CLIENT -
CONSULTANT -
CONTRACTOR -
PROJECT:
PACKAGE-II :
DOC. NAME : DESIGN CALCULATION SHEET FOR LT POWER CABLE
DOCUMENT NO. - REV-05
From
Equipment Tag
 
No.
To
Equipment Tag 
No.
Motor/Eq
uipment 
Voltage 
Rating  
   
(V)
For 45 
Deg amb.
Cable laid 
on tray 
exposed to 
air
Cables laid 
inside 
concrete 
trench
Over­all
 
Rating 
Factor
Derated 
current 
rating of 
cable
No. of run 
required of
 
selected 
cable size
Selected No. 
of run
Net Current 
Provided
Starting 
PF of 
Motor
Running 
PF of 
Motor
Resistance 
at 90deg .C
  
( R )
Reactance 
at 50Hz  
   
( XL )
Starting 
Impedance 
Ohms/Km
   
Z
start
Running 
Impedance 
Ohms/Km    
Z
run
Starting 
Vdrop in 
volts   
   
V
start
Running 
Vdrop in 
volts   
   
V
run
Ground Air
Avg.of air & 
ground 
rating
Cable 
Length  Per
 
Run (m)
Deration factor
Full Load 
Current in 
Amp (I
fc
)
Motor 
Efficiency 
No of 
Core 
  
Installed 
Output 
Power 
   
(kW 
rated)
Cable 
Type
Selected 
Cable Size 
Voltage Drop Calculation Feeder Description                                                            
   
Feeder Description                                                
   
CABLES FEED FROM SS 1 SUBSTATION
Current rating Of cable 
Selected
Sr.No.
Drive 
Type
Plant Area
1 VVVFCONVERTER TRANSFORMER­3TR‐3723­VVF PANELVF723
2 VVVFCONVERTER TRANSFORMER­4TR‐4723­VVF PANELVF723
3 VVVF
CONVEYOR‐DHC‐723 VVF PANEL AT FIRST FLOOR OF 
SS‐1
VF723 DOWN HILL CONVEYOR‐DHC‐723 MOTOR‐1 AT TAIL DRIVE HOUSE M1_723 800 0.95 690 840 0.95 0.68 ‐ 0.65 3300A2XFY ‐ 455 455 295.75 2.843887.25 150 ‐ 0.85 0.13 0.07 0 0.15 0.00 10.62
3A VVVF
CONVEYOR‐DHC‐723 VVF PANEL AT FIRST FLOOR OF 
SS‐1 ‐ DRIVE PANEL BODY EARTH 
VF723
DOWN HILL CONVEYOR‐DHC‐723 MOTOR‐1 AT TAIL DRIVE HOUSE

FROM DRIVE PANEL EARTH TO MOTOR BODY EARTH
PE_723_M1 8003150A2XFY1150
4 VVVF
CONVEYOR‐DHC‐723 VVF PANEL AT FIRST FLOOR OF 
SS‐1
VF723 DOWN HILL CONVEYOR‐DHC‐723 MOTOR‐1 AT TAIL DRIVE HOUSE M2_723 800 0.95 690 840 0.95 0.68 ‐ 0.65 3300A2XFY ‐ 455 455 295.75 2.843887.25 150 ‐ 0.85 0.13 0.07 0 0.15 0.00 10.62
4A VVVF
CONVEYOR‐DHC‐723 VVF PANEL AT FIRST FLOOR OF 
SS‐1‐DRIVE PANEL BODY EARTH 
VF723
DOWN HILL CONVEYOR‐DHC‐723 MOTOR‐2 AT TAIL DRIVE HOUSE 
‐FROM DRIVE PANEL EARTH TO MOTOR BODY EARTH
PE_723_M2 8003150A2XFY1150
5 VVVF
CONVEYOR‐DHC‐723 VVF PANEL AT GROUND FLOOR 
OF SS‐1
VF723 BREAKING RESISTER‐1 AT GROUND FLOOR OF SS‐1 BR1_723 400 ‐ 980 ‐‐ ‐ ‐ ‐ ‐ ‐ ‐ 1 0.00 40 ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐
6 VVVF
CONVEYOR‐DHC‐723 VVF PANEL AT GROUND FLOOR 
OF SS‐1
VF723 BREAKING RESISTER‐2 AT GROUND FLOOR OF SS‐1 BR2_723 400 ‐ 980 ‐‐ ‐ ‐ ‐ ‐ ‐ ‐ 1 0.00 40 ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐
7 VVVF
CONVEYOR‐DHC‐723 VVF PANEL AT GROUND FLOOR 
OF SS‐1
VF723 BREAKING RESISTER‐3 AT GROUND FLOOR OF SS‐1 BR3_723 400 ‐ 980 ‐‐ ‐ ‐ ‐ ‐ ‐ ‐ 1 0.00 40 ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐
BUSDUCT­3
Copper 
3C X 120Sqmm
3C X 120Sqmm
3C X 120Sqmm
DOWN HILL CONV ‐ 723
CONVEYOR­DHC­723 VVF PANEL AT SS­1
BUSDUCT­2
SUBSTATION (SS‐1)
DOWN HILL CONV ‐ 723
DOWN HILL CONV ‐ 723
DOWN HILL CONV ‐ 723
DOWN HILL CONV ‐ 723
CABLES FEED FROM SS
-
1 SUBSTATION
SUBSTATION (SS‐1)
DOWN HILL CONV ‐ 723
DOWN HILL CONV ‐ 723
8 VVVF
CONVEYOR‐DHC‐723 VVF PANEL AT GROUND FLOOR 
OF SS‐1
VF723 BREAKING RESISTER‐4 AT GROUND FLOOR OF SS‐1 BR4_723 400 ‐ 980 ‐‐ ‐ ‐ ‐ ‐ ‐ ‐ 1 0.00 40 ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐
1PMCCDISTRIBUTION TRANSFORMER­1TR­1 415V POWER MOTOR CONTROL CENTRE SS1_PMCC
2 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC POWER SUPPLY TO UPS SYSTEM PANEL UPS‐1 15 1 415 26.1 0.95 ‐ 0.76 0.65 4 10 2XWY 57 ‐ 37.05 1 37.05 30 ‐ 0.80 3.94 0.08 0 3.20 0.00 4.34
3 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC GEAR BOX FOR DOWNHILL HILL CONVEYOR‐723‐M1  GB_723_M1 1.5 ‐ 415 2.6 0.95 0.68 ‐ 0.65 4 4 2XWY ‐ 36 23.26 1 23.26 150 ‐ 0.80 9.48 0.09 0 7.64 0.00 5.18
4 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC GEAR BOX FOR DOWNHILL HILL CONVEYOR‐723‐M2  GB_723_M2 1.5 ‐ 415 2.6 0.95 0.68 ‐ 0.65 4 4 2XWY ‐ 36 23.26 1 23.26 150 ‐ 0.80 9.48 0.09 0 7.64 0.00 5.18
5 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC HYD.POWER PACK BRAKE SYSTEM FOR CONV.723M1 HPP_723M1 4 ‐ 415 7.0 0.95 0.68 ‐ 0.65 4 10 2XWY ‐ 62 40.05 1 40.05 150 ‐ 0.80 3.94 0.08 0 3.20 0.00 5.79
6 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC HYD.POWER PACK BRAKE SYSTEM FOR CONV.723M2 HPP_723M2 4 ‐ 415 7.0 0.95 0.68 ‐ 0.65 4 10 2XWY ‐ 62 40.05 1 40.05 150 ‐ 0.80 3.94 0.08 0 3.20 0.00 5.79
7 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC POWER SUPPLY  TO BATT. CHARG.PANEL INCOMER‐1 BC1 20 ‐ 415 34.8 0.95 ‐ 0.76 0.65 4 25 A2XFY 94 ‐ 61.10 1 61.10 30 ‐ 0.80 1.54 0.08 0 1.28 0.00 2.31
8 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC POWER SUPPLY  TO BATT. CHARG.PANEL INCOMER‐2 BC2 20 ‐ 415 34.8 0.95 ‐ 0.76 0.65 4 25 A2XFY 94 ‐ 61.10 1 61.10 30 ‐ 0.80 1.54 0.08 0 1.28 0.00 2.31
9 DOL SS‐1 SUBSTATION ‐ PMCC SS1_PMCC SIREN AT TH‐2 HTR_TH2 0.375 0.63415 1.0 0.95 0.68 ‐ 0.65 4 2.5 2XWY 34 ‐ 21.96 1 21.96 80 0.40 0.80 15.50 0.10 6.29 12.46 6.47 1.78
10 DOL SS‐1 SUBSTATION ‐ PMCC SS1_PMCC SIREN AT TH‐2A HTR_TH2A 0.375 0.63 415 1.0 0.95 0.68 ‐ 0.65 4 2.5 2XWY ‐ 30 19.38 1 19.38 110 0.40 0.80 15.50 0.10 6.29 12.46 8.89 2.45
11 DOL SS‐1 SUBSTATION ‐ PMCC SS1_PMCC SIREN‐1 AT TAIL HOUSE DHC‐723 HTR1_DHC723 0.375 0.63 415 1.0 0.95 0.68 ‐ 0.65 4 2.5 2XWY ‐ 30 19.38 1 19.38 150 0.40 0.80 15.50 0.10 6.29 12.46 12.12 3.33
12 DOL SS‐1 SUBSTATION ‐ PMCC SS1_PMCC SIREN‐2 AT TAIL HOUSE DHC‐723 HTR2_DHC723 0.375 0.63 415 1.0 0.95 0.68 ‐ 0.65 4 2.5 2XWY ‐ 30 19.38 1 19.38 150 0.40 0.80 15.50 0.10 6.29 12.46 12.12 3.33
13
DOL
SS 1 SUBSTATION PMCC
SS1 PMCC
BELT CONVEYOR MOTOR 718 AT TH 1
M 718
45
092
415
85 1
095
068
065
35
95
A2XFY
221
142 77
2
285 53
350
030
080
041
007
019
037
35 65
958
SUBSTATION (SS‐1)
SUBSTATION (SS‐1)
TRANSFER HOUSE‐2
TAIL DRIVE HOUSE
TAIL DRIVE HOUSE
SUBSTATION (SS‐1)
SUBSTATION (SS‐1)
3C X 120Sqmm
BUSDUCT­1
SS­1 SUBSTATION ­ PMCC
DOWN HILL CONV ‐ 723
TRANSFER HOUSE‐2A
TAIL DRIVE HOUSE
TAIL DRIVE HOUSE
TAIL DRIVE HOUSE
TAIL DRIVE HOUSE
TRANSFER HOUSE 1
13
DOL
SS

