Whatareshallow foundations?
Ifasoilstratumnearthesurfaceiscapableof
adequatelysupportingthestructuralloadsitis
possibletouseshallowfoundations.
Arbitrarydefinition: Shallow foundations referto
those whered/B<1orwhend<3m (accordingto
CP4).
B
13
d
Whatareshallow foundations?
Examples of shallow foundations:
■
Spreadfootings
Afooting
supportinga
singlecolumn
isreferred as
anindividual
footingor
pad.
14
Astripfooting
supportsaload
bearingwall.
Shallow foundations transfer the structural load to the soil
by spreading the load laterally and therefore the term
“spread footing”. A spread footing supports a single column.
Whatareshallow foundations?
■
Raft/matfoundations
17
A raft is a special footing that supports several randomly
spaced columns or several rows of parallel columns. They
usually occupy the footprint of the entire building.
Whataredeepfoundations?
Examples of deep foundations:
(a)PrecastRCpile
(b)SteelH-pile
(c)Steeltubularpile
21
(d)Shellpile(e)CFApile (d)Under-reamedboredpile
ShallowvsDeepFoundations
(Coduto2001)
22
Inshallow
foundations,load
transferisby
lateralspreading
i.e.endbearing
throughpassive
resistanceofsoil
Indeepfoundations,side
resistancebecomesthe
dominantloadtransfer
mechanismcomparedto
endbearing.
Deep foundationstransfer most of the applied structural loads to
deeper strata
Foundation Selection and Design Criteria
The type of foundation most suitable for a given
structure depends upon several factors:
1.Function of structure and the loads it must carry
2.Subsurface conditions
3.Cost of the foundation in comparison with the
cost of the superstructure
23
The foundation design must satisfy the following
criteria:
25
1.Factor of safety/Resistance w.r.t.collapse of building
or failure of the foundation is adequate both during the
construction and the life of the structure
2.Settlements at working load are sufficiently small that
they do not affect the function of the building
3.Adverse effects on adjacent structures and on the
environment are as small as possible during
construction as well as during the life of the structure
Numberof boreholes
29
EN 1997-2:2007 –Appendix B recommends for:
1.High-rise and industrial structures: grid pts at 15m
–40m spacing
2.Large area structures: grid pts at ≤ 60m spacing
3.Linear structures (e.g.roads, railway, tunnels etc.):
20m –200m
4.Special structures (e.g.bridges, stacks, machine
foundations): 2 –6 pts per foundation
5.Dams and weirs: 25m –75m along relevant section
ShallowFoundations
30
Soilsgenerallyfailinshear:
31
ModulusofElasticityE,ShearModulusG
x
32
z z
E
1
''
E
1
x
'
x
'
z
xzzxxz
G
33
Typical Values of Poisson’s Ratio for Soils and Rocks
BearingCapacity
34
Ultimate bearing capacity, q
ult
, is the least pressure that would
cause shear failure of the soil immediately below or adjacent to a
foundation.
Allowable bearing capacity, q
a
, is the maximum pressure that may
be applied to the soil such that:
1.settlement is limited to a tolerable amount, and
2.ultimate bearing capacity is not exceeded
Bearing capacity (q
f
) is defined as the pressure which would cause
shear failure of the supporting soil immediately below and adjacent
to a foundation.
Shear Failure modes
Threedistinctmodes:
35
General shear
Local shear
Punching shear
BearingCapacity
Punchingshear:
Punchingshearfailureoccurswhenthereis
relativelyhighcompressionofthesoilunderthe
footing,accompaniedbyshearinginthevertical
directionaroundtheedgesofthefooting.Thereis
noheavingofthegroundsurfaceawayfromthe
edges,andnotiltingoftheofthefooting.Relatively
largesettlementsarealsocharacteristicofthis
modeandagainq
f
isnotwelldefined.
Punchingshearfailurewillalsooccurinasoiloflow
compressibilityifthefoundationislocatedat
considerabledepth.
39
q
f
= ?
Commoncauseoffoundationproblems
Lackor inadequate
site investigation
40
In case of the leaning tower of Pisa where
inadequate soil tests were performed,
even though they might have saved
money in the process, it jeopardized the
stability of the structure and therefore led
to the ultimate loss of levelling.
Such practice can seriously lead to a
complete collapse of a structure.
UltimateBearingPressure/Capacity,q
f
41
-Maximumbearing pressure that the soil can
sustainbeforebearingcapacityfailure.
