BSI BS*3875i: PART*L b5 m Lb24669 0052775 2 m
B,S. 3871 : 1965
A
The opening time shall not exceed three minutes.
NOTE. Where circuit-breakers are fitted with optional extra features such as shunt trip
coils, auxiliary contacts, etc., the relevancy of this Clause should be the subject of agreement
between manufacturer and purchaser.
-- 30. -- & -__ For circuit-bieakers, __ types 1, 2-3-and 4, sadubmitted for this te&
shall have bEiiteped to check that they will not tripswithin two hours when
~~JI-Y&I~ rated cuqent; and that tfie opening the at-1.5 times rated curr.ent,
fQKsircg~~reakers rated up to
and includine 1[1 ZWIID. a nd 1. 5 times rated!
-_ current, for circuit-breakers rat- above ~ 10 ~p,~~mplies withF-a
SHORT-CIRCUIT CAPACITY TESTS (GENERAL) A’-
--~ --
.
-
cpecifiedh SugdaGër26717 __
~ --_b__--
For circuit-breakers, types B, C and D, saiiiples subinitted for this test shall
have been tested to check that when
a current of 1.13 I,, is passed through all
poles for the time specified
in Table 5, the’circuit-breaker does not trip and
when the current is then increased within
5 s to 1.45 I,, the circuit-breaker
.
,sco,ic,,i~(ed
.\In?: 1981 - - --
As
altered
No v.
1974
shall trip within ___ the - time specified in Table 5;
b. The metal support on which the circuit-breaker is mounted, together with
all metal parts normally earthed in service, shall
be connected to the neutral
through
a tine wire fuse having a minimum length ot‘75 mm. The fuse shall be,
a tinned coppcr wire not greater
than 0.125 mm diameter and shall remain
intact at the conclusion of the complete series
of tests.
c. During all breaking capacity tests cheesecloth shall be applied to the
exterior of the circuit-breaker
as indicated below.
The cheesecloth shall be clean and
dry, bleached, plain cotton, approximately
30-40 grams per square metre. When placed in position the cheesecloth shall
be folded loosely in such a manner that cut’or tom edges will not be exposed
directly
to the arc or flash.
There shall
be no ignition of the cheesecloth. The material may be changed
during the series of tests.
(i) For circuit-breakers intended to
be used in an enclosure, cheesecloth
shall be placed on the outside of the enclosure at all openings, handles, etc.,
and inside the enclosure wherever
insulated conductors may be located, care
being taken not to block the vents.
(ii) For circuit-breakers not intended to
be used in an enclosure, cheese-
cloth shall
be placed at all openings, handles, etc., care being taken not to
block the vents.
(iii) Circuit-breakers
so constructed that they may or may not be fitted
in an enclosure shall be tested as in (i¡) above.
d. Ail poles of multi-pole circuit-breakers shall be tested simultaneously, the
test circuit being arranged
io represent a normal condition under balanced
loading. In addition, tests shall
be made on individual poles of multi-pole
circuit-breakers in accordance with Subclause
31g.
more than 110 per cent of the rated voltage. The recovery voltage shali be not
less than 95 per cent nor more than 105 per cent of the rated voltage and shall
I
e. The applied voltage shall be not less than 100 per cent and shall be not I ..
-
22
COPYRIGHT British Standards Institute on ERC Specs and Standards
Licensed by Information Handling Services
COPYRIGHT British Standards Institute on ERC Specs and Standards
Licensed by Information Handling Services