1
 SUBSTATION
 ‐ 
PMCC
SS1
_
PMCC
BELT
 CONVEYOR
 MOTOR
 ‐
718
 AT
 TH

1
M
_
718
45
0
.92
415
85
.1
0
.95
0
.68

0
.65
3
.5
95
A2XFY

221
142
.77
2
285
.53
350
0
.30
0
.80
0
.41
0
.07
0
.19
0
.37
35
.65
9
.58
14 MCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC SPACE HEATER FOR CONV‐718 (SPH‐718) SPH_718 0.4 ‐ 415 0.7 0.95 0.68 ‐ 0.65 3 4 2XWY ‐ 36 23.26 1 23.26 350 ‐ 0.80 9.48 0.09 0 7.64 0.00 3.22
15 DOL SS‐1 SUBSTATION ‐ PMCC SS1_PMCC BELT CONVEYOR MOTOR ‐719 AT SILO TOP M_719 90 0.94 415 166.5 0.95 0.68 ‐ 0.65 3.5 95 A2XFY196‐ 126.62 2 253.23 120 0.30 0.80 0.41 0.07 0.19 0.37 23.93 6.43
16 MCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC SPACE HEATER FOR CONV‐719 (SPH‐719) SPH_719 0.4 ‐ 415 0.7 0.95 0.68 ‐ 0.65 3 4 2XWY ‐ 36 23.26 1 23.26 120 ‐ 0.80 9.48 0.09 0 7.64 0.00 1.10
17 DOL SS‐1 SUBSTATION ‐ PMCC SS1_PMCC SIREN AT TH‐1 HTR‐TH1 0.375 0.63 415 1.0 0.95 0.68 ‐ 0.65 4 2.5 2XWY ‐ 30 19.38 1 19.38 350 0.40 0.80 15.50 0.10 6.29 12.46 28.28 7.78
18 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC BELT WEIGH SCALE ‐ LCP (721B ) AT CONV.‐721 CP_721B 0.5 ‐ 415 0.9 0.95 0.68 ‐ 0.65 4 2.5 2XWY ‐ 30 19.38 119.38 150 ‐ 0.80 15.50 0.10 0 12.46 0.00 2.81
19 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC METAL DETECTOR MD‐719A AT CONV.719 MD‐719A 0.5 ‐ 415 0.9 0.95 0.68 ‐ 0.65 4 4 2XWY ‐ 36 23.26 1 23.26 250 ‐ 0.80 9.48 0.09 0 7.64 0.00 2.88
20 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC METAL DETECTOR MD‐721A AT CONV.721 MD‐721A 0.5 ‐ 415 0.9 0.95 0.68 ‐ 0.65 4 4 2XWY ‐ 36 23.26 1 23.26 150 ‐ 0.80 9.48 0.09 0 7.64 0.00 1.73
21 DOL SS‐1 SUBSTATION ‐ PMCC SS1_PMCC ILMS‐718A AT TH‐1 CP‐718A 16.46 ‐ 415 28.6 0.95 0.68 ‐ 0.65 3.5 70 A2XFY ‐ 179 115.63 1 115.63 350 ‐ 0.80 0.57 0.07 0 0.50 0.00 8.64
22 DOL SS‐1 SUBSTATION ‐ PMCC SS1_PMCC ILMS‐720A AT TH‐2 CP‐720A 18.46 ‐ 415 32.1 0.95 0.68 ‐ 0.65 3.5 35 A2XFY 113 ‐ 73.00 1 73.00 150 ‐ 0.80 1.11 0.080 0.93 0.00 7.80
23 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC BELT WEIGH SCALE ‐ LCP (718C ) AT CONV.‐718 CP_718C 0.5 ‐ 415 0.9 0.95 0.68 ‐ 0.65 4 2.5 2XWY ‐ 30 19.38 119.38 325 ‐ 0.80 15.50 0.10 0 12.46 0.00 6.10
24 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC 15T DOUBLE GRIDER EOT CRANE AT TAIL DRIVE  722 25 ‐ 415 43.5 0.95 0.68 ‐ 0.65 3.5 50 A2XFY ‐ 142 91.73 1 91.73 150 0.40 0.80 0.82 0.08 0.40 0.70 32.26 7.92
25 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC 5T‐UNDER SLUNG EOT LP ‐723A AT PS‐1 EH‐723A 6 ‐ 415 10.4 0.95 0.68 ‐ 0.65 4 6 2XWY ‐ 47 30.36 1 30.36 125 0.40 0.80 5.90 0.09 2.44 4.77 39.70 10.78
26 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC 2T‐ELECT.HOIST LP (EH‐721C‐1) AT TH‐2A EH‐721C_1 3 ‐ 415 5.2 0.95 0.68 ‐ 0.65 4 6 2XWY ‐ 47 30.36 1 30.36 150 0.40 0.80 5.90 0.09 2.44 4.77 23.82 6.47
27 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC 15T‐ELCT.HOIST LP  (EH‐718B‐2) AT TH‐1 EH‐718B_2 19 ‐ 415 33.0 0.95 0.68 ‐ 0.65 3.5 70 A2XFY ‐ 179 115.631 115.63 350 0.40 0.80 0.57 0.07 0.29 0.50 42.49 9.97
28 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC 2T‐ELECT.HOIST LP (EH‐718B‐1) AT TH‐1 EH‐718B_1 3 ‐ 415 5.2 0.95 0.68 ‐ 0.65 4 10 2XWY ‐ 62 40.05 1 40.05 350 0.40 0.80 3.94 0.08 1.65 3.20 37.63 10.13
29 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC 25T‐ELECT HOIST LP (EH‐720B) AT TH‐2 EH‐720B 26 ‐ 415 45.2 0.95 0.68 ‐ 0.65 3.5 50 A2XFY 133 ‐ 85.92 1 85.92 100 0.40 0.80 0.82 0.08 0.40 0.70 22.37 5.49
30 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC 2T‐ELECT.HOIST (EH‐719B) AT SILO BLDG EH‐719B 3 ‐ 415 5.2 0.95 0.68 ‐ 0.65 4 6 2XWY ‐ 47 30.36 1 30.36 150 0.40 0.80 5.90 0.09 2.44 4.77 23.82 6.47
TAIL DRIVE HOUSE
TRANSFER HOUSE‐2
CONV.‐718
CONV.‐719
CONV.‐721
TRANSFER HOUSE‐1
TRANSFER HOUSE‐1
PARKING STATION‐1
TRANSFER HOUSE‐2A
TRANSFER HOUSE‐1
TRANSFER HOUSE‐2
CONV.‐721
SILO TOP FLOOR
SILO BLDG
TRANSFER HOUSE‐1
SILO TOP FLOOR
TRANSFER HOUSE‐1
TRANSFER
 HOUSE

1
DESIGN CALCULATION SHEET FOR LT POW ER CABLEDOC. NO.- EL00009, REV.-041 OF 12

From
Equipment Tag
 
No.
To
Equipment Tag 
No.
Motor/Eq
uipment 
Voltage 
Rating  
   
(V)
For 45 
Deg amb.
Cable laid 
on tray 
exposed to 
air
Cables laid 
inside 
concrete 
trench
Over­all
 
Rating 
Factor
Derated 
current 
rating of 
cable
No. of run 
required of
 
selected 
cable size
Selected No. 
of run
Net Current 
Provided
Starting 
PF of 
Motor
Running 
PF of 
Motor
Resistance 
at 90deg .C
  
( R )
Reactance 
at 50Hz  
   
( XL )
Starting 
Impedance 
Ohms/Km
   
Z
start
Running 
Impedance 
Ohms/Km    
Z
run
Starting 
Vdrop in 
volts   
   
V
start
Running 
Vdrop in 
volts   
   
V
run
Avg.of air & 
ground 
rating
Cable 
Length  Per
 
Run (m)
Deration factor
Full Load 
Current in 
Amp (I
fc
)
Motor 
Efficiency 
No of 
Core 
  
Installed 
Output 
Power 
   
(kW 
rated)
Cable 
Type
Selected 
Cable Size 
Voltage Drop Calculation Feeder Description                                                            
   
Feeder Description                                                
   
Current rating Of cable 
Selected
Sr.No.
Drive 
Type
Plant Area
31 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC 1T‐ELECT.HOIST LP (EH‐719B‐3) AT SILO BLDG EH‐719B‐3 2 ‐ 415 3.5 0.95 0.68 ‐ 0.65 4 6 2XWY ‐ 47 30.36 1 30.36 125 0.40 0.80 5.90 0.09 2.44 4.77 13.23 3.59
32 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC
5T ELECT HOIST LP @TAIL DRIVE HOUSE OF DHC CRANE 
MAINTANCE
EOT‐722A 8 ‐ 415 13.9 0.95 0.68 ‐ 0.65 4 16 A2XFY ‐ 79 51.03 1 51.03 175 0.40 0.802.44 0.08 1.05 2.00 31.88 8.44
33 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC DFDS‐1 BOARD AT PUMP HOUSE‐1 DFDS1 75 ‐ 415 130.4 0.95 0.68 ‐ 0.65 3.5 150 A2XFY ‐ 292 188.63 2 377.26 300 ‐ 0.80 0.26 0.07 0 0.25 0.00 8.61
34 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC A/C & VENTILLATION PANEL AT SS‐1 ACVMCC 66 ‐ 415 114.8 0.95 ‐ 0.76 0.65 3.595A2XFY 196 ‐127.401 127.40 30 ‐ 0.80 0.41 0.07 0 0.37 0.00 2.22
35 MCCB SS‐1 SUBSTATION ‐ PMCC SS1_PMCC WELDING TRANSFORMER‐9 AT SS‐1 TR9128‐ 415 222.6 0.95 ‐ 0.76 0.65 3.595A2XFY 196 ‐ 127.402254.80 30 ‐ 0.80 0.41 0.07 0 0.37 0.00 2.15
36 MCCB SS‐1 SUBSTATION ‐ PMCC PMCC POWER SUPPLY TO BELT CONVEYOR‐721 VVVF PANEL AT SS‐1 VF721 11 ‐ 415 19.1 0.95 ‐ 0.76 0.65 4 10 2XWY 57 ‐ 37.05 1 37.05 30 ‐ 0.80 3.94 0.08 0 3.20 0.00 3.18
37 VVVF BELT CONVEYOR‐721 VVVF PANEL AT SS‐1 VF721 BELT CONVEYOR‐721 MOTOR AT TH‐2A M_721 11 0.86 415 22.2 0.95 0.68 ‐ 0.65 4 25 A2XFY ‐ 108 69.77 1 69.77 150 0.30 0.80 1.54 0.08 0.54 1.28 22.42 7.40
38
MCCB
SS

1SUBSTATION

PMCC
SS1 PMCC
POWER SUPPLY TO BELT FEEDER BF

720 VVVF PANEL AT SS

1
VF720
45

415
78.3
0.95

0.76
0.65
3.5
70
A2XFY
164

106.60
1
106.60
30

0.80
0.57
0.07
0
0.50
0.00
2.02
TAIL HOUSE DHC
SUBSTATION (SS‐1)
SUBSTATION (SS‐1)
SUBSTATION (SS‐1)
SILO BLDG
TRANSFER HOUSE‐2A
TRANSFER HOUSE‐1
SUBSTATION (SS