The resistance for the general shear bearing
capacity failure can be derived
Upperboundapproach,mechanismUB1
Energydissipatedduetoshearingatrelative
velocityv
i
alongsliplineoflengthL
i
:
E
i
f
L
i
v
i
WorkdoneW
i
byapressureq
i
actingoveran
areaperunitlengthB
i
movingatvelocityv
i
:
W
i
q
i
B
i
v
i
52
Upperboundapproach,mechanismUB1
Hodograph
53
v 2 v 2
v 2
v 2
Upperboundapproach,mechanismUB1
E
i
dissipatedEnergyv
i
RelativevelocityL
i
Length
fi
StresslineSlip
c
u
Bvv2B/2c
u
OA
2c
u
Bv2vBc
u
OB
c
u
Bvv2B/2c
u
OC
c
u
Bvv2B/2c
u
AB
c
u
Bvv2B/2c
u
BC
TotalEnergyDissipated,E
i
=6c
u
Bv
-v
54
E
i
f
L
i
v
i
Energydissipated:
Upperboundapproach,mechanismUB1
Energydissipated:
Workdone:
E
i
dissipatedEnergyv
i
RelativevelocityL
i
Length
fi
StresslineSlip
c
u
Bv2vB/2c
u
OA
2c
u
Bv2vBc
u
OB
c
u
Bv2vB/2c
u
OC
c
u
Bv2vB/2c
u
AB
c
u
Bv2vB/2c
u
BC
TotalEnergyDissipated,E
i
=
55
6c
u
Bv
W
i
doneWorkv
i
velocityRelativeB
i
Areap
i
PressureComponent
q
f
BvvBq
f
Footing
pressure
-
q
Bv-vB
q
Surcharge
q
f
Bv-
q
BvTotalWorkDone,W
i
=
W
i
q
i
B
i
v
i
Upperboundapproach,mechanismUB1
56
q
f
q
Bv6c
u
Bv
q
f
6c
u
q
W
i
E
i
Upperboundapproach,mechanismUB2
q
f
2
c
u
q
W
i
E
i
q
f
q
Bv
2
c
u
Bv
E
i
dissipatedEnergyv
i
RelativevelocityL
i
Length
fi
StresslineSlip
c
u
Bvv2B/2c
u
OA
c
u
Bvv
fan
= v2R=B/2c
u
Fanzone
c
u
Bvv2B/2c
u
OC
TotalEnergyDissipated,E
i
=
58
(2+)c
u
Bv
BearingCapacityinUndrainedMaterials
59
Analysisusingthelowerboundtheorem
Inthelowerboundapproach,theconditions ofequilibrium
andyieldaresatisfiedwithoutconsiderationofthemodeof
deformation.
2 2
4
f u q u
f u q
q z c z c
q c
Lowerboundapproach,stressstateLB2
60
c
u
1
=
f
+ z
3
=
q
+ z
2
f u q u u
f u q
q z c z c c
q c
ComparingUpperandLowerBoundsq
f
LowerBoundUpperBound
4c
u
q
6c
u
q
1
2
c
u
q
2
c
u
q
2
61
BearingCapacityFactors (Undrained)
Generalformofbearingcapacityofashallowfoundation
onanundrainedmaterial maybewrittenas:
q
f
s
c
N
c
c
u
q
Wheres
c
=shapefactor,forstripfooting=1.0
N
c
=bearingcapacityfactor=(2+)
d
62
Foundingplane
q
d
BearingCapacityFactors(Undrained)
B
d
N
c
2
10.27
Salgadoetal.(2004):
Eqn(a)
L
63
Eurocode7:
c
s10.2
B
BL
Inpractice,N
c
islimitedatavalue
of9.0foradeeplyembedded
squareorcircularfoundation.
Eqn(b)
a and b
N
c
= 9.0
Terzaghi’sBearingCapacityFormula
for undrained material
64
q
f
s
c
c
u
N
c
q
s
c
Footingshape
1.0Continuous
1.3Square
1.3Circular
N
c
=5.7–differentassumptions
BearingCapacityFactors (Undrained)
For two layer soil,
Merifieldetal.(1999)
SolidlinesforUB,dashedlinesforLB
65
MerifieldandNguyen(2006)
forsquarefootings
Note:incalculatingq
f
,c
u
=c
u1
BearingCapacityFactors (Undrained)
Forstripfooting closeto aslope,
Georgiadis(2010)
Lowestupperboundsolution
Not the exact solution
66
BearingCapacityFactors (Undrained)
ForGibson’ssoil:c
u
(z)c
u0
Cz
DavisandBooker(1973)
67
f z
CB
q 2 F
4
u
c
BearingCapacityFactors (Undrained)
68
Bearingcapacityisaffectedby:
(a)Equation used
(b)Depth of embedment
(c)Layeredsoil
(d)Proximityofslope
Astripfoundation 2.0mwide islocatedatadepthof2.0 m
inastiffclayofsaturatedunitweightof21kN/m
3
.The
undrainedshearstrengthisuniformwithdepth,withc
u
=
120kPa.Determinetheundrainedbearingcapacityofthe
foundationunderthefollowingconditions:
69
(a)
Thefoundationisconstructedinlevelground;
(b)
Acuttingatagradientof1:2issubsequentlymade
adjacenttothefoundation,withthecrest1.5mfromthe
edgeofthefoundation.
