About This Presentation

It is a project on pure electrical engineering. Here three phase motor is starting from star to delta automatically by using some components.In other hand it also provide protection to the motor.


Slide Content

WELCOME

STAR-DELTA AUTO STARTER WITH FORWARD REVERCE AND MOTOR PROTECTION PROJECT GUIDE :- Prof . Sibananda Mishra (HOD Dept.EE ) PREPAIRED BY:- Bhupatibhakti manas Pradhan (1501298212) Arabinda Sahoo (1621298008) Jagannath Sahoo (1621298062) Trilochan Gochhayat (1621298051)

CONTENTS INTRODUCTION OBJECTIVES OF PROJECT STAR DELTA STARTING OF MOTOR WHY STAR TO DELTA IS USED STAR-DELTA AUTO STARTER FORWARD AND REVERSE OPERATION OF MOTOR PROTECTION OF MOTOR COMPONENTS AND THEIR WORKING METHOD OF OPERATION STEPS TO OPERATE ADVANTAGES OF AUTO STARTER OVER DOL STARTER MODEL INFORMATION COST ANALYSIS CONCLUSION REFERENCES

INTRODUCTION M ain purpose of any starter is to reduce the requirement of high starting current. Normally the starting current of an induction motor is 6 to 7 times of the full load current . Starters are employed to reduce the starting current. The  forward reverse motor control is used in a system where  forward and backward or upward and downward movement in the operation are needed. Forward and Reverse Operation of motor can be obtained by interchanging any two of its three terminals.  Motor protection is used to prevent damage to the electrical motor, such as internal faults in the motor. Faults like single phase protection, overload protection and over current protection.

OBJECTIVES OF PROJECT Perform forward and reverse operation of motor. Auto starting of motor from star to delta. Single switch operation. Provide protection to the motor. Single phase protection Over current protection / Overload protection Short circuit protection

STAR DELTA STARTING OF MOTOR Star Delta Starter, which is sometimes called as Y – Δ Starter , is a common type of Reduced Voltage Starter. I n a Star Delta Starter, the initial connection of the stator windings is in the form of Star . As the motor accelerates and gains speed, the stator windings are disconnected from the Star configuration and connected in the form of Delta.

The equation shows that star delta starter reduces the starting torque to one-third of that produced by DOL starter. The star-delta starter is equivalent to an autotransformer with a 57.7% tapping. Current relation between STAR connection and DELTA connection T orque relation between STAR connection and DELTA connection

WHY STAR TO DELTA STARTING IS USED? In STAR condition I L = I Ph V L = √3 V Ph So, I L ↑ T ↑ S ↓ In DELTA condition I L = √3 I Ph V L = V Ph So, I L ↓ T ↓ S ↑ B1 B B1 Y1

Advantages of Star Delta Starter Inexpensive No heat is produced, or tap changing device needs to be used, hence efficiency increases. Starting current reduced to 1/3 of direct online starting current. Produce less torque. Disadvantages of Star Delta Starter Starting torque is reduced to 1/3 of full load torque. A particular set of motors required.

STAR-DELTA AUTO STARTER The project is designed to provide low voltage start to induction motors. This is achieved by using star to delta conversion. Star/Delta starters are probably the most common reduced voltage starters in the 50Hz industrial motor world. Star delta is used in an attempt to reduce the start current applied to the motor. Thereafter, full load current is applied to the motor. The Star/Delta starter is generally manufactured from three contactors; and electromechanical timer. The main difference between manual star delta starters and automatic star delta starters is the automatic switching from Star Connection to Delta Connection based on predefined time intervals. A Time Delay Relay is used to obtain the necessary time before switching from Star to Delta. Depending on the capacity of the motor and its load conditions, the time delay can be more or less around 10 seconds.

FORWARD AND REVERSE OPERATION OF MOTOR The forward reverse motor control is used in a system where forward and backward or upward and downward movement in the operation are needed. Forward and Reverse Operation of motor can be obtained by interchanging any two of its three terminals.

PROTECTION OF MOTOR Phase Loss Protection / Phase Imbalance Protection A three-phase motor can continue operating if one of the phases is lost. However, this causes a considerable mechanical stress on the equipment while also increasing the current of the two operational phases. This condition may cause a motor to fail prematurely . Protection against phase loss and imbalance is accomplished with an auxiliary circuit, just like phase failure relay is used. Typically, phase imbalance must not exceed 2% in order to guarantee optimal motor performance . 2.Over load / over current protection An overload is a condition in which currents above the rated value are present, but unlike a fault current, overloads may be of just a few amperes over the rated current. Nevertheless, overloads can cause irreversible damage due to the amount of heat released. 3.Short-circuit protection A short circuit occurs when current travels along an unintended path, often where essentially no (or a very low) electrical impedance is encountered. Short circuit protection is protection against excessive currents or current beyond the acceptable current rating of equipment and it operates instantly. As soon as an overcurrent is detected, the device trips and breaks the circuit.