1)
38
MCCB
SS 1
 SUBSTATION
  
PMCC
SS1
_
PMCC
POWER
 SUPPLY
 TO
 BELT
 FEEDER
 BF 720
 VVVF
 PANEL
 AT
 SS 1
VF720
45
415
78.3
0.95
0.76
0.65
3.5
70
A2XFY
164
106.60
1
106.60
30
0.80
0.57
0.07
0
0.50
0.00
2.02
39 VVVF BELT FEEDER BF‐720 VVVF PANEL AT SS‐1 VF720 BELT FEEDER BF‐720 MOTOR AT TH‐2 M_720 45 0.92 415 85.1 0.95 0.68 ‐ 0.65 3.5 70 A2XFY 164 ‐ 105.94 1 105.94 100 0.30 0.80 0.57 0.07 0.24 0.50 25.53 7.34
40 DOL BELT FEEDER BF‐720 VVVF PANEL AT SS‐1 VF720 BELT FEEDER BF‐720 THRUSTER BRAKE AT TH‐2 THB_720 0.5 ‐ 415 0.9 0.95 0.68 ‐ 0.65 4 4 2XWY 43‐ 27.78 1 27.78 100 ‐ 0.80 9.48 0.09 0 7.64 0.00 1.15
41 MCB BELT FEEDER BF‐720 VVVF PANEL AT SS‐1 VF720 SPACE HETARE FOR BF‐720  AT TH‐2 SPH‐720 0.4 ‐ 415 0.7 0.95 0.68 ‐ 0.65 3 4 2XWY 43 ‐ 27.78 1 27.78 100 ‐ 0.80 9.48 0.09 0 7.64 0.00 0.92
42 DOL SS‐1 SUBSTATION ‐ PMCC PMCC AUXILARY DISTRIBUTION BOARD AT SS‐1 APDB15‐ 415 26.1 0.95 ‐ . 0.65 4 10 2XWY 57 ‐ 37.05 1 37.05 30 ‐ 0.80 3.94 0.08 0 3.20 0.004.34
43 MCCB SS‐1 SUBSTATION ‐ PMCC PMCC BELT VULCANIZING AT TAIL DRVE HOUSE BVM_TDH 45.54 ‐ 415 79.2 0.95 ‐ . 0.65 3.5 70 A2XFY 164 ‐ 106.60 1 106.60 150 ‐ 0.80 0.57 0.07 0 0.50 0.00 10.25
1 DOL DFDS‐1 BOARD AT PUMP HOUSE‐1 DFDS1 DFDS1‐PUMP‐1 AT PUMP HOUSE‐1(W) PM1 1.1 0.73 415 1.9 0.95 ‐ 0.76 0.65 4 4 2XWY 43 ‐ 27.95 1 27.95 40 0.40 0.80 9.48 0.09 3.88 7.64 3.70 1.01
2 DOL DFDS‐1 BOARD AT PUMP HOUSE‐1 DFDS1 DFDS1‐PUMP‐2 AT PUMP HOUSE‐1(S) PM2 1.1 0.73 415 1.9 0.95 ‐ 0.76 0.65 4 4 2XWY 43 ‐ 27.95 1 27.95 40 0.40 0.80 9.48 0.09 3.88 7.64 3.70 1.01
3 DOL DFDS‐1 BOARD AT PUMP HOUSE‐1 DFDS1 SW1‐PUMP‐1 AT PUMP HOUSE‐1(W) SW1_PM1 7.5 0.88 415 13.0 0.95 ‐ 0.76 0.65 4 4 2XWY 43 ‐ 27.95 1 27.95 40 0.400.80 9.48 0.09 3.88 7.64 25.22 6.90
4 DOL DFDS‐1 BOARD AT PUMP HOUSE‐1 DFDS1 SW1‐PUMP‐2 AT PUMP HOUSE‐1(S) SW1_PM2 7.5 0.88 415 13.0 0.95 ‐ 0.76 0.65 4 4 2XWY 43 ‐ 27.95 1 27.95 40 0.400.80 9.48 0.09 3.88 7.64 25.22 6.90
5 DOL DFDS‐1 BOARD AT PUMP HOUSE‐1 DFDS1 DW1‐PUMP‐1 AT PUMP HOUSE‐1(W) DW1_PM1 3.7 0.84 415 6.4 0.95 ‐ 0.76 0.65 4 4 2XWY 43 ‐ 27.95 1 27.95 40 0.40 0.80 9.48 0.09 3.88 7.64 12.44 3.41
6 DOL DFDS‐1 BOARD AT PUMP HOUSE‐1 DFDS1 DW1‐PUMP‐2 AT PUMP HOUSE‐1(S) DW1_PM2 3.7 0.84 415 6.4 0.95 ‐ 0.76 0.65 4 4 2XWY 43 ‐ 27.95 1 27.95 40 0.40 0.80 9.48 0.09 3.88 7.64 12.44 3.41
7 DOL DFDS‐1 BOARD AT PUMP HOUSE‐1 DFDS1 COMPRESSOR‐1 AT PUMP HOUSE‐1 (W) CP1 90 0.95 415 156.5 0.95 ‐ 0.76 0.65 3.5150A2XFY 249 ‐ 161.85 1 161.85 40 0.40 0.80 0.26 0.07 0.17 0.25 13.37 2.76
8 DOL DFDS‐1 BOARD AT PUMP HOUSE‐1 DFDS1 COMPRESSOR‐2  AT PUMP HOUSE‐1 (S) CP2 90 0.95 415 156.5 0.95 ‐ 0.76 0.65 3.5150A2XFY 249 ‐ 161.85 1 161.85 40 0.40 0.80 0.26 0.07 0.17 0.25 13.37 2.76
PUMP HOUSE­1 DFDS1 DISTRIBUTION BOARD
PUMP HOUSE‐1 DFDS1
PUMP HOUSE‐1 DFDS1
PUMP HOUSE‐1 DFDS1
PUMP HOUSE‐1 DFDS1
SUBSTATION (SS‐1)
TRANSFER HOUSE‐2
TRANSFER HOUSE‐2
SUBSTATION (SS‐1)
PUMP HOUSE‐1 DFDS1
PUMP HOUSE‐1 DFDS1
SUBSTATION
 (SS 1)
TRANSFER HOUSE‐2
PUMP HOUSE‐1 DFDS1
PUMP HOUSE‐1 DFDS1
9 DOL DFDS‐1 BOARD AT PUMP HOUSE‐1 DFDS1 EXAUST FAN ‐1 AT PUMP HOUSE‐1(W) EXF1 0.25 0.63 415 0.4 0.95 ‐ 0.76 0.65 4 4 2XWY 43 ‐ 27.95 1 27.95 40 0.400.80 9.48 0.09 3.88 7.64 0.84 0.23
10 DOL DFDS‐1 BOARD AT PUMP HOUSE‐1 DFDS1 EXAUST FAN ‐2 AT PUMP HOUSE‐1(S) EXF2 0.25 0.63 415 0.4 0.95 ‐ 0.76 0.65 4 4 2XWY 43 ‐ 27.95 1 27.95 40 0.40 0.80 9.48 0.09 3.88 7.64 0.84 0.23
11 DOL DFDS‐1 BOARD AT PUMP HOUSE‐1 DFDS1 EXAUST FAN ‐3 AT PUMP HOUSE‐1(W) EXF3 0.25 0.63 415 0.4 0.95 ‐ 0.76 0.65 4 4 2XWY 43 ‐ 27.95 1 27.95 40 0.40 0.80 9.48 0.09 3.88 7.64 0.84 0.23
1 MCCB A/C & VENTILLATION PANEL SS1_ACVMCC AC PANEL  AT SS‐1 (VENDOR PANEL) ACP1 60 ‐ 415 104.3 0.95 ‐ 0.76 0.653.5 70A2XFY 164 ‐ 106.60 1 106.60 40 ‐ 0.80 0.57 0.07 0 0.50 0.00 3.60
1 DOL AC PANEL  AT SS‐1 (VENDOR PANEL) SS1_ACVMCC PACKAGE UNIT‐I (22TR) ACP1 37 ‐ 415 64.3 0.95 ‐ 0.76 0.653.5 50A2XFY 133 ‐ 86.45 1 86.45 40 ‐ 0.80 0.82 0.08 0 0.70 0.00 3.12
1 DOL AC PANEL  AT SS‐1 (VENDOR PANEL) SS1_ACVMCC PACKAGE UNIT‐II (22TR) ACP2 37 ‐ 415 64.3 0.95 ‐ 0.76 0.653.5 50A2XFY 133 ‐ 86.45 1 86.45 40 ‐ 0.80 0.82 0.08 0 0.70 0.00 3.12
1 DOL AC PANEL  AT SS‐1 (VENDOR PANEL) SS1_ACVMCC PUMP‐1 PM‐1 3 ‐ 415 5.2 0.95 ‐ 0.76 0.65 4 2.52XWY34 ‐ 22.10 1 22.10 40 ‐ 0.80 15.50 0.10 0 12.46 0.00 4.50
1 DOL AC PANEL  AT SS‐1 (VENDOR PANEL) SS1_ACVMCC PUMP‐2 PM‐2 3 ‐ 415 5.2 0.95 ‐ 0.76 0.65 4 2.52XWY34 ‐ 22.10 1 22.10 40 ‐ 0.80 15.50 0.10 0 12.46 0.00 4.50
2 DOL A/C & VENTILLATION PANEL SS1_ACVMCC EXAUST FAN‐1 AT CABLE FLOOR EXF1 0.25 ‐ 415 0.4 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 0.40 0.80 15.50 0.10 6.29 12.46 1.36 0.38
3 DOL A/C & VENTILLATION PANEL SS1_ACVMCC SUPPLY FAN‐1 AT SS‐1 SUF1 11 ‐ 415 19.1 0.95 ‐ 0.76 0.65 4 10 2XWY 57 ‐ 37.05 1 37.05 40 0.40 0.80 3.94 0.08 1.65 3.20 15.77 4.24
4 DOL A/C & VENTILLATION PANEL SS1_ACVMCC EXAUST FAN‐2 AT CAP.BANK ROOM EXF2 0.55 ‐ 415 1.0 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 0.40 0.80 15.50 0.10 6.29 12.46 3.00 0.83
5 DOL A/C & VENTILLATION PANEL SS1_ACVMCC EXAUST FAN‐3 AT BATTERY ROOM EXF3 0.55 ‐ 415 1.0 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 0.40 0.8015.50 0.10 6.29 12.46 3.00 0.83
6 DOL A/C & VENTILLATION PANEL SS1_ACVMCC EXAUST FAN‐4 AT MLDB ROOMEXF4 0.25 ‐ 415 0.4 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 0.40 0.80 15.50 0.10 6.29 12.46 1.36 0.38
7 DOL A/C & VENTILLATION PANEL SS1_ACVMCC EXAUST FAN‐5 AT PMCC  EXF50.25 ‐ 415 0.4 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 0.40 0.80 15.50 0.10 6.29 12.46 1.36 0.38
8 DOL A/C & VENTILLATION PANEL SS1_ACVMCC EXAUST FAN‐6 AT PMCC  EXF60.25 ‐ 415 0.4 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 0.40 0.80 15.50 0.10 6.29 12.46 1.36 0.38
A/C & VENTILLATION PANEL
CAP. BANK ROOM
PMCC
BATTERY ROOM
SS‐1 AHU ROOM
SS‐1 AHU ROOM
CABLE FLOOR
PUMP HOUSE‐1 DFDS1
PMCC
PUMP HOUSE‐1 DFDS1
SUBSTATION (SS‐1)
MLDB ROOM
SS‐1 AHU ROOM
SS‐1 AHU ROOM
SS‐1 AHU ROOM
PUMP HOUSE‐1 DFDS1
9 DOL A/C & VENTILLATION PANEL SS1_ACVMCC EXAUST FAN‐7 AT PMCC  EXF70.25 ‐ 415 0.4 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 0.40 0.80 15.50 0.10 6.29 12.46 1.36 0.38
10 DOL A/C & VENTILLATION PANEL SS1_ACVMCC EXAUST FAN‐8 AT PMCC  EXF8 0.25 ‐ 415 0.4 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 0.40 0.80 15.50 0.10 6.29 12.46 1.36 0.38
1 MCCB WELDING TRANSFORMER‐9 AT SS‐1 SS1_TR9 WELDING DISTRIBUTION BOARD AT SS‐1 SS1_WDB128­415 222.6 0.95 ‐ 0.76 0.65 3.595A2XFY 196­127.402254.80 40 ‐ 0.80 0.41 0.07 0 0.37 0.00 2.86
2 MCCB WELDING DB AT SS‐1 SS1_WDB WELDING SOCKET OUTLET AT SS‐1 GROUND FLOOR WS_SS1 18 ‐ 415 31.3 0.95 ‐ 0.76 0.65 3.550A2XFY 133 ‐ 86.45 1 86.45 35 ‐ 0.80 0.82 0.08 0 0.70 0.00 1.33
3 MCCB WELDING DB AT SS‐1 SS1_WDB WELDING SOCKET OUTLET AT TH‐2  EL+952.000 WS_TH2 18 ‐ 415 31.3 0.95 ‐ 0.76 0.65 3.550A2XFY 133 ‐ 86.45 1 86.45 100 ‐ 0.80 0.82 0.08 0 0.70 0.00 3.80
4 MCCB WELDING DB AT SS‐1 SS1_WDB WELDING SOCKET OUTLET AT SILO BUILDING EL+981.800 WS_SLDBG 18 ‐ 415 31.3 0.95 ‐ 0.76 0.65 3.595A2XFY 196 ‐ 127.40 1 127.40 150 ‐ 0.80 0.41 0.07 0 0.37 0.00 3.02
5 MCCB WELDING DB AT SS‐1 SS1_WDB WELDING SOCKET OUTLET AT TAIL DRIVE HOUSE EL+957.00 WS_TDH 18 ‐ 415 31.3 0.95 ‐ 0.76 0.65 3.595A2XFY 196 ‐ 127.40 1 127.40 150 ‐ 0.80 0.41 0.07 0 0.37 0.00 3.02
6 MCCB WELDING DB AT SS‐1 SS1_WDB WELDING SOCKET OUTLET AT TH‐2A EL+946.600 WS_TH2A 18 ‐ 415 31.3 0.95 ‐ 0.76 0.65 3.570A2XFY 164 ‐ 106.60 1 106.60 125 ‐ 0.80 0.57 0.07 0 0.50 0.00 3.37
7 MCCB WELDING DB AT SS‐1 SS1_WDB WELDING SOCKET OUTLET AT CONVEYOR‐719 EL+980.500 WS_CON719 18 ‐ 415 31.3 0.95 ‐ 0.76 0.65 3.595A2XFY 196 ‐ 127.40 1 127.40 150 ‐ 0.80 0.41 0.07 0 0.37 0.00 3.02
8 MCCB WELDING DB AT SS‐1 SS1_WDB WELDING SOCKET OUTLET AT TH‐1,EL+980.500 WS_TH1 18 ‐ 415 31.3 0.95 ‐ 0.76 0.65 3.5240A2XFY 326 ‐ 211.90 1 211.90 350 ‐ 0.80 0.16 0.07 0 0.17 0.00 3.24
9 MCCB WELDING DB AT SS‐1 SS1_WDB WELDING SOCKET OUTLET AT PUMP HOUSE‐1, EL+001.500 WS_DFDS1 18 ‐ 415 31.3 0.95 ‐ 0.76 0.65 3.5185A2XFY 282 ‐ 183.30 1 183.30 300 ‐ 0.80 0.21 0.07 0 0.21 0.00 3.43
10 MCCB WELDING DB AT SS‐1 SS1_WDB WELDING SOCKET OUTLET AT PARKING STATION‐1, EL+939.800 WS_PS1 18 ‐ 415 31.3 0.95 ‐ 0.76 0.65 3.570A2XFY 164 ‐ 106.60 1 106.60 125 ‐ 0.80 0.57 0.07 0 0.50 0.00 3.37
1 MCCB  LIGHTING TRANSFORMER‐7 AT SS‐1 SS1_TR7  MAIN LIGHTING DISTRIBUTION BOARD AT SS‐1 SS1_MLDB 80 ‐ 230 251.0 0.95 ‐ 0.76 0.65 3.5240A2XFY 326 ‐ 211.90 2 423.80 20 ‐ 0.80 0.16 0.07 0 0.17 0.00 0.74 SUBSTATION (SS‐1)
MAIN LIGHTING DISTRIBUTION BOARD
WELDING DB AT SS­1
CONVEYOR‐719
SUBSTATION (SS‐1)
SILO BUILDING
PUMP HOUSE‐1 DFDS1
PARKING STATION‐1
PMCC
SUBSTATION (SS‐1)
TAIL DRIVE HOUSE
TRANSFER HOUSE TH‐2A
PMCC
TRANSFER HOUSE TH‐2
TRANSFER HOUSE TH‐1
DESIGN CALCULATION SHEET FOR LT POW ER CABLEDOC. NO.- EL00009, REV.-042 OF 12

From
Equipment Tag
 
No.
To
Equipment Tag 
No.
Motor/Eq
uipment 
Voltage 
Rating  
   
(V)
For 45 
Deg amb.
Cable laid 
on tray 
exposed to 
air
Cables laid 
inside 
concrete 
trench
Over­all
 
Rating 
Factor
Derated 
current 
rating of 
cable
No. of run 
required of
 
selected 
cable size
Selected No. 
of run
Net Current 
Provided
Starting 
PF of 
Motor
Running 
PF of 
Motor
Resistance 
at 90deg .C
  
( R )
Reactance 
at 50Hz  
   
( XL )
Starting 
Impedance 
Ohms/Km
   
Z
start
Running 
Impedance 
Ohms/Km    
Z
run
Starting 
Vdrop in 
volts   
   
V
start
Running 
Vdrop in 
volts   
   
V
run
Avg.of air & 
ground 
rating
Cable 
Length  Per
 
Run (m)
Deration factor
Full Load 
Current in 
Amp (I
fc
)
Motor 
Efficiency 
No of 
Core 
  
