32
are YNyn0 type transformer. These transformers are charged to 0CA board through segregated phase
bus duct (SPB)
UNIT switchboard OCA: it is 6.6KV 2500A board. Power is coming out from ST through SPB.
In this board, there are two sections, one for ST-1 and another for ST-2. From this board, power is
going to two gas compressor motor in sec-1(3840KW) but in sec-2, there is one gas compressor motor
service switchgear (2000KVA,3000A,6.6K/.433KV),raw water switchgear(1600KVA,6.6/.433
KV,2500A),administrative building PMCC (1600,2500 A,6.6/.433KV), gas station
PMCC(1600,2500A,6.6/.433KV),spare transformer feeder(2000KVA,6.6/.433KV), spare motor
feeder(3840 KW). In SEC-2, the entire portion is same as SCE-1. There are 4 ties connected to 0CA,
in sec-1 two ties is connected, one for 1CA & another for 2CA, and in sec-2, again two ties are
connected. One is for 1CB & another for 2CB.
A bus coupler is connected in between sec-1 and sec-2.
1. GAS STN PMCC (gas station PMCC): It is a 1600KVA, 2500A, 6.6/.433KV board. Power
comes in this board through step down transformer, which steps down the voltage 6.6 kV to
415 V. from transformer power is fed to this board through NSPB. In this centre power is
coming from both sec-1 & sec-2 through transformer
2. RAW WATER SWITCHGEAR: It is a 1600KVA, 2500A, 6.6/.433KV board. Power comes
in this board through step down transformer, which steps down the voltage 6.6KV to 415 V.
from transformer power through NSPB. In this centre power is coming from both sec-1 and
sec-2 through transformer. Power goes to ETP MCC,fire water MCC,
DM plant MCC, hydrogen plant MCC
i. ETP MCC (effluent treatment plant MCC): it is a 400 V, 400 A board. In this board power
is coming from both part of raw water switchgear. In this centre, fuse is used as a bus coupler
and also as a protection purpose of this board of lower current.
ii. FIRE WATER MCC: It is a 400V, 400 A board. In this board power is coming both part of
raw water switchgear. In this centre, fuse is used as a bus coupler and also as a protection
device because of low power.
iii. DM PLANT MCC: It is a 400 V, 630 A board. In this board power is coming from both part
of raw water switchgear. In this centre, fuse is used as a bus coupler and also as protection
purpose of thus board, because of lower power.
iv. HYDROGEN PLANT MCC: It is a 400 V, 250A board. In this board power is coming from
both part of raw water switchgear. In this centre, fuse is used as a bus coupler and also as
protection purpose of this board, because of lower current.
3. ADMINISTRATIVE BUILDING PMCC: It is a 1600KVA, 2500A,6.6/.433 KV board. Power
comes in this board through step down transformer, which steps down the voltage 6.6 KV to 415 V.
From transformer power is fed to this board through NSPB. In this centre power is coming from both
sec-1 and sec-2 through transformer. From this centre power goes to training hostel DB (Distribution
Board)(415 V ,125 A) and security hostel DB (415V,125 A)