4.Under Voltage Protection / Over Voltage Protection Electric motors are designed to operate within a specific voltage range, and any voltage outside that range will cause problems that shorten the service life of the motor: Under-voltage makes the motor draw a higher current, to be able to keep up with the load. Over time, this damages the motor and it also causes the inrush current to be higher. Over-voltage saturates the ferromagnetic cores, which also increases the line current . 5 .Bidirectional protection When a motor running in one direction it is impossible to reverse the direction of motor immediately due to interlocking condition.

COMPONENTS AND THEIR WORKING 1.Contactor Unlike general-purpose relays, contactors are designed to be directly connected to high-current load devices. Relays tend to be of lower capacity and are usually designed for both normally closed and normally open applications. Unlike relays, contactors are designed with features to control and suppress the arc produced when interrupting heavy motor currents. when current passes through the electromagnet a magnetic field is produced which attracts the moving core of the contactor.

2.Timer time delay relays (TDRs) can provide simple, reliable, and economical control. Adjusting the delay time is often as simple as turning a knob. Providing time-delayed switching to start a motor, control a load, or affect a process, TDRs are typically used in industrial applications. Additionally, they play an important role for targeted logic needs, such as in a small panel or in sub-panels. They have a variety of features and operating characteristics, such as compactness, economy, simplicity, and ease-of-use . ON Delay timer OFF Delay timer

3.Singlephase failure The Phase Failure Relay is a phase-voltage-balance monitoring device designed for use with magnetic controls to automatically prevent three phase motors or other equipment from operating or attempting to start up under open phase or single-phase conditions, thereby eliminating burnouts and consequent down-time frequently incurred by phase failure Phase Failure Relay is not a thermal device. It operates on the principle of phase voltage unbalance which may occur in a three phase system. It also protects against phase loss.

4.Miniature circuit breaker (MCB) We use more commonly miniature circuit breaker or MCB in low voltage electrical network instead of fuse. The MCB has some advantages compared to fuse. It automatically switches off the electrical circuit during abnormal condition of the network means in over load condition as well as faulty condition. The fuse does not sense but miniature circuit breaker does it in more reliable way. MCB is much more sensitive to over current than fuse . The operating principle of MCB is simple. An  MCB function by interrupting the stability of electrical flow through the circuit once an error is detected. In simple conditions this circuit breaker is a switch which routinely turns off when the current flows through it and passes the maximum acceptable limit. 3 Pole MCB Single Pole MCB

5.DPDT Switch 6.Push button In industrial and commercial applications, push buttons can be connected together by a mechanical linkage so that the act of pushing one button causes the other button to be released. In this way, a stop button can "force" a start button to be released. This method of linkage is used in simple manual operations in which the machine or process has no  electrical circuits  for control.

7.Contactor Add-On block It is used for adding an NO / NC to the contactor according to the requirement. Add-on block work as an extension of contactor. 8.Cable tray In the electrical wiring  of buildings, a cable tray system is used to support insulated electrical cables used for power distribution, control, and communication. Cable trays are used as an alternative to open wiring or electrical conduit systems, and are commonly used for cable management in commercial and industrial construction. 9.Din rail A  DIN rail  is a metal rail of a standard type widely used for mounting circuit breakers and industrial control equipment inside equipment racks. These products are typically made from cold rolled carbon steel sheet with a zinc-plated or  chromated  bright surface finish. Although metallic, they are meant only for mechanical support, and are not used as a bus bar to conduct electric current, although they may provide a chassis grounding connection

10.Metal casing Metal casing means a structure made up of metal where the components are placed for safety and maintenance purposes. L= 40cm W= 25cm H= 20cm 11.Connector A connector is a device used to join electrical circuits and are also referred to as electrical connectors.