Installed 
Output 
Power 
   
(kW 
rated)
Cable 
Type
Selected 
Cable Size 
Voltage Drop Calculation Feeder Description                                                            
   
Feeder Description                                                
   
Current rating Of cable 
Selected
Sr.No.
Drive 
Type
Plant Area
2 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS1_MLDB LDB‐1 AT TH‐1  LDB120 ‐ 230 62.8 0.95 0.68 ‐ 0.65 3.5120A2XFY ‐ 257 166.02 1 166.02 350 ‐ 0.80 0.32 0.07 0 0.30 0.00 6.63
3 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS1_MLDB LDB‐2 AT CONV.‐719LDB2 20 ‐ 230 62.8 0.95 0.68 ‐ 0.65 3.570A2XFY ‐ 179 115.63 1 115.63 150 ‐ 0.80 0.57 0.07 0 0.50 0.00 4.69
4 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS1_MLDB LDB‐3 AT SILO BUILDING GRD. FLOOR LDB3 20 ‐ 230 62.8 0.95 0.68 ‐ 0.65 3.570A2XFY ‐ 179 115.63 1 115.63 170 ‐ 0.80 0.57 0.07 0 0.50 0.00 5.31
5 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS1_MLDB LDB‐4 AT TAIL DRIVE HOUSE LDB‐4 20 ‐ 230 62.8 0.95 0.68 ‐ 0.65 3.550A2XFY ‐ 142 91.73 1 91.73 150 ‐ 0.80 0.82 0.08 0 0.70 0.00 6.60
6 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS1_MLDB LDB‐5 AT TH‐2 LDB‐520 ‐ 230 62.8 0.95 0.68 ‐ 0.65 3.550A2XFY 133 ‐ 85.92 1 85.92 150 ‐ 0.80 0.82 0.08 0 0.70 0.00 6.60
7 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS1_MLDB LDB‐6 AT TH‐2A LDB‐6 20 ‐ 230 62.8 0.95 0.68 ‐ 0.65 3.550A2XFY ‐ 142 91.73 1 91.73 150 ‐ 0.80 0.82 0.08 0 0.70 0.00 6.60
8 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS1_MLDB LDB‐7 AT SS‐1 GROUND FLOOR LDB‐7 20 ‐ 230 62.8 0.95 0.68 ‐ 0.65 425A2XFY ‐ 108 69.77 1 69.77 50 ‐ 0.80 1.54 0.08 0 1.28 0.00 4.02
9 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS1_MLDB LDB‐8 AT SS‐1 FIRST FLOOR LDB‐8 20 ‐ 230 62.8 0.95 0.68 ‐ 0.65 3.535A2XFY ‐ 117 75.58 1 75.58 100 ‐ 0.80 1.11 0.08 0 0.93 0.00 5.87
TRANSFER HOUSE‐1
TAIL DRIVE HOUSE
CONV.‐719
SS‐1 GROUND FLOOR
TRANSFER HOUSE‐2A
TRANSFER HOUSE‐2
SS‐1 FIRST FLOOR
SILO BUILDING
10 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS1_MLDB LDB‐9 AT PUMP HOUSE‐1(DFDS1) LDB‐9 20 ‐ 230 62.8 0.95 0.68 ‐ 0.65 3.595A2XFY ‐ 221 142.77 1 142.77 250 ‐ 0.80 0.41 0.07 0 0.37 0.00 5.83
11 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS1_MLDB SLDB‐1 at SS1 SLDB1 20 ‐ 230 62.8 0.95 0.68 ‐ 0.65 3.595A2XFY ‐ 221 142.77 1 142.77 300 ‐ 0.80 0.41 0.07 0 0.37 0.00 6.99
1 MCB AUX. POWER DISTRIBUTION BOARD SS1_APDB FPDB AT CONV.‐718 TAIL END OR CH FPDB_718 1 ‐ 415 1.7 0.95 0.68 ‐ 0.65 4 10 2XWY ‐ 62 40.30 1 40.30 350‐ 0.80 3.94 0.08 0 3.20 0.00 1.95
2 MCB AUX. POWER DISTRIBUTION BOARD SS1_APDB FPDB AT TRANSFER HOUSE TH‐1 FPDB_TH1 1 ‐ 415 1.7 0.95 0.68 ‐ 0.65 4 10 2XWY ‐ 62 40.30 1 40.30 350 ‐ 0.803.94 0.08 0 3.20 0.00 1.95
3 MCB AUX. POWER DISTRIBUTION BOARD SS1_APDB FPDB AT TRANSFER HOUSE TH‐2 FPDB_TH2 1 ‐ 415 1.7 0.95 0.68 ‐ 0.65 4 10 2XWY ‐ 62 40.30 1 40.30 150 ‐ 0.803.94 0.08 0 3.20 0.00 0.84
4 MCB AUX. POWER DISTRIBUTION BOARD SS1_APDB FPDB AT TRANSFER HOUSE TH‐2A FPDB_TH2A 1 ‐ 415 1.7 0.95 0.68 ‐ 0.65 4 10 2XWY ‐ 62 40.30 1 40.30 150 ‐ 0.80 3.94 0.08 0 3.20 0.00 0.84
5 MCB AUX. POWER DISTRIBUTION BOARD SS1_APDB FPDB AT PUMP HOUSE‐1(DFDS1) FPDB_DFDS1 1 ‐ 415 1.7 0.95 0.68 ‐ 0.65 4 10 2XWY ‐ 62 40.30 1 40.30 150 ‐ 0.80 3.94 0.08 0 3.20 0.00 0.84
6 MCB AUX. POWER DISTRIBUTION BOARD SS1_APDB AUX POWER SUPPLY TO DIST.TRAFO‐1 MARSH.BOX TR1 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 50 ‐ 0.80 15.50 0.10 0 12.46 0.00 1.08
7 MCB AUX. POWER DISTRIBUTION BOARD SS1_APDB AUX POWER SUPPLY TO CONV.TRAFO‐3 MARSH.BOX TR3 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 50 ‐ 0.80 15.50 0.10 0 12.46 0.00 1.08
8 MCB AUX. POWER DISTRIBUTION BOARD SS1_APDB AUX POWER SUPPLY TO CONV.TRAFO‐4 MARSH.BOX TR4 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 50 ‐ 0.80 15.50 0.10 0 12.46 0.00 1.08
9 MCB AUX. POWER DISTRIBUTION BOARD SS1_APDB AUX POWER SUPPLY TO LIGHT .TRAFO‐7 MARSH.BOX TR7 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 122.10 50 ‐ 0.80 15.50 0.10 0 12.46 0.00 1.08
10 MCB AUX. POWER DISTRIBUTION BOARD SS1_APDB AUX POWER SUPPLY TO WELDING TRAFO‐9 MARSH.BOX TR9 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 50 ‐ 0.80 15.50 0.10 0 12.46 0.00 1.08
11 MCB AUX. POWER DISTRIBUTION BOARD SS1_APDB AUX POWER SUPPLY TO BUSDUCT OF PMCC BD1 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 50 ‐0.80 15.50 0.10 0 12.46 0.00 1.08
12 MCB AUX. POWER DISTRIBUTION BOARD SS1_APDB AUX POWER SUPPLY TO OF 6.6KV SWGR. 6.6KV SWGR 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 50 ‐ 0.80 15.50 0.10 0 12.46 0.00 1.08
STREET LIGHTING
AUX. POWER DISTRIBUTION BOARD
SUBSTATION (SS‐1)
SUBSTATION (SS‐1)
SUBSTATION (SS‐1)
SUBSTATION (SS‐1)
SUBSTATION (SS‐1)
SUBSTATION (SS‐1)
SUBSTATION (SS‐1)
SUBSTATION (SS‐1)
SUBSTATION (SS‐1)
PUMP HOPUSE‐1
SUBSTATION (SS‐1)
SUBSTATION (SS‐1)
SUBSTATION (SS‐1)
13 MCB AUX. POWER DISTRIBUTION BOARD SS1_APDB AUX POWER SUPPLY TO BUSDUCT OF CONV.INC‐1 BD2 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 50 ‐ 0.80 15.50 0.10 0 12.46 0.00 1.08
14 MCB AUX. POWER DISTRIBUTION BOARD SS1_APDB AUX POWER SUPPLY TO BUSDUCT OF CONV.INC.‐2 BD3 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 50 ‐ 0.80 15.50 0.10 0 12.46 0.00 1.08
15 MCB AUX. POWER DISTRIBUTION BOARD SS1_APDB AUX POWER SUPPLY TO FIRE PANEL AT SS‐1 FAP 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.1050 ‐ 0.80 15.50 0.10 0 12.46 0.00 1.08
16 MCB AUX. POWER DISTRIBUTION BOARD SS1_APDB AUX POWER SUPPLY TO BRAKE PANEL‐1 BRK PNL‐1 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 50 ‐ 0.80 15.50 0.10 0 12.46 0.00 1.08
17 MCB AUX. POWER DISTRIBUTION BOARD SS1_APDB AUX POWER SUPPLY TO BRAKE PANEL‐2 BRK PNL‐2 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 50 ‐ 0.80 15.50 0.10 0 12.46 0.00 1.08
CABLES FED FROM SS-2 SUBSTATION
SUBSTATION (SS‐1)
SUBSTATION (SS‐1)
SUBSTATION (SS‐1)
SUBSTATION (SS‐1)
SUBSTATION (SS‐1)
1 VVVFCONVERTER TRANSFORMER­5 TR5 727­VVF PANEL VF727
2 VVVFCONVERTER TRANSFORMER­6 TR6 727­VVF PANEL VF727
3 VVVF CONVEYOR‐727 VVF PANEL AT SS‐2 VF721 CONV 727 (REVERSIBLE) MOTOR M_727 450 0.96 690 484.2 0.95 0.68 ‐ 0.65 3300A2XFY ‐ 455 455 295.75 1.642591.50 300 ‐ 0.81 0.13 0.07 0.00 0.15 0.00 18.24
3AVVVF
CONVEYOR‐727 VVF PANEL AT SS‐2‐DRIVE PANEL 
EARTH 
VF721
CONV 727 (REVERSIBLE)  FROM DRIVE PANEL EARTH TO MOTOR 
EARTH TERMINAL
PE_727 4503150A2XFY1300
5 VVVF CONVEYOR‐727 VVF PANEL AT SS‐2 VF723 BREAKING RESISTER‐1 AT GROUND FLOOR OF SS‐2 BR1_727 400 ‐ 980 ‐ ‐ ‐ ‐ ‐ CU ‐ ‐ ‐1‐‐40‐‐‐‐‐‐‐‐
4PMCCDISTRIBUTION TRANSFORMER­2 TR2 415V POWER MOTOR CONTROL CENTRE PMCC
5 MCCB SS‐2 SUBSTATION ‐ PMCC SS2_PMCC GEAR BOX FOR CONVEYOR‐727  GB_7271.5‐ 415 2.6 0.95 0.68 ‐ 0.65 4 10 2XWY ‐ 62 40.05 1 40.05 350 ‐ 0.80 3.94 0.08 0 3.20 0.00 5.06
6 MCCB SS‐2 SUBSTATION ‐ PMCC SS2_PMCC HYD.BRAKE SYSTEM FOR CONV.727 HYB_727 5 ‐ 415 8.7 0.95 0.68 ‐ 0.65 4 16 A2XFY ‐ 79 51.03 1 51.03 350 ‐ 0.80 2.440.08 0 2.00 0.00 10.54
7 DOL SS‐2 SUBSTATION ‐ PMCC SS2_PMCC BELT CONVEYOR 727‐1 MOTOR M‐721‐1 30 0.92 415 56.7 0.95 0.68 ‐ 0.65 3.5 120 A2XFY ‐ 257 166.02 1 166.02 400 0.30 0.80 0.32 0.07 0.17 0.30 46.71 11.86
9 DOL SS‐2 SUBSTATION ‐ PMCC SS2_PMCC BELT CONVEYOR 727‐2 MOTOR M_727‐2 1100.94415 191.3 0.95 0.68 ‐ 0.65 3.5240A2XFY 326 ‐ 210.60 2 421.19 300 0.30 0.80 0.16 0.07 0.12 0.17 41.41 8.48
10 DOL SS‐2 SUBSTATION ‐ PMCC SS2_PMCC BELT .CONV. 727‐2 THRUSTER BRAKE (Y‐721‐2) THB_721‐2 0.5 ‐ 415 0.9 0.95 0.68 ‐ 0.65 4 4 2XWY 43 ‐ 27.78 1 27.78 300 ‐ 0.80 9.48 0.09 0 7.64 0.00 3.45
10 MCB SS‐2 SUBSTATION ‐ PMCC SS2_PMCC SPACE HEATER FOR CONV.727‐2 (SPH‐721‐2) SPH_721‐2 0.6 ‐ 415 1.0 0.95 0.68 ‐ 0.65 3 4 2XWY 43 ‐ 27.78 1 27.78300 0.80 9.48 0.09 0 7.64 0.00 4.14
11 DOL SS‐2 SUBSTATION ‐ PMCC SS2_PMCC TRANSFER HOUSE‐4 SIREN(H‐TH‐4) HTR_TH4 0.375 0.63 415 1.0 0.95 0.68 ‐ 0.65 4 2.5 2XWY 30 19.38 1 19.38 350 0.40 0.80 15.50 0.10 6.29 12.46 28.28 7.78
12 DOL SS‐2 SUBSTATION ‐ PMCC SS2_PMCC TRANSFER HOUSE‐5 SIREN(H‐TH‐5) HTR_TH5 0.375 0.63 415 1.0 0.95 0.68 ‐ 0.65 4 2.5 2XWY 34 0 21.96 1 21.96 300 0.40 0.80 15.50 0.10 6.29 12.46 24.24 6.67
TRANSFER HOUSE‐4
727  VVVF PANEL
TRANSFER HOUSE‐43C X 120Sqmm
TRANSFER HOUSE‐4
TRANSFER HOUSE‐5
SUBSTATION (SS‐2)
TRANSFER HOUSE‐5
BUSDUCT­1
BUSDUCT­2
SS­2 SUBSTATION ­ PMCC
BUSDUCT
SUBSTATION (SS‐2)
TRANSFER HOUSE‐5
TRANSFER HOUSE‐6
BELT CONV.727
BELT CONV.727
TRANSFER HOUSE‐5
SUBSTATION (SS‐2)
TRANSFER HOUSE‐4
DESIGN CALCULATION SHEET FOR LT POW ER CABLEDOC. NO.- EL00009, REV.-043 OF 12

