Training on Plate Heat Exchangers Project – Grand Zone @ Mall of Qatar Contractor – Lightning Electromechanical Consultant – KEO Manufacturer – Alfa Laval, Sweden Supplier – Leminar Global Distribution & Services WLL
Authorized Distributor for Alfa Laval – HVAC Division in State of Qatar PO Box-3841, Doha Tel: 44673755; Fax: 44663076
Details of the Unit Supplied Cluster-1 Ref: PHE-C1-B1-01 to 04 Model: AQ4L Unit Capacity: 1305 kW Quantity: 4 nos Cluster-2 Ref: PHE-C1-B1-01 to 04 Model: AQ4L Unit Capacity: 1118 kW Quantity: 4 nos
Details of the Unit Supplied Cluster-3 Ref: PHE-C3-B1-01 to 04 Model: AQ10T Unit Capacity: 1741 kW Quantity: 4 nos SC Ref: PHE-SC-B1-01 to 03 Model: AQ6L Unit Capacity: 1616 kW Quantity: 3 nos
Topics Heat Exchanger Basics System Description Operation and Maintenance Storage Startup/Shutdown Cleaning On Site Opening and Closing PHE Routine Checks Spare parts and their care Contact information
Heat Exchanger? A Heat exchanger is a device in which energy is transferred from one fluid to another across a solid surface.
Function - basics PHE = Plate Heat Exchanger Consists of a plate pack assembled into a frame The plates are pressed in a corrugated pattern Two plates creates channels in which the fluid flows in a turbulent manner The fluids are separated by the plates and heat is exchanged mainly by convection
Cold in Hot out Hot in Cold out Plate pack - example single pass End Plate II End Plate I Channel plates Only 2 plates that do not transfer heat - the endplates
PHE – Without insulation
Accessories Cooling insulation with drip tray
Operation and Maintenance How to handle your PHE
Routine operation checks Primary and Secondary Side Temperatures (4) Primary and Secondary Side Flows (2) Primary and Secondary Side Pressure Drops (2) Q= m p (cp) p ( Δ T in – Δ T out ) p = m s (cp) s ( Δ T in - Δ T out ) s Check visually for leakages Follow operation and Maintenance manual Mark the HEX serial number (301xx-xxxxx) on the Insulation, this is crucial information required when calling for service support!
Plate - parallel flow (Symmetrical flows only)
Supplier Contact details: Leminar Global Distribution & Services WLL P O Box 3841, Doha, Qatar Tel: +974 4467 3755 Fax: +974 4466 3076 Contact person: Robin Thomas Mob: + 974 66743314