Chiller Plant Design Course for mechanical engineer

azly81 127 views 17 slides Aug 23, 2024
Slide 1
Slide 1 of 17
Slide 1
1
Slide 2
2
Slide 3
3
Slide 4
4
Slide 5
5
Slide 6
6
Slide 7
7
Slide 8
8
Slide 9
9
Slide 10
10
Slide 11
11
Slide 12
12
Slide 13
13
Slide 14
14
Slide 15
15
Slide 16
16
Slide 17
17

About This Presentation

This course provides a comprehensive understanding of chiller plant design, focusing on the theoretical and practical aspects of creating energy-efficient, sustainable, and reliable chiller systems. Participants will learn about different types of chillers, including air-cooled and water-cooled chil...


Slide Content

Chiller Plant Design

Table of Content Introduction Typical Piping Design Concepts Plant Sizing Plant Power & Control System

Introduction Chiller plant produces chilled water at set temperature (typically 6.7 oC /44oF) Distributed to Air Handling unit or Fan Coil Unit. Minimized refrigeration charge inside the building. Higher specific heat of water means lower energy required and volume for energy delivery.

Type of compressor Scroll <60TR Reciprocating <100TR Screw 70-500TR Centrifugal 300-3000 TR

What? Heat rejection method Air cooled Using Air cooled condenser Water cooled Using water cooled condenser and cooling tower Type: Shell & tube Tube & tube (refrigerant to water) Fin and tube (Refrigerant to air)

Typical Piping Design Concept Series & Parallel chillers Chiller configuration

Series & Parallel Chiller LOAD LOAD Characteristics -Series: Single flow higher delta T -Parallel: Double flow standard delta T

Chilled Water Plant Type

Water Cooled Chilled Water Plant -Dedicated pumping

Water Cooled Chilled Water Plant -Common pumping

Air Cooled Chiller Plant -Common pumping

Water Cooled Chilled Water Plant -Primary Secondary loop

Water Cooled Chilled Water Plant -Variable Primary Flow

Plant Sizing Plant capacity must consider maximum and minimum anticipated load. Base load chiller can be provided to cater for base load (usually night load). Alternatively independent system can be provided to serve base load e.g server room, control room, security room etc. Minimum chiller operating load shall be considered. Screw compressor >12.5% Centrifugal ≈ >30% (above surging range) Operating chiller frequently at low load may cause chiller freezing and coil burst due to expansion Higher chiller capacity better efficiency.

Short Exercise AHU load AHU 1: 30 TR (8 hrs ) AHU 2: 50 TR (8hrs) AHU 3: 20 TR (24 hrs ) No plant shut down allowed Determine Each AHU chilled water flowrate . Chiller capacity Cooling tower capacity Chilled water pump flowrate Condenser water pump flowrate Make-up water tank capacity (2% losses) Expansion tank capacity (assume 25 cu.m volume of pipe) This is hypothetical case only. In real condition, water cooled chiller is not available at that capacity.

The End