From
Equipment Tag
 
No.
To
Equipment Tag 
No.
Motor/Eq
uipment 
Voltage 
Rating  
   
(V)
For 45 
Deg amb.
Cable laid 
on tray 
exposed to 
air
Cables laid 
inside 
concrete 
trench
Over­all
 
Rating 
Factor
Derated 
current 
rating of 
cable
No. of run 
required of
 
selected 
cable size
Selected No. 
of run
Net Current 
Provided
Starting 
PF of 
Motor
Running 
PF of 
Motor
Resistance 
at 90deg .C
  
( R )
Reactance 
at 50Hz  
   
( XL )
Starting 
Impedance 
Ohms/Km
   
Z
start
Running 
Impedance 
Ohms/Km    
Z
run
Starting 
Vdrop in 
volts   
   
V
start
Running 
Vdrop in 
volts   
   
V
run
Avg.of air & 
ground 
rating
Cable 
Length  Per
 
Run (m)
Deration factor
Full Load 
Current in 
Amp (I
fc
)
Motor 
Efficiency 
No of 
Core 
  
Installed 
Output 
Power 
   
(kW 
rated)
Cable 
Type
Selected 
Cable Size 
Voltage Drop Calculation Feeder Description                                                            
   
Feeder Description                                                
   
Current rating Of cable 
Selected
Sr.No.
Drive 
Type
Plant Area
13 DOL SS‐2 SUBSTATION ‐ PMCC SS2_PMCC TRANSFER HOUSE‐6 SIREN(H‐TH‐6) HTR_TH6 0.375 0.63 415 1.0 0.95 0.68 ‐ 0.65 4 2.5 2XWY ‐ 30 19.38 1 19.38 400 0.40 0.80 15.50 0.10 6.29 12.46 32.33 8.89
14 RDOL SS‐2 SUBSTATION ‐ PMCC SS2_PMCC WINCH DRIVE AT TH‐3 WD_TH3 18‐ 415 31.3 0.95 0.68 ‐ 0.65 3.5 150 A2XFY ‐ 292 188.63 1 188.63 550 0.40 0.80 0.26 0.07 0.17 0.25 36.76 7.58
15 MCCB SS‐2 SUBSTATION ‐ PMCC SS2_PMCC HYDRAULIC GATE PANEL (HG‐724A) HG‐724A 18.5 ‐ 415 32.2 0.95 0.68 ‐ 0.65 3.5 120 A2XFY ‐ 257 166.02 1 166.02600 0.40 0.80 0.32 0.07 0.19 0.30 46.90 10.09
17 MCCB SS‐2 SUBSTATION ‐ PMCC SS2_PMCC 7.5 T SINGLE GIRDER EOT CRANE (EOT‐727B)‐TH4 EOT‐727B 10 ‐ 415 17.4 0.95 0.68 ‐ 0.65 3.550A2XFY ‐ 142 91.73 1 91.73 400 0.40 0.80 0.82 0.08 0.40 0.70 34.41 8.45
18 MCCB SS‐2 SUBSTATION ‐ PMCC SS2_PMCC 3.0 T. ELECT HOIST LP AT TH‐5 (EH‐727A) EH‐727A 5.5 ‐ 415 9.6 0.95 0.68 ‐ 0.65 425A2XFY 94 ‐ 60.72 1 60.72 325 0.40 0.80 1.54 0.08 0.69 1.28 26.74 6.89
19 MCCB SS‐2 SUBSTATION ‐ PMCC SS2_PMCC 2.0 T. ELECT HOIST LP AT TH‐6 (EH‐727C) EH‐727C 3.0 ‐ 415 5.2 0.95 0.68 ‐ 0.65 4 25 A2XFY ‐ 108 69.77 1 69.77 450 0.40 0.80 1.54 0.08 0.69 1.28 20.19 5.21
20 MCCB SS‐2 SUBSTATION ‐ PMCC TR10 WELDING TRANSFORMER‐10 AT SS‐2 TR‐10128‐ 415 222.6 0.95 ‐ 0.76 0.65 3.595A2XFY 196 ‐ 127.402254.80 40 ‐ 0.80 0.41 0.07 0 0.37 0.00 2.86
21 MCCB SS‐2 SUBSTATION ‐ PMCC SS2_PMCC POWER SUPPLY  TO BATT. CHARG PANEL INCOMER‐1 BC 20 ‐ 415 34.8 0.95 ‐ 0.76 0.65 3.5 35 A2XFY 113 ‐ 73.45 1 73.45 40 ‐ 0.80 1.11 0.08 0 0.93 0.00 2.25
TRANSFER HOUSE‐3
TRANSFER HOUSE‐6
TRANSFER HOUSE‐6
TRANSFER HOUSE‐5
SUBSTATION (SS‐2)
TRANSFER HOUSE‐4
SUBSTATION (SS‐2)
TRANSFER HOUSE‐3
22 MCCB SS‐2 SUBSTATION ‐ PMCC SS2_PMCC POWER SUPPLY  TO BATT. CHARG PANEL INCOMER‐2 BC 20 ‐ 415 34.8 0.95 ‐ 0.76 0.65 3.5 35 A2XFY 113 ‐ 73.45 1 73.45 40 ‐ 0.80 1.11 0.08 0 0.93 0.00 2.25
23 MCCB SS‐2 SUBSTATION ‐ PMCC SS2_PMCC A/C & VENTILATION PANEL FOR SS‐2 ACVMCC 90 ‐ 415 156.5 0.95 ‐ 0.76 0.65 3.5150A2XFY 249 ‐ 161.85 1 161.85 40 ‐ 0.80 0.26 0.07 0 0.25 0.00 2.76
24 MCCB SS‐2 SUBSTATION ‐ PMCC SS2_PMCC POWER DB AT SS‐3 PDB 65 ‐ 415 113.0 0.95 ‐ 0.76 0.65 3.5 185 A2XFY 282 ‐ 183.30 2 366.60 600 ‐ 0.80 0.21 0.07 0 0.21 0.00 12.40
25 MCCB SS‐2 SUBSTATION ‐ PMCC SS2_PMCC AUXILARY POWER DISTRIBUTION BOARD APDB 15 ‐ 415 26.1 0.95 ‐ 0.76 0.65 3.510A2XFY 57 ‐ 37.05 1 37.05 40 ‐ 0.80 3.94 0.08 0 3.20 0.00 5.79
26 MCCB SS‐2 SUBSTATION ‐ PMCC PMCC BELT VULCANIZING AT PS2 BVM_PS2 45.54 ‐ 415 79.2 0.95 ‐ . 0.65 3.5 150 A2XFY 249 ‐ 161.85 1 161.85 300 ‐ 0.80 0.26 0.07 0 0.25 0.00 10.46
27 MCCB SS‐2 SUBSTATION ‐ PMCC PMCC BELT VULCANIZING FOR FABRIC AT TH‐6 BVM_TH6 38.7 ‐ 415 67.3 0.95 ‐ . 0.65 3.5 240 A2XFY 326 ‐ 211.90 1 211.90 500 ‐ 0.80 0.16 0.07 0 0.17 0.00 9.94
28 MCCB SS‐2 SUBSTATION ‐ PMCC PMCC DFDS BOARD AT SS‐2 DFDS‐2 96 ‐ 415 166.9 0.95 ‐ . 0.65 3.5 240 A2XFY 326 ‐ 211.90 3 635.70 600 ‐ 0.80 0.16 0.07 0 0.170.00 9.87
1 MCCB WELDING TRANSFORMER‐10 SS2_TR8 WELDING DISTRIBUTION BOARD AT SS‐2 SS2_MLDB 128 ‐ 415 222.6 0.95 ‐ 0.76 0.65 3.595A2XFY 196 ‐ 127.402254.80 40 ‐ 0.80 0.41 0.07 0 0.37 0.00 2.86
2 MCCB WELDING DISTRIBUTION BOARD AT SS‐2 SS2_WDB SOCKET OUTLET AT SS‐2 GROUND FLOOR WS_SS2 18 ‐ 415 31.3 0.95 0.68 ‐ 0.65 3.5 50 A2XFY 142 91.73 1 91.73 30 ‐ 0.80 0.82 0.08 0 0.70 0.00 1.14
3 MCCB WELDING DISTRIBUTION BOARD AT SS‐2 SS2_WDB WELDING DISTRIBUTION BOARD AT TH‐5 WDB_TH5 50 ‐ 415 87.0 0.95 0.68 ‐ 0.65 3.5 120 A2XFY 223 ‐ 144.06 2 288.12 350 ‐ 0.80 0.32 0.07 0 0.30 0.00 7.96
1 MCCB WELDING DISTRIBUTION BOARD AT TH‐5 TH5_WDB WELDING SOCKET OUTLET‐1 AT TH‐5. EL+768.000 WS_TH5 18 ‐ 415 31.3 0.95 0.68 ‐ 0.65 3.550A2XFY 133 ‐ 85.92 1 85.92 50 ‐ 0.80 0.82 0.08 0 0.70 0.00 1.90
2 MCCB WELDING DISTRIBUTION BOARD AT TH‐5 TH5_WDB WELDING SOCKET OUTLET‐1 AT CONV.‐727, EL+744.238 WS_CONV.‐727 18 ‐ 415 31.3 0.95 0.68 ‐ 0.65 3.5150A2XFY 249 ‐ 160.85 1 160.85 250 ‐ 0.80 0.26 0.07 0 0.25 0.00 3.44
3 MCCB WELDING DISTRIBUTION BOARD AT TH‐5 TH5_WDB WELDING SOCKET OUTLET‐1 AT TH‐3, EL+726.900 WS_CONV.‐727 18 ‐ 415 31.3 0.95 0.68 ‐ 0.65 3.5185A2XFY 282 ‐ 182.17 1 182.17 275 ‐ 0.80 0.21 0.07 0 0.21 0.00 3.15
4 MCCB WELDING DISTRIBUTION BOARD AT TH‐5 TH5_WDB WELDING SOCKET OUTLET‐1 AT PS‐2, EL+734.305 WS_PS2 18 ‐ 415 31.3 0.95 0.68 ‐ 0.65 3.5185A2XFY 282 ‐ 182.17 1 182.17 300 ‐ 0.80 0.21 0.07 0 0.21 0.00 3.43
5
MCCB
WELDING DISTRIBUTION BOARD AT TH 5
TH5 WDB
WELDING SOCKET 1 OUTLET AT TH 4 EL+754 000
WS TH4
18
415
31 3
095
068
065
35
50
A2XFY
133
85 92
1
85 92
50
080
082
008
0
070
000
190
SUBSTATION (SS‐2)
TH‐5
SUBSTATION (SS‐2)
SUBSTATION (SS‐2)
SUBSTATION (SS‐2)
TH‐5 & CONV‐727
WELDING DISTRIBUTION BOARD AT TH­5
WELDING DISTRIBUTION BOARD AT SS­2
TH‐3
PS‐2
SUBSTATION (SS‐2)
SUBSTATION (SS‐2)
TH 4
CONV.‐727
SUBSTATION (SS‐2)
SUBSTATION (SS‐3)
SUBSTATION (SS‐2)
5
MCCB
WELDING
 DISTRIBUTION
 BOARD
 AT
 TH

5
TH5
_
WDB
WELDING
 SOCKET

1
 OUTLET
 AT
 TH

4

EL+754
.000
WS
_
TH4
18

415
31
.3
0
.95
0
.68

0
.65
3
.5
50
A2XFY
133

85
.92
1
85
.92
50

0
.80
0
.82
0
.08
0
0
.70
0
.00
1
.90
6 MCCB WELDING DISTRIBUTION BOARD AT TH‐5 TH5_WDB WELDING SOCKET OUTLET‐1 AT CONV.‐727‐1, EL+765.946 WS_TH6 18 ‐ 415 31.3 0.95 0.68 ‐ 0.65 3.570A2XFY 164 ‐ 105.94 1 105.94 100 ‐ 0.80 0.57 0.07 0 0.50 0.00 2.70
6 MCCB WELDING DISTRIBUTION BOARD AT TH‐5 TH5_WDB WELDING SOCKET OUTLET‐1 AT CONV.‐727‐2, EL+765.946 WS_TH6 18 ‐ 415 31.3 0.95 0.68 ‐ 0.65 3.570A2XFY 164 ‐ 105.94 1 105.94 100 ‐ 0.80 0.57 0.07 0 0.50 0.00 2.70
7 MCCB WELDING DISTRIBUTION BOARD AT TH‐5 TH5_WDB WELDING SOCKET OUTLET‐1 AT TH‐6, EL+769.718 WS_TH6 18 ‐ 415 31.3 0.95 0.68 ‐ 0.65 3.595A2XFY 196 ‐ 126.62 1 126.62 150 ‐ 0.80 0.41 0.07 0 0.37 0.00 3.02
CONV‐727‐1
TH‐6 
CONV‐727‐2
TH