Example 1
Solution (1a)
d=2.0m
Foundingplane
q
d
21kN/m
3
2.0m
42kN/m
2
B=2.0mc
u
=120kPa
70
B2.0
UsingSkempton'svalues,N
c
6.4
Forstripfooting,s
c
1.0
d
2.0
1.0
6.4
q
f
s
c
N
c
c
u
q
1.0x6.4x120
42
810kPa
Solution (1b)
2.9
2.0
1.5
0.75
o
120
B
21
2.0
26.6
1
2
tan
c
u
1
71
d=2.0m
Foundingplane
q
d
21kN/m
3
2.0m
42kN/m
2
B=2.0mc
u
=120kPa
B=1.5m
1
2
Interpolating,N
c
4.7
4.7
q
f
s
c
N
c
c
u
q
1.0x4.7x120
42
606kPa
q
f
s
c
N
c
c's
q
N
q
'
q
0.5Bs
N
77
GeneralBearingCapacityforDrainedMaterials
(Coduto2001)
d
’
q
q
f
s
c
d
c
N
c
c's
q
d
q
N
q
'
q
0.5Bs
d
N
GeneralBearingCapacityforDrained Materials
78
2
(Salgado2008)
(EC7)
N
2
N
q
1
tan'
N
N
q
1
tan
1.32'
tan
q
1+ sin
N e
1- sin
q
c
N 1
N
tan
As'0,Nc
q q
c
q
S N 1
S
N 1
q
B
S 1+ sin
L
B
S 1- 0.3
L
q
f
s
c
N
c
c's
q
N
q
'
q
0.5Bs
N
GeneralBearingCapacityforDrained Materials
79
d
c
,d
q
,d
–depthfactors.EC7doesnotrecommendtheuseofdepthfactorsi.e.
d
c
=d
q
=d
=1.0
2
(Salgado2008)
(EC7)
N
2
N
q
1
tan'
N
N
q
1
tan
1.32'
tan
q
1+ sin
N e
1- sin
q
c
N 1
N
tan
As'0,Nc
q q
c
q
S N 1
S
N 1
q
B
S 1+ sin
L
B
S 1- 0.3
L
Case1:
Case2:
Case3:
d
’
q
80
GeneralBearingCapacityforDrained Materials
'
w
Case1:d
w
d
Case2:d<d
w
<d+B
'Case3:d+Bd
w
1
w
w
d d
B
d
w
=depthofgroundwatertable
Unitweighttobeused 0.5Bs
N
Example2
Afooting 2.25mx2.25mislocatedatadepthof1.5min asandfor
whichc’=0and ’=38
o
.Determinethebearing resistancefor:
(a)ifthegroundwater tableiswellbelowthe foundation level,and
(b)ifthegroundwatertableisatthe groundsurface.Theunitweightof
thesandabovethe groundwater tableis18kN/m
3
;thesaturatedunit
weightis 20kN/m
3
.
