Rate of Rise of Re-striking Voltage (RRRV):
The transient voltage that appears across the contacts of the circuit breaker
at the current zero period during arcing is known as Restrikingvoltage.
Theexpressionforthere-strikingvoltageisV
C
(t)=V
m
(1−cosω
n
t)
The maximum value of the re-striking voltage occurs att = π / ω
n
= π √ L C
The maximum value of re-striking voltage = 2 V
m
= 2 ×peak value of the
system voltage.
The rate of rise of re-striking voltage (RRRV)= d/dt[ Vm(1− cosω
n
t) ]
∴RRRV = V
mω
n
sin ω
n
t
The rate of rise of re-striking voltage is directly proportional to the natural
frequency.
R RRV ∝ω
n
∝1 √ L C
Where L is the inductance of the system
C is the capacitance of the system
So, the rate of rise of re-striking voltage (RRRV) is dependent upon both
the inductance and capacitance of the system.
Now, the maximum value of RRRV occurs when ω
n
t= π/2 i.e. when
t = π/2ω
n
∴The maximum value of RRRV = V
m
ω
n
= V
m
/ √ L C
RRRV
max
= V
m
/ √ L C
RRRV is measured in kV /μ-sec.
Advantages:
(i) Due to the superior arc quenching property of
SF6, such circuit breakers have very short arcing
time.
(ii) Since the dielectric strength of SF6 gas is 2 to 3
times that of air, such breakers can interrupt
much larger currents.
(iii) TheSF6 circuit breakergives noiseless
operation due to its closed gas circuit and no
exhaust to atmosphere, unlike the air blast circuit
breaker.
(iv) The closed gas enclosure keeps the interior dry
so that there is no moisture problem.
(v) There is no risk of fire in such breakers because
SF6 gas is non-inflammable.
(vi) TheSF6 Circuit breakershave a low
maintenance cost, light foundation requirements
and minimum auxiliary equipment.
(vii) Since SF6 breakers are totally enclosed and
sealed from the atmosphere, they are particularly
suitable where explosion hazard exists e.g., coal
mines.
Disadvantages:
(i)SF6 breakers are costly due to the high cost of SF6.
(ii) Since SF6 gas has to be reconditioned after every
operation of the breaker, additional equipment is required for
this purpose.
Minimum Oil Circuit Breaker (Low oil
Circuit Breakers) (MOCB)
In case of bulk oil circuit breaker, the oil is used for two
functions.
-Firstly it acts as an arc-quenching medium and
-Secondly it insulates the live parts from earth.
But for arc extinction purpose a very small amount of oil is
sufficient while the major part is utilized for insulation
purposes.
Thus the oil required in case of bulk oil circuit breaker is
large and need frequent replacement.
This increasesthe overall cost; tank size and weight of or
the breaker.
Above drawbacks of bulk oil circuit breakers are removed
in minimum oil circuit (also known as MOCB) breaker in
which a small quantity of oil is used for arc extinction and
for insulation purpose.
Advantages:
1. It requires a very little amount of oil.
2. Less amount of oil means the risk of fire hazards
is low.
3. It has low weight.
4. It has small size and takes up small space
5. It is cheaper than BOCB.
6. It has easier maintenance and oil can be easily
replaced.
7. Best for installation in places where it is not
frequently used.
Disadvantages:
1.Lesser oil is more affected by the amount of
carbonization from the contacts.
2.The oil quickly losses its dielectric strength..
3.It requires more frequent maintenance.
Axial Blast Circuit Breaker:
Under Normal Condition
The fixed and moving contacts are held in a closed
position with the help of spring pressure.There is
an airreservoirconnected to the arcing chamber
through an air valve.
Theairvalvecontrolstheflowofairintothearcing
chamber.Thevalveisclosedundernormalconditions.