4
DESIGN CALCULATION SHEET FOR LT POW ER CABLEDOC. NO.- EL00009, REV.-044 OF 12

From
Equipment Tag
 
No.
To
Equipment Tag 
No.
Motor/Eq
uipment 
Voltage 
Rating  
   
(V)
For 45 
Deg amb.
Cable laid 
on tray 
exposed to 
air
Cables laid 
inside 
concrete 
trench
Over­all
 
Rating 
Factor
Derated 
current 
rating of 
cable
No. of run 
required of
 
selected 
cable size
Selected No. 
of run
Net Current 
Provided
Starting 
PF of 
Motor
Running 
PF of 
Motor
Resistance 
at 90deg .C
  
( R )
Reactance 
at 50Hz  
   
( XL )
Starting 
Impedance 
Ohms/Km
   
Z
start
Running 
Impedance 
Ohms/Km    
Z
run
Starting 
Vdrop in 
volts   
   
V
start
Running 
Vdrop in 
volts   
   
V
run
Avg.of air & 
ground 
rating
Cable 
Length  Per
 
Run (m)
Deration factor
Full Load 
Current in 
Amp (I
fc
)
Motor 
Efficiency 
No of 
Core 
  
Installed 
Output 
Power 
   
(kW 
rated)
Cable 
Type
Selected 
Cable Size 
Voltage Drop Calculation Feeder Description                                                            
   
Feeder Description                                                
   
Current rating Of cable 
Selected
Sr.No.
Drive 
Type
Plant Area
8 MCCB WELDING DISTRIBUTION BOARD AT TH‐5 TH5_WDB  WELDING SOCKET OUTLET‐1 AT PUMP HOUSE‐2 WS_SS3 18 ‐ 415 31.3 0.95 0.68 ‐ 0.65 3.5120A2XFY ‐ 257 166.02 2 332.04 400 ‐ 0.80 0.32 0.07 0 0.30 0.00 3.27
9 MCCB WELDING DISTRIBUTION BOARD AT TH‐5 TH5_WDB
 WELDING SOCKET OUTLET‐1 AT TRANSFER STATION, 
EL+766.733
WS_TS 18 ‐ 415 31.3 0.95 0.68 ‐ 0.65 3.595A2XFY ‐ 221 142.77 1 142.77 150 ‐ 0.80 0.41 0.07 0 0.37 0.00 3.02
10 MCCB WELDING DISTRIBUTION BOARD AT TH‐5 TH5_WDB
 WELDING SOCKET OUTLET‐1 AT TCONV.‐723 BELT TURN OVER 
AREA
WS_BTUA 18 ‐ 415 31.3 0.95 0.68 ‐ 0.65 3.595A2XFY ‐ 221 142.77 1 142.77 150 ‐ 0.80 0.41 0.07 0 0.37 0.00 3.02
1 MCCB AC & VENTILLATION PANEL AT SS‐2 SS2_ACVMCC AC PANEL(VENDOR) ACP1 75 ‐ 415 130.4 0.95 ‐ 0.76 0.65 3.5120A2XFY 223 ‐ 144.95 1 144.95 40 ‐ 0.80 0.32 0.07 0 0.30 0.00 2.73
MCCB AC PANEL(VENDOR) PACKAGE UNIT‐I (11TR) ACP1 25 ‐ 415 43.5 0.95 ‐ 0.760.65416A2XFY 73 ‐ 47.45 1 47.45 40 ‐ 0.80 2.44 0.08 0 2.00 0.00 6.03
MCCB AC PANEL(VENDOR) PACKAGE UNIT‐II (11TR) ACP2 25 ‐ 415 43.5 0.95 ‐ 0.76 0.65 416A2XFY 73 ‐ 47.45 1 47.45 40 ‐ 0.80 2.44 0.08 0 2.00 0.00 6.03
DOL AC PANEL(VENDOR) PUMP‐1 PM‐1 3 ‐ 415 5.2 0.95 ‐ 0.76 0.65 462XWY 43 ‐ 27.95 1 27.95 40 ‐ 0.80 5.90 0.09 0 4.77 0.00 1.73
AC & VENTILLATION PANEL AT SS­2
SS‐2 AHUROOM
DHC 723 AREA
SS‐2 AHUROOM
SS‐2 AHUROOM
TRANSFER STATION
SS‐2 AHUROOM
TRANSFER STATION
DOL AC PANEL(VENDOR) PUMP‐2 PM‐2 1.5 ‐ 415 2.6 0.95 ‐ 0.76 0.65 462XWY 43 ‐ 27.95 1 27.95 40 ‐ 0.80 5.90 0.09 0 4.77 0.00 0.86
2 DOL AC & VENTILLATION PANEL AT SS‐2 SS2_ACVMCC EXAUST FAN EF‐1(CAP BANK ROOM) EXF1 0.55 ‐ 415 1.0 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 0.40 0.80 15.50 0.10 6.29 12.46 3.00 0.83
3 DOL AC & VENTILLATION PANEL AT SS‐2 SS2_ACVMCC EXAUST FAN EF‐2(BATTERY ROOM) EXF2 0.55 ‐ 415 1.0 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 400.40 0.80 15.50 0.10 6.29 12.46 3.00 0.83
4 DOL AC & VENTILLATION PANEL AT SS‐2 SS2_ACVMCC EXAUST FAN EF‐3(MLDB ROOM) EXF3 0.25 ‐ 415 0.4 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 0.40 0.80 15.50 0.10 6.29 12.46 1.36 0.38
5 DOL AC & VENTILLATION PANEL AT SS‐2 SS2_ACVMCC EXAUST FAN EF‐4(PMCC) EXF4 0.25 ‐ 415 0.4 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 0.40 0.8015.50 0.10 6.29 12.46 1.36 0.38
6 DOL AC & VENTILLATION PANEL AT SS‐2 SS2_ACVMCC EXAUST FAN EF‐5(CABLE FOOR) EXF5 0.25 ‐ 415 0.4 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 0.40 0.80 15.50 0.10 6.29 12.46 1.36 0.38
7 DOL AC & VENTILLATION PANEL AT SS‐2 SS2_ACVMCC EXAUST FAN EF‐6(PMCC) EXF6 0.25 ‐ 415 0.4 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 0.40 0.8015.50 0.10 6.29 12.46 1.36 0.38
8 DOL AC & VENTILLATION PANEL AT SS‐2 SS2_ACVMCC EXAUST FAN EF‐7(PMCC) EXF7 0.25 ‐ 415 0.4 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 0.40 0.8015.50 0.10 6.29 12.46 1.36 0.38
9 DOL AC & VENTILLATION PANEL AT SS‐2 SS2_ACVMCC EXAUST FAN EF‐8(PMCC) EXF8 0.25 ‐ 415 0.4 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 0.40 0.8015.50 0.10 6.29 12.46 1.36 0.38
10 DOL AC & VENTILLATION PANEL AT SS‐2 SS2_ACVMCC SUPPLY FAN‐1 AT SS‐2 AF‐1 11 ‐ 415 19.1 0.95 ‐ 0.76 0.65 4 10 2XWY 57 ‐ 37.05 1 37.05 40 0.40 0.80 3.94 0.08 1.65 3.20 15.77 4.24
MAIN LIGHTING DISTRIBUTION BOARD AT SS­2
1 MCCB LIGHTING TRANSFORMER‐8 SS2_TR8 MLDB AT SS‐2 SS2_MLDB80‐230251.0 0.95 ‐ 0.76 0.65 3.5240A2XFY 326 ‐ 211.90 2 423.80 20 ‐ 0.80 0.16 0.07 0 0.17 0.00 0.74
2 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS2_MLDB LDB‐10 AT PS2 LDB‐1020‐ 230 62.8 0.95 0.68 ‐ 0.65 3.5185A2XFY ‐ 337 217.70 2 435.40 600 ‐ 0.80 0.21 0.07 0 0.21 0.00 6.88
3 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS2_MLDB LDB‐11 AT TH‐3 LDB‐1120‐ 230 62.8 0.95 0.68 ‐ 0.65 3.5185A2XFY ‐ 337 217.70 2 435.40 600 ‐ 0.80 0.21 0.07 0 0.21 0.00 6.88
4 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS2_MLDB LDB‐12 AT CONV‐727LDB‐1220‐ 230 62.8 0.95 0.68 ‐ 0.65 3.595A2XFY ‐ 221 142.77 2 285.53 350 ‐ 0.80 0.41 0.07 0 0.37 0.00 7.07
5 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS2_MLDB LDB‐13 AT TH‐5 LDB‐1320‐ 230 62.8 0.95 0.68 ‐ 0.65 3.5240A2XFY 326 ‐ 210.60 1 210.60 350 ‐ 0.80 0.16 0.07 0 0.17 0.00 6.49
TRANSFER HOUSE‐3
AC VENT PANEL
SUBSTATION (SS‐2)
PMCC
CONV‐723
PMCC
SS‐2 AHUROOM
CAP BANK ROOM
PMCC
BATTERU ROOM
PMCC
PARKING STATION‐2
CABLE FLOOR
TRANSFER HOUSE‐5
MLDB ROOM
6 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS2_MLDB LDB‐14 AT TH‐4 LDB‐1420‐ 230 62.8 0.95 0.68 ‐ 0.65 3.5185A2XFY ‐ 337 217.70 1 217.70 350 ‐ 0.80 0.21 0.07 0 0.21 0.00 8.03
7 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS2_MLDB LDB‐15 AT TH‐6 LDB‐1520‐ 230 62.8 0.95 0.68 ‐ 0.65 3.5240A2XFY ‐ 399 257.75 1 257.75 400 ‐ 0.80 0.16 0.07 0 0.17 0.00 7.42
8 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS2_MLDB LDB‐16 AT TRANSFER STATION,CONV‐727‐1 LDB‐1620‐ 230 62.8 0.95 0.68 ‐ 0.65 3.5120A2XFY ‐ 257 166.02 2 332.04 500 ‐ 0.80 0.32 0.07 0 0.30 0.00 8.20
9 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS2_MLDB LDB‐17 AT SS‐2 GROUND FLOOR LDB‐1720‐ 230 62.8 0.95 0.68 ‐ 0.65 425A2XFY ‐ 108 69.77 1 69.77 30 ‐ 0.80 1.54 0.08 0 1.28 0.00 4.17
10 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS2_MLDB LDB‐18 AT SS‐2 FIRST FLOOR LDB‐1820‐ 230 62.8 0.95 0.68 ‐ 0.65 425A2XFY ‐ 108 69.77 1 69.77 50 ‐ 0.80 1.54 0.08 0 1.28 0.00 6.96
11 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS2_MLDB LDB‐19 AT SS‐3 & PUMP AREA LDB‐1920‐ 230 62.8 0.95 0.68 ‐ 0.65 3.5240A2XFY ‐ 399 257.75 1 257.75 400 ‐ 0.80 0.16 0.07 0 0.17 0.00 7.42
12 MCCB MAIN LIGHTING DISTRIBUTION BOARD SS2_MLDB SLDB2‐STREETLIGHTING SLDB120‐ 230 62.8 0.95 0.68 ‐ 0.65 4 25 A2XFY ‐ 108 69.77 1 69.77 50 ‐ 0.80 1.54 0.08 0 1.28 0.00 6.96
AUX. POWER DISTRIBUTION BOARD
1 MCB AUX. POWER DISTRIBUTION BOARD SS2_APDB FPDB AT TRANSFER HOUSE TH‐3 FPDB_TH3 1 ‐ 415 1.7 0.95 0.68 ‐ 0.65 4 10 2XWY ‐ 62 40.05 1 40.05 550 ‐ 0.803.94 0.08 0 3.20 0.00 3.06
2 MCB AUX. POWER DISTRIBUTION BOARD SS2_APDB FPDB AT TRANSFER HOUSE TH‐4 FPDB_TH4 1 ‐ 415 1.7 0.95 0.68 ‐ 0.65 4 10 2XWY ‐ 62 40.05 1 40.05 350 ‐ 0.803.94 0.08 0 3.20 0.00 1.95
3 MCB AUX. POWER DISTRIBUTION BOARD SS2_APDB FPDB AT TRANSFER HOUSE TH‐5 FPDB_TH5 1 ‐ 415 1.7 0.95 0.68 ‐ 0.65 4 10 2XWY 57 ‐ 36.82 1 36.82 300 ‐ 0.803.94 0.08 0 3.20 0.00 1.67
4 MCB AUX. POWER DISTRIBUTION BOARD SS2_APDB FPDB AT TRANSFER HOUSE TH‐6 FPDB_TH6 1 ‐ 415 1.7 0.95 0.68 ‐ 0.65 4 10 2XWY ‐ 62 40.05 1 40.05 400 ‐ 0.803.94 0.08 0 3.20 0.00 2.23
5 MCB AUX. POWER DISTRIBUTION BOARD SS2_APDB AUX POWER SUPPLY TO DIST.TRAFO‐2 MARSH.BOX TR2 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 ‐ 0.80 15.50 0.10 0 12.46 0.00 0.87
6 MCB AUX. POWER DISTRIBUTION BOARD SS2_APDB AUX POWER SUPPLY TO CONV.TRAFO‐5 MARSH.BOX TR5 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 ‐ 0.80 15.50 0.10 0 12.46 0.00 0.87
7 MCB AUX. POWER DISTRIBUTION BOARD SS2_APDB AUX POWER SUPPLY TO CONV.TRAFO‐6 MARSH.BOX TR6 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 ‐ 0.80 15.50 0.10 0 12.46 0.00 0.87
8 MCB AUX. POWER DISTRIBUTION BOARD SS2_APDB AUX POWER SUPPLY TO LIGHT .TRAFO‐8 MARSH.BOX TR8 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 122.10 40 ‐ 0.80 15.50 0.10 0 12.46 0.00 0.87
8
MCB
AUX POWER DISTRIBUTION BOARD
SS2 APDB
AUX POWER SUPPLY TO WELDING TRAFO 10 MARSH BOX
TR10
1
415
17
095
076
065
4
25
2XWY
34
22 10
1
22 10
40
080
15 50
010
0
12 46
000
087
SUBSTATION (SS‐2)
SUBSTATION (SS‐2)
SUBSTATION (SS‐2)
SS2‐FIRST FLOOR
SUBSTATION (SS‐2)
TRANSFER HOUSE‐6
SS2‐GROUND FLOOR
SUBSTATION (SS‐2)
SUBSTATION (SS‐2)
SUBSTATION (SS‐2)
SUBSTATION (SS‐2)
STREETLIGHTS
SS3  & PUMP AREA
CONV 727‐1
SUBSTATION (SS 2)TRANSFER HOUSE‐4
8
MCB
AUX