METHOD OF OPERATION In this starter there is two type of connection is established, one is called control circuit and another is power circuit. Control circuit is for controlling and switching purposes. And power circuit is used for three phase supply according to requirement. CONTROL CIRCUIT

FORWARD MOTORING When supply is given and start push button is pushed contactor K1,K3 is energised and timer get started, so that forward condition is applied and connection is become Star. After 15sec contactor K3 is de-energised and K4 is energised so the connection is become delta. Y Y Y Y

REVERSE MOTORING When supply is given and start push button is pushed contactor K1,K3 is energised and timer get started, so that forward condition is applied and connection is become Star. After 15sec contactor K3 is de-energised and K4 is energised so the connection is become delta. Y Y Y

POWER CIRCUIT

STEPS TO OPERATE Step 1: Provide the supply to the circuit. Step 1: Select the mode of operation i.e. forward motoring or reverse motoring by using a SPDT switch. Step 2: Check the phase failure relay, whether red LED is glowing or not. If LED is turn red then everything is ok to start the process, otherwise there is a fault in three phase supply. Step 3: Start the process by pushing START push button. Step 3: Wait 15sec to turn the connection from star to delta automatically. Step 4: After the work is done press the Stop push button.

ADVANTAGES OF AUTO STARTER OVER DOL STARTER It is an automatic process where Start connection is converted to Delta connection automatically after 15sec. Star Delta auto starter reduces the starting torque 1/3 of the DOL starter. Due to inter-locking system when a motor is running in on direction , It is impossible to reverse the direction of motor by switching the SPDT switch. Single switch operation. Operation is smooth and simple. It provides protection to the motor followed by the auto starter. It is modified easily according to the motor requirement. Low maintenance.

MODEL INFORMATION RATING PLATE 415V – 440V

PHYSICAL OVERVIEW

COST ANLYSIS Sl. No Component Name No Of Unit Price 1 contactor 4 ( 4*820 ) ₹3280 2 Contactor add-on block 2 ( 2*310 ) ₹620 3 Phase failure relay 1 ₹550 4 Timer delay relay 1 ₹800 5 3P MCB 1 ₹620 6 1P MCB 1 ₹380 7 Push button 2 ( 2*100 ) ₹200 8 SPDT switch 1 ₹30 9 Connector 3 point 1 ₹10 10 Connector 6 point 1 ₹20 11 Connecting wire As per requirement ₹250 12 Cable tray ( 25mm*25mm ) 2 ( 2*60 ) ₹120 13 Din rail 1 ₹70 14 Metal casing L= 40cm W= 25cm H= 20cm 1 ₹1200 15 Transparent fibre plate L=40cm W=25cm 1 ₹100   TOTAL   ₹8250

CONCLUSION In this project a three phase device is designed or constructed, due to which starting of a three phase sq cage induction motor is done automatically. It also gives an option to choose between forward motoring and reverse motoring. In other hand it provides protection to the motor. Three phase auto starter converts STAR connection into DELTA connection after 15sec from the starting of device. Star Delta auto starter reduces the starting torque 1/3 of the DOL starter. It provides options to select forward motoring and reverse motoring according to the requirement. In addition to this process it provides the protection to the three phase motor are; Phase protection, over voltage protection, over current protection, short circuit protection , Bidirectional protection .etc .

REFERENCES STAR-DELTA STARTER ,Islamic university of gaza,PLC lab, Eng.Mohammed s. jouda . ENERGY CONSERVATION USING STAR-DELTA STARTER, IRJET, D.M. Bokde , S.S. Jalkote , M.V. Birajdar , Asst. Prof. R.S.Biradar . AUTOMATIC STAR DELTA STARTER USING RELAY AND ADJUSTABLE ELECTRONIC TIMER FOR 3 PHASE INDUCTION MOTOR , Apoorva , anurag dwivedi , vishwas chaudhri , pradnya chauhan , R.s. deasi . AUTOMATIC STAR DELTA STARTER USING RELAY WITH AN ELECTRONIC ADJUSTABLE TIMER,TRPCS, Swapnil R. Badge, Nitin M. Sonune , Akshay P. Wakekar , Hemant S. Ulmale , Rugved R. Deshmukh . THREE PHASE INDUCTION MOTOR, module 8, IIT Kharagpur . ELECTRICAL MACHINE- II,vssut . CLOSE DIFFERENTIAL UNDER VOLTAGE RELAY, LAKESHORE electric corporation. PHASE FAILURE RELAY, RMS technology. PHASE FAILURE RELAY-PHASE PHEE, Prok devices private limited. TIMER AND TIMES SWITCHES, CSM technology. CONTACTORS AND RELAYS, Eaton wiring manual 06/11. MOTOR PROTECTION PRINCIPLES, craig wester , ge multilin . AN INTRODUCTION TO ELECTRIC MOTORS, life augmented.

ANY QUERY ?