGE
END OF MODULE 09 BLT - BUILDING TECHNOLOGY II MODULE 09 ELECTRICAL AND AUXILIARY DRAWINGS