POWER
 DISTRIBUTION
 BOARD
SS2
_
APDB
AUX
 POWER
 SUPPLY
 TO
 WELDING
 TRAFO

10
 MARSH
.BOX
TR10
1

415
1
.7
0
.95

0
.76
0
.65
4
2
.5
2XWY
34

22
.10
1
22
.10
40

0
.80
15
.50
0
.10
0
12
.46
0
.00
0
.87
9 MCB AUX. POWER DISTRIBUTION BOARD SS2_APDB AUX POWER SUPPLY TO BUSDUCT OF PMCC BD1 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 ‐ 0.80 15.50 0.10 0 12.46 0.00 0.87
9 MCB AUX. POWER DISTRIBUTION BOARD SS2_APDB AUX POWER SUPPLY TO 6.6KV SWITCHGEAR 6.6KV SWGR 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 ‐ 0.80 15.50 0.10 0 12.46 0.00 0.87
10 MCB AUX. POWER DISTRIBUTION BOARD SS2_APDB AUX POWER SUPPLY TO BUSDUCT OF CONV.INC‐1 BD2 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 ‐ 0.80 15.50 0.10 0 12.46 0.00 0.87
11 MCB AUX. POWER DISTRIBUTION BOARD SS2_APDB AUX POWER SUPPLY TO BUSDUCT OF CONV.INC.‐2 BD3 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 ‐ 0.80 15.50 0.10 0 12.46 0.00 0.87
12 MCB AUX. POWER DISTRIBUTION BOARD SS2_APDB AUX POWER SUPPLY TO FIRE PANEL AT SS‐2 FAS 1 ‐ 415 1.7 0.95 ‐ 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.1040 ‐ 0.80 15.50 0.10 0 12.46 0.00 0.87
SUBSTATION (SS‐2)
SUBSTATION (SS‐2)
SUBSTATION (SS‐2)
SUBSTATION (SS‐2)
SUBSTATION (SS‐2)
SUBSTATION
 (SS

2)
DESIGN CALCULATION SHEET FOR LT POW ER CABLEDOC. NO.- EL00009, REV.-045 OF 12

From
Equipment Tag
 
No.
To
Equipment Tag 
No.
Motor/Eq
uipment 
Voltage 
Rating  
   
(V)
For 45 
Deg amb.
Cable laid 
on tray 
exposed to 
air
Cables laid 
inside 
concrete 
trench
Over­all
 
Rating 
Factor
Derated 
current 
rating of 
cable
No. of run 
required of
 
selected 
cable size
Selected No. 
of run
Net Current 
Provided
Starting 
PF of 
Motor
Running 
PF of 
Motor
Resistance 
at 90deg .C
  
( R )
Reactance 
at 50Hz  
   
( XL )
Starting 
Impedance 
Ohms/Km
   
Z
start
Running 
Impedance 
Ohms/Km    
Z
run
Starting 
Vdrop in 
volts   
   
V
start
Running 
Vdrop in 
volts   
   
V
run
Avg.of air & 
ground 
rating
Cable 
Length  Per
 
Run (m)
Deration factor
Full Load 
Current in 
Amp (I
fc
)
Motor 
Efficiency 
No of 
Core 
  
Installed 
Output 
Power 
   
(kW 
rated)
Cable 
Type
Selected 
Cable Size 
Voltage Drop Calculation Feeder Description                                                            
   
Feeder Description                                                
   
Current rating Of cable 
Selected
Sr.No.
Drive 
Type
Plant Area
DFDS BOARD PUMP HOUSE­2 AT SS­3
1 DOL DFDS‐2 BOARD AT PUMP HOUSE‐2 DFDS2 DFDS1‐PUMP‐1 AT PUMP HOUSE‐2(W) PM1 1.5 ‐ 415 2.6 0.95 0.79 0.76 0.65 4 4 2XWY 43 ‐ 27.95 1 27.95 40 0.40 0.80 9.48 0.09 3.88 7.64 5.04 1.38
2 DOL DFDS‐2 BOARD AT PUMP HOUSE‐2 DFDS2 DFDS1‐PUMP‐2 AT PUMP HOUSE‐2(S) PM2 1.5 ‐ 415 2.6 0.95 0.79 0.76 0.65 4 4 2XWY 43 ‐ 27.95 1 27.95 40 0.40 0.80 9.48 0.09 3.88 7.64 5.04 1.38
3 DOL DFDS‐2 BOARD AT PUMP HOUSE‐2 DFDS2 SW2‐PUMP‐1 AT PUMP HOUSE‐2(W) SW2_PM1 11 ‐ 415 19.1 0.95 0.79 0.76 0.65 4 10 2XWY 57 ‐ 37.05 1 37.05 40 0.400.80 3.94 0.08 1.65 3.20 15.77 4.24
4 DOL DFDS‐2 BOARD AT PUMP HOUSE‐2 DFDS2 SW2‐PUMP‐2 AT PUMP HOUSE‐2(S) SW2_PM2 11 ‐ 415 19.1 0.95 0.79 0.76 0.65 4 10 2XWY 57 ‐ 37.05 1 37.05 40 0.400.80 3.94 0.08 1.65 3.20 15.77 4.24
5 DOL DFDS‐2 BOARD AT PUMP HOUSE‐2 DFDS2 DW2‐PUMP‐1 AT PUMP HOUSE‐2(W) DW2_PM1 7.5 ‐ 415 13.0 0.95 0.79 0.76 0.65 4 6 2XWY 43 ‐ 27.95 1 27.95 40 0.400.80 5.90 0.09 2.44 4.77 15.88 4.31
CABLES FED FROM SS-3 SUBSTATION
PUMP HOUSE‐2 AT SS‐3
PUMP HOUSE‐2 AT SS‐3
PUMP HOUSE‐2 AT SS‐3
PUMP HOUSE‐2 AT SS‐3
PUMP HOUSE‐2 AT SS‐3
6 DOL DFDS‐2 BOARD AT PUMP HOUSE‐2 DFDS2 DW2‐PUMP‐2 AT PUMP HOUSE‐2(S) DW2_PM2 7.5 ‐ 415 13.0 0.95 0.79 0.76 0.65 4 6 2XWY 43 ‐ 27.95 1 27.95 40 0.400.80 5.90 0.09 2.44 4.77 15.88 4.31
7 DOL DFDS‐2 BOARD AT PUMP HOUSE‐2 DFDS2 COMPRESSOR‐1 AT PUMP HOUSE‐2 (W) CP1 75 ‐ 415 130.4 0.95 0.79 0.76 0.65 3.5 185 A2XFY 282 ‐ 183.30 1 183.30 40 0.40 0.80 0.21 0.07 0.15 0.21 9.75 1.91
8 DOL DFDS‐2 BOARD AT PUMP HOUSE‐2 DFDS2 COMPRESSOR‐2  AT PUMP HOUSE‐2 (S) CP2 75 ‐ 415 130.4 0.95 0.79 0.76 0.65 3.5 185 A2XFY 282 ‐ 183.30 1 183.30 40 0.40 0.80 0.21 0.07 0.15 0.21 9.75 1.91
9 DOL DFDS‐2 BOARD AT PUMP HOUSE‐2 DFDS2 EXAUST FAN ‐1 AT PUMP HOUSE‐2(W) EXF1 0.25 ‐ 415 0.4 0.95 0.79 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 0.40 0.80 15.50 0.10 6.29 12.46 1.36 0.38
10 DOL DFDS‐2 BOARD AT PUMP HOUSE‐2 DFDS2 EXAUST FAN ‐2 AT PUMP HOUSE‐2(S) EXF2 0.25 ‐ 415 0.4 0.95 0.79 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 0.40 0.80 15.50 0.10 6.29 12.46 1.36 0.38
11 DOL DFDS‐2 BOARD AT PUMP HOUSE‐2 DFDS2 EXAUST FAN ‐3 AT PUMP HOUSE‐2(W) EXF3 0.25 ‐ 415 0.4 0.95 0.79 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 1 22.10 40 0.40 0.80 15.50 0.10 6.29 12.46 1.36 0.38
POWER DISTRIBUTION BOARD AT SS­3
1 MCCB POWER DISTRIBUTION BOARD AT SS‐3 SS3_PDB VENTILLATION FOR SS‐3 ACVMCC 3 ‐ 415 5.2 0.95 0.68 0.76 0.65 4 4 2XWY 43 ‐ 27.95 1 27.95 50 ‐ 0.80 9.480.09 0.00 7.64 0.00 3.45
2 MCCB POWER DISTRIBUTION BOARD AT SS‐3 SS3_PDB 7.5 T. ELECT HOIST LP AT TH‐3 (EH‐726) EH‐726 9.37 ‐ 415 16.3 0.95 0.68 ‐ 0.65 4 16 A2XFY ‐ 79 51.03 1 51.03 100 0.40 0.80 2.44 0.08 1.05 2.00 21.34 5.65
3 MCCB POWER DISTRIBUTION BOARD AT SS‐3 SS3_PDB 2.0 T. ELECT HOIST LP AT TH‐3  (EH‐726A) EH‐726A 3 ‐ 415 5.2 0.95 0.68 ‐ 0.65 4 16 A2XFY ‐ 79 51.03 1 51.03 100 0.40 0.80 2.44 0.08 1.05 2.00 6.83 1.81
4 MCCB POWER DISTRIBUTION BOARD AT SS‐3 SS3_PDB 2.0 T. ELECT HOIST LP AT TH‐3 ( (EH‐726B) EH‐726B 3 ‐ 415 5.2 0.95 0.68 ‐ 0.65 4 16 A2XFY ‐ 79 51.03 1 51.03 100 0.40 0.80 2.44 0.08 1.05 2.00 6.83 1.81
5 MCCB POWER DISTRIBUTION BOARD AT SS‐3 SS3_PDB 2.0 T. ELECT HOIST LP AT TH‐3  (EH‐726C) EH‐726C 3 ‐ 415 5.2 0.95 0.68 ‐ 0.65 4 16 A2XFY ‐ 79 51.03 1 51.03 100 0.40 0.80 2.44 0.08 1.05 2.00 6.83 1.81
6 MCCB POWER DISTRIBUTION BOARD AT SS‐3 SS3_PDB 5 T UNDER SLUNG EOT CRANE LP AT PS‐2(EH‐723B) EH‐723B 6 ‐ 415 10.4 0.95 0.68 ‐ 0.65 3.550A2XFY ‐ 142 91.73 1 91.73 610 0.40 0.80 0.82 0.08 0.40 0.70 31.49 7.73
7 DOL POWER DISTRIBUTION BOARD AT SS‐3 SS3_PDB SIREN AT TH3 H‐TH‐3 HTR_TH3 0.375 ‐ 415 0.7 0.95 0.68 ‐ 0.65 4 2.5 2XWY ‐ 30 19.38 1 19.38 550 0.40 0.80 15.50 0.10 6.29 12.46 28.13 7.74
8 DOL POWER DISTRIBUTION BOARD AT SS‐3 SS3_PDB SUPPLY FAN‐1 AT SS‐3SF_SS3 1.5 ‐ 415 2.6 0.95 0.68 ‐ 0.65 4 2.5 2XWY ‐ 30 19.38 1 19.38 25 0.40 0.80 15.50 0.10 6.29 12.46 5.12 1.41
9
DOL
POWER DISTRIBUTION BOARD AT SS 3
SS3 PDB
EXAUST FAN 1 AT SS 3
EXF SS3
025
415
04
095
068
076
065
4
25
2XWY
34
22 10
1
22 10
25
040
080
15 50
010
629
12 46
085
023
PUMP HOUSE‐2 AT SS‐3
TRANSFER HOUSE‐3
PUMP HOUSE‐2 AT SS‐3
TRANSFER HOUSE‐3
TRANSFER HOUSE‐3
PUMP HOUSE‐2 AT SS‐3
PUMP HOUSE‐2 AT SS‐3
PUMP HOUSE‐2 AT SS‐3
SUBSTATION (SS‐3)
SUBSTATION (SS‐3) TRANSFER HOUSE‐3
SUBSTATION (SS‐3)
TRANSFER HOUSE‐3
PARKING STATION‐3
PUMP HOUSE‐2 AT SS‐3
9
DOL
POWER
 DISTRIBUTION
 BOARD
 AT
 SS

