Unit –5 Testing of Transformers
32. Open circuit and Short circuit test
Open circuit and Short circuit test
Thecircuitconstants,efficiencyandvoltageregulationofatransformer
canbedeterminedbytwosimpletests
(i)open-circuittestand
(ii)short-circuitlest.
Thesetestsareveryconvenientastheyprovidetherequiredinformation
withoutactuallyloadingthetransformer.
Further,thepowerrequiredtocarryoutthesetestsisverysmallas
comparedwithfull-loadoutputofthetransformer.
Thesetestsconsistofmeasuringtheinputvoltage,currentandpowerto
theprimaryfirstwithsecondaryopen-circuited(open-circuittest)andthen
withthesecondaryshort-circuited(shortcircuittest).
Open-Circuit or No-Load Test
Thistestisconductedtodeterminetheironlosses(orcorelosses)and
parametersR0andX0ofthetransformer.
Inthistest,theratedvoltageisappliedtotheprimary(usuallylow-voltage
winding)whilethesecondary(HVwinding)isleftopencircuited.
TheappliedprimaryvoltageV1ismeasuredbythevoltmeter,thenoload
currentI0byammeterandno-loadinputpowerW0bywattmeterasshown
inFig.
Asthenormalratedvoltageisappliedtotheprimary,therefore,normaliron
losseswilloccurinthetransformercore.
Hencewattmeterwillrecordtheironlossesandsmallcopperlossinthe
primary.
Sinceno-loadcurrentI0isverysmall(usually5to6%ofratedcurrent).
Culossesintheprimaryunderno-loadconditionarenegligibleascompared
withironlosses.
Hence,wattmeterreadingpracticallygivestheironlossesinthetransformer.
Itisremindedthatironlossesarethesameatallloads.
Open-Circuit or No-Load Test
Short-Circuit or Impedance Test
ThistestisconductedtodetermineR01(orR02),X01(orX02)andfull-
loadcopperlossesofthetransformer.
Inthistest,thesecondary(usuallylow-voltagewinding)isshort-circuited
byathickconductorandvariablelowvoltageisappliedtotheprimaryas
showninFig.