Transformer Efficiency

ridwanalvee001 1,724 views 16 slides Mar 26, 2020
Slide 1
Slide 1 of 16
Slide 1
1
Slide 2
2
Slide 3
3
Slide 4
4
Slide 5
5
Slide 6
6
Slide 7
7
Slide 8
8
Slide 9
9
Slide 10
10
Slide 11
11
Slide 12
12
Slide 13
13
Slide 14
14
Slide 15
15
Slide 16
16

About This Presentation

Just like any other electrical machine, efficiency of a transformer can be defined as the output power divided by the input power. That is efficiency = output / input . Transformers are the most highly efficient electrical devices. Most of the transformers have full load efficiency between 95% to 98...


Slide Content

Transformer Efficiency Transformer Rating Transformer Regulation Condition for maximum Efficiency

Why Transformers are Rated in kVA, Not in kW? Rating of a transformer or any electrical machine reflects its load carrying capability without overheating. Core Losses of the transformer depends on Voltage ( V) and Copper losses ( I²R ) depends on Current (A) which passes through the transformer. That's why the rating of Transformer in kVA, not in kW. When a manufacturer makes a transformer, they have no idea of the type of load that will be used & consequently they can only rate the device according to its maximum current output that the conductors can safely carry (at unity Power Factor) & the insulation rating of the conductors (voltage & temperature). So the transformer is designed for rated voltage and rated current. We can't predict the power factor while designing the machine, because power factor depends upon the load which varies time to time. That’s why the Transformer Rating is expressed in kVA, not in kW.

Regulation of a Transformer The measure of how well a power transformer maintains constant secondary voltage over a range of load currents is called the transformer’s voltage regulation . It can be calculated from the following formula:

As the transformer is loaded, the secondary terminal voltage falls (for a lagging p.f .). Hence, to keep the output voltage constant, the primary voltage must be increased. Suppose primary voltage has to be raised from its rated value to ’, then  

Problem: A 250/500-V transformer gave the following test results : OC test : 250 V, 1 A, 80 W on low-voltage side. SC test : with low-voltage winding short-circuited :20 V; 12 A, 100 W . Determine the equivalent circuit parameters and insert them on the equivalent circuit diagram and calculate the full load efficiency when the output is 10 A at 500 volt and 0.8 power factor lagging. Solution. Open-circuit Test :

As and refer to primary, hence we will transfer these values to primary with the help of transformation ratio  

Efficiency of a Transformer Efficiency =   A better method is to determine the losses and then to calculate the efficiency from ; or It may be noted here that efficiency is based on power output in watts and not in volt-amperes, al- though losses are proportional to VA. Hence, at any volt-ampere load, the efficiency depends on power factor, being maximum at a power factor of unity.

Condition for Maximum Efficiency Considering primary side, or, η ….. (1) Differentiating both sides of equation (1) with respect to , we get  

Condition for Maximum Efficiency ….. (2) For η to be maximum, Hence, the equation (2) becomes or Iron loss = Cu loss

All- day Efficiency The ordinary or commercial efficiency of a transformer is given by the ratio But there are certain types of transformers whose performance cannot be judged by this efficiency; distribution transformers have their primaries energized all the twenty-four hours, although their secondaries supply little or no-load much of the time during the day except during the house lighting period. The performance of such is compared on the basis of energy consumed during a certain time period, usually a day of 24 hours

Problem: A 10 kVA, 500/250 V, single-phase transformer gave the following test results: S.C. Test (H.V. side) : 60 V, 20 A, 150 W The maximum efficiency occurs at unity power factor and at 1.20 times full-load current. Determine full-load efficiency at 0.80 p.f . Also calculate the maximum efficiency. Solution. Full-load current on H.V. side = 10,000/500 = 20 Amp S.C. test has been conducted from H.V. side only. Hence, at unity p.f . , full-load copper-loss is = 150 watts Maximum efficiency occurs at 1.2 times of full-load current, So, at unity p.f . corresponding copper loss is = x 150 = 216 watts At maximum efficiency, copper-loss = core-loss = 216 watts   Corresponding Power-output = 1.2 x 10,000 x 1.0 = 12 kW Hence, maximum efficiency at unity P.f . = (12)/(12 + 0.216 + 0.2160) = 0.9653 = 96.53 %

Problem: A 10 kVA, 500/250 V, single-phase transformer gave the following test results: S.C. Test (H.V. side) : 60 V, 20 A, 150 W The maximum efficiency occurs at unity power factor and at 1.20 times full-load current. Determine full-load efficiency at 0.80 p.f . Also calculate the maximum efficiency. Solution (b) Full-load efficiency at 0.80 P.f . Output Power at full-load, 0.80 P.f . = 10,000 x 0.8 = 8000 W, constant core-loss = 216 W Corresponding copper-loss = 150 W Total losses = 366 W Hence, efficiency = (8000/8366) x 100 % = 95.63 %.

Conclusion

Say our substation is loaded to the maximum transformer capacity and we know it is delivering power at a poor power factor. Our options are: 1. unload the transformer by disconnecting loads from it, 2. buy a larger transformer, 3. provide additional cooling to it (this raises the transformer capacity) or 4. correct the power factor. Power Factor (P.F.) is the ratio of Working Power to Apparent Power. P.F. =  

Lagging and Leading Power Factors: In addition, there is also a difference between a lagging and leading power factor. A lagging power factor signifies that the load is inductive, as the load will “consume” reactive power, and therefore the reactive component Q is positive as reactive power travels through the circuit and is “consumed” by the inductive load. A leading power factor signifies that the load is capacitive, as the load “supplies” reactive power, and therefore the reactive component Q is negative as reactive power is being supplied to the circuit. If θ is the phase angle between the current and voltage, then the power factor is equal to the cosine of the angle, :