3
SS3
_
PDB
EXAUST
 FAN

1
 AT
 SS

3
EXF
_
SS3
0
.25

415
0
.4
0
.95
0
.68
0
.76
0
.65
4
2
.5
2XWY
34

22
.10
1
22
.10
25
0
.40
0
.80
15
.50
0
.10
6
.29
12
.46
0
.85
0
.23
10 MCCB POWER DISTRIBUTION BOARD AT SS‐3 SS3_PDB SUPPLY FOR BF ‐725 VVVF PANEL VF725 45 ‐ 415 78.3 0.95 0.68 0.76 0.65 3.5 70 A2XFY 164 ‐ 106.60 1106.60 25 0.80 0.57 0.07 0.50 0.00 1.69
11 DOL POWER DISTRIBUTION BOARD AT SS‐3 SS3_PDB HYD. OPERATED GATE 724A 18.5 ‐ 415 32.2 0.95 0.68 ‐ 0.65 3.5 95 A2XFY ‐ 221 143.65 1 143.65 100 0.40 0.80 0.41 0.07 0.23 0.37 9.24 2.07
12 DOL POWER DISTRIBUTION BOARD AT SS‐3 SS3_PDB WINCH DRIVE FOR DHC 723 AT TH‐3 WD_723 15 ‐ 415 26.1 0.95 0.68 ‐ 0.65 3.5 70 A2XFY ‐ 179 116.35 1 116.35 70 0.40 0.80 0.57 0.07 0.29 0.50 6.71 1.57
13 DOL POWER DISTRIBUTION BOARD AT SS‐3 SS3_PDB SPLIT AC UNIT AT SS‐3 ACU 2 ‐ 415 3.5 0.95 0.68 0.76 0.65 4 4 A2XFY 43 ‐ 27.95 1 27.95 30 0.80 9.48 0.09 7.64 0.00 1.38
14 MCB POWER DISTRIBUTION BOARD AT SS‐3 SS3_PDB AUX POWER SUPPLY TO FIRE PANEL AT SS‐3 FAP 1 ‐ 415 1.7 0.95 0.68 0.76 0.65 4 2.5 2XWY 34 ‐ 22.10 122.10 30 ‐ 0.80 15.50 0.10 0.00 12.46 0.00 0.65
VF725 PANEL
1 VVVF BF ‐725 VVVF PANEL VF‐725 BELT FEEDER BF‐725 MOTOR M_725 45 0.92 415 85.1 0.95 0.68 0.65 3.570A2XFY164‐ 105.94 1 105.94 90 0.30 0.80 0.57 0.07 0.24 0.50 22.98 6.60
2 DOL BF ‐725 VVVF PANEL VF‐725 BRAKE FOR BF‐725 THB_725 0.5 ‐ 415 0.9 0.95 0.68 ‐ 0.65 4 4 2XWY ‐ 36 23.26 1 23.26 90 ‐ 0.80 9.48 0.09 0.00 7.64 0.00 1.04
3 MCB BF ‐725 VVVF PANEL VF‐725 SPACE HEATER FOR BF‐725 SPH_725 0.4 ‐ 415 0.7 0.95 0.68 ‐ 0.65 3 4 2XWY ‐ 36 23.26 1 23.26 90 0.80 9.48 0.09 0 7.64 0.00 0.83
VENTILATION SYSTEM FOR SS­3
1 DOL VENTILLATION PANEL AT SS‐3 VNTMCC C.F.SUPPLY AIR FAN CFS 1.5 ‐ 415 2.6 0.95 0.68 0.76 0.65 4 4 A2XFY 43 ‐ 27.95 1 27.95 30 0.80 0.80 9.48 0.09 7.647.64 7.46 1.04
2 DOL VENTILLATION PANEL AT SS‐3 VNTMCC A.F.EXAUST AIR FAN AFE 0.25 ‐ 415 0.4 0.95 0.68 0.76 0.65 4 4 A2XFY 43 ‐ 27.95 1 27.95 30 0.80 0.80 9.48 0.09 7.64 7.64 1.24 0.17
NOTE:­ 1. IF ANY CHANGE IN EQUIPMENT KW RATING /QTY/LOCATION OF THE EQUIPMENT/METHOD OF LAYING/CABLE LENGTH,THE CABLE SIZING CALCULATION SHALL BE SUITABLEY UPGRADE BY ELECON.
SUBSTATION (SS‐3)
SUBSTATION (SS‐3)
SUBSTATION (SS‐3)
TRANSFER HOUSE‐3
TRANSFER HOUSE‐3
TRANSFER HOUSE‐3
TRANSFER HOUSE‐3
SUBSTATION
 (SS‐3)
TRANSFER HOUSE‐3
SUBSTATION (SS‐3)
SUBSTATION (SS‐3)
FOR WELDING SOCKET OUTLT AT FIELD ,EARTH CONDUCTOR EQUAL TO SIZE OF NEUTRAL CONDUCTOR TO BE PROVIDED USING 1 CORE INSULATED EARTHING CABLE FROM NEAR BY EARTH BUS. 
DESIGN CALCULATION SHEET FOR LT POW ER CABLEDOC. NO.- EL00009, REV.-046 OF 12

Starting 
Vdrop in 
% of 
Rated   
   
V
start
%
Running 
Vdrop in %
 
of Rated  
   
V
run
%
Total 
Quantity of 
Cable 
Length
0.00 1.54 450
150
0.00 1.54 450
150
‐‐40
‐‐40
‐‐40
‐‐40
0.00 1.05 30
0.00 1.25 150
0.00 1.25 150
0.00 1.39 150
0.00 1.39 150
0.00 0.56 30
0.00 0.56 30
1.56 0.43 80
2.14 0.59 110
2.92 0.80 150
2.92 0.80 150 859
231
700
8
.59
2
.31
700
0.00 0.78 350 5.77 1.55 240 0.00 0.27 120 6.82 1.87 350 0.00 0.68 150 0.00 0.69 250 0.00 0.42 150 0.00 2.08 350 0.00 1.88 150 0.00 1.47 325 7.77 1.91 150 9.57 2.60 125 5.74 1.56 150
10.24 2.40 350
9.07 2.44 350
5.39 1.32 100
5.74 1.56 150
DESIGN CALCULATION SHEET FOR LT POW ER CABLEDOC. NO.- EL00009, REV.-047 OF 12

Starting 
Vdrop in 
% of 
Rated   
   
V
start
%
Running 
Vdrop in %
 
of Rated  
   
V
run
%
Total 
Quantity of 
Cable 
Length
3.19 0.87 125
7.68 2.03 175
0.00 2.08 600
0.00 0.53 30
0.00 0.52 60
0.00 0.77 30
5.40 1.78 150
0.00
0.49
30
0.00
0.49
30
6.15 1.77 100
0.00 0.28 100
0.00 0.22 100
0.00 1.05 30
0.00 2.47 150
0.89 0.24 40
0.89 0.24 40
6.08 1.66 40
6.08 1.66 40
3.00 0.82 40
3.00 0.82 40
3.22 0.66 40
3.22 0.66 40
0.20 0.06 40 0.20 0.06 40 0.20 0.06 40
0.00 0.87 40
0.000.7540
0.000.7540
0.00 1.09 40
0.00 1.09 40
0.33 0.09 40
3.80 1.02 40
0.72 0.20 40
0.72 0.20 40
0.33 0.09 40
0.33 0.09 40
0.33 0.09 40
0.33 0.09 40 0.33 0.09 40
0.00 0.69 80
0.00 0.32 35
0.00 0.92 100
0.00 0.73 150
0.00 0.73 150
0.00 0.81 125
0.00 0.73 150
0.00 0.78 350
0.00 0.83 300
0.00 0.81 125
0.00 0.18 40
DESIGN CALCULATION SHEET FOR LT POW ER CABLEDOC. NO.- EL00009, REV.-048 OF 12

Starting 
Vdrop in 
% of 
Rated   
   
V
start
%
Running 
Vdrop in %
 
of Rated  
   
V
run
%
Total 
Quantity of 
Cable 
Length
0.00 1.60 350
0.00 1.13 150
0.00 1.28 170
0.00 1.59 150
0.00 1.59 150
0.00 1.59 150
0.00 0.97 50
0.00 1.41 100
0.00 1.40 250 0.00 1.69 300
0.00 0.47 350
0.00 0.47 350
0.00 0.20 150
0.00 0.20 150
0.00 0.20 150
0.00 0.26 50
0.00 0.26 50
0.00 0.26 50
0.00 0.26 50
0.00 0.26 50
0.00 0.26 50
0.00 0.26 50
0.00 0.26 50
0.00 0.26 50
0.00 0.26 50
0.00 0.26 50
0.00 0.26 50
0.00 2.64 600
‐‐40
0.00 1.22 350
0.00 2.54 350
11.25 2.86 400
9.98 2.04 600
0.00 0.83 300
0.00 1.00 300
6.82 1.87 350
5.84 1.61 300
DESIGN CALCULATION SHEET FOR LT POW ER CABLEDOC. NO.- EL00009, REV.-049 OF 12

Starting 
Vdrop in 
% of 
Rated   
   
V
start
%
Running 
Vdrop in %
 
of Rated  
   
V
run
%
Total 
Quantity of 
Cable 
Length
7.79 2.14 400
8.86 1.83 550
11.30 2.43 600
8.29 2.04 400
6.44 1.66 325
4.87 1.25 450
0.00 0.69 80
0.00 0.54 40
0.00 0.54 40 0.00 0.66 40 0.00 2.99 1200 0.00 1.39 40 0.00 2.52 300 0.00 2.40 500 0.00 2.38 1800
0.00 0.69 80
0.00 0.27 30
0.00 1.92 700
0.00 0.46 50
0.00 0.83 250
0.00 0.76 275
0.00 0.83 300
000
046
50
0
.00
0
.46
50
0.00 0.65 100
0.00 0.65 100
0.00 0.73 150
DESIGN CALCULATION SHEET FOR LT POW ER CABLEDOC. NO.- EL00009, REV.-0410 OF 12

Starting 
Vdrop in 
% of 
Rated   
   
V
start
%
Running 
Vdrop in %
 
of Rated  
   
V
run
%
Total 
Quantity of 
Cable 
Length
0.00 0.79 800
0.00 0.73 150
0.00 0.73 150
0.00 0.66 40
0.00 1.45 40
0.00 1.45 40
0.00 0.42 40
0.00 0.21 40 0.72 0.20 40 0.72 0.20 40 0.33 0.09 40 0.33 0.09 40 0.33 0.09 40 0.33 0.09 40 0.33 0.09 40 0.33 0.09 40 3.80 1.02 40
0.00 0.18 40
0.00 1.66 1200
0.00 1.66 1200
0.00 1.70 700
0.00 1.56 350
0.00 1.93 350 0.00 1.79 400 0.00 1.98 1000 0.00 1.01 30 0.00 1.68 50 0.00 1.79 400 0.00 1.68 50
0.00 0.74 550
0.00 0.47 350
0.00 0.40 300
0.00 0.54 400
0.00 0.21 40
0.00 0.21 40
0.00 0.21 40
0.00 0.21 40
000
021
40
0
.00
0
.21
40
0.00 0.21 40 0.00 0.21 40 0.00 0.21 40 0.00 0.21 40 0.00 0.21 40
DESIGN CALCULATION SHEET FOR LT POW ER CABLEDOC. NO.- EL00009, REV.-0411 OF 12

Starting 
Vdrop in 
% of 
Rated   
   
V
start
%
Running 
Vdrop in %
 
of Rated  
   
V
run
%
Total 
Quantity of 
Cable 
Length
1.22 0.33 40
1.22 0.33 40
3.80 1.02 40
3.80 1.02 40
3.83 1.04 40
3.83 1.04 40 2.35 0.46 40 2.35 0.46 40 0.33 0.09 40 0.33 0.09 40 0.33 0.09 40
0.00 0.83 50
5.14 1.36 100
1.65 0.44 100
1.65 0.44 100
1.65 0.44 100
7.59 1.86 610
6.78 1.87 550
1.23 0.34 25
021
006
25
0
.21
0
.06
25
0.00 0.41 25 2.23 0.50 100 1.62 0.38 70 0.00 0.33 30 0.00 0.16 30
5.54 1.59 90
0.00 0.25 90
0.00 0.20 90
1.80 0.25 30
0.30 0.04 30
DESIGN CALCULATION SHEET FOR LT POW ER CABLEDOC. NO.- EL00009, REV.-0412 OF 12