(notusedasc'0)
For
'38
o
,
81
(notusedasc'0)
tan
q
1+ sin
N e 49
1- sin
q
c
N 1
N
tan
N
2
N
q
1
tan= 75
q q
c
q
S N 1
S
N 1
q
B
S 1+ sin
L
B
S 1- 0.3 = 0.7
L
Solution2(a)
(a)ifthegroundwatertableiswellbelowthefoundationlevel
q
f
s
q
N
q
'
q
0.5Bs
N
s
q
N
q
d0.5Bs
N
1.62x49x 18x 1.5
0.5x 18x2.25x0.7x75
3206kPa
Case 3
82
(b)ifthegroundwatertableisatthegroundsurface
s
q
N
q
'd0.5'Bs
N
1.62x49x
20-9.81
x 1.5
0.5x
209.81
x2.25x 0.70x75
1815kPa
q
f
s
q
N
q
'
q
0.5Bs
N
Case 1
Terzaghi’s Bearing CapacityFormulas
q
ult
cN
c
zD
N
q
0.5BN
83
Terzaghi’s Bearing CapacityFormulas
q
ult
s
c
cN
c
zD
N
q
0.5s
BN
s
s
c
Footingshape
1.01.0Continuous
0.81.3Square
0.61.3Circular
84
Terzaghi’sBearingCapacityFormula for
undrained material
q
f
s
c
c
u
N
c
q
Terzaghi’s Bearing CapacityFormulas
Approximate formulaby Coduto
2
N
q
2
q
c
a
2
q
10.4sin4'
2
N1
tan'
1
cos'
tan'
for'0
tan'
N1
N
for'0N
c
5.7
tan'
360
o
'
whereaexp0.75
2
2 cos 45
2
'
o
N
K
p
N
85
86
Example 1 –A square footing is to be constructed as shown inFigure
below. The groundwater table is at a depth of 50 ft below the ground
surface. Compute the ultimate bearing capacity and the column load
required to produce a bearing capacity failure.
19kN/m
3
0.6m
1.0m
7kPaD
19kN/m
3
0.6m
11.4kPa
For ' 30
o
:N37.2,N22.5,N20.1
zD
q
ult
1.3cN
c
zD
N
q
0.4BN
1.3
7kPa
37.2
11.4kPa
22.5
0.4(19kN/m
3
)
1m
20.1
338.5256.5152.8
748kPa
c q
87
Example 1(cont’d)
A
0.6m
ult
3
f
P W
f
q q
23.6kN/m
14.2kNW
1m
1m
748
P 14.2kN
(1m)(1m)
P 733.8kN
“Nearly half of this capacity comes from the first term in the bearing
capacity formula and is therefore dependent on the cohesion of thesoil.
……it is prudent to use conservative values of c’ in bearing capacity
analyses. In contrast, the frictional strength is more reliable and does not
need to be interpreted asconservatively.”
88
Example 2 –The proposed continuous footing shown in the Figure belowwill
support the exterior wall of a new industrial building. The underlying soil is an
undrained clay, and the groundwater table is below the bottom of the footing.
Compute the ultimate bearing capacity,and compute the wall load required to
cause a bearing capacityfailure.
D
18kN/m
3
0.4m
7.2kPa
For 0
o
:N5.7,N1,N0
zD
q
ult
s
u
N
c
zD
N
q
0.4BN
120kPa
5.7
7.2kPa
1
0.5(18kN/m
3
)
0.7m
0
6847.20
691kPa
c q D=
89
Example 2(cont’d)
The zone above the bottom of the footing is partly concrete
andpartlysoil.The weight of this zone is small compared
to the wall load, so compute it using (18+23.6)/2 21
kN/m
3
as the averaged.
q
2b
ult
33
P
11kN/m
3
691kPa
b
0.7m
P 473kN
P
W
f
q
bb
B
21kN/m
11kN/m
W
f
0.4m1.1m
0.7m
90
Vesic’s Bearing CapacityFormulas
q
ult
cN
c
s
c
d
c
i
c
b
c
g
c
zD
N
q
s
q
d
q
i
q
b
q
g
q
0.5BN
s
d
i
b
g
91
Notation for Vesic’sload inclination, base inclination, and ground inclination factors. All angles are expressed
in degrees
Vesic’s Bearing CapacityFormulas
92
Vesic’s Bearing CapacityFormulas
BearingCapacity
Factors
GroundInclination
Factors
BaseInclination
Factors
N
N
q
1
for'0
c
tan'
N
c
5.14for '0
Ne
tan'
tan
2
45
o
'
q
2
N
2
N
q
1
tan'
g1
c
147
o
gg
1tan
2
q
b1
c
147
o
tan'
2
b
q
b
1
57
o
93
GroundwaterEffects
ApparentCohesion
Soils may be unsaturated, additional shear
strength contribution due tosuction.
Sampling disturbance, storage and handling
conditions may alter water content and change
the shearstrength.
Pore WaterPressure
94
GroundwaterEffects
q'
ult
c'N
c
s
c
d
c
i
c
b
c
g
c
'
zD
N
q
s
q
d
q
i
q
b
q
g
q
0.5'BN
s
d
i
b
g
95
Three groundwater cases for bearing capacity analyses
GroundwaterEffects
'
w
Case 1: D
w
D
Case 2: D < D
w
<D+B
'
Case 3: D+B D
w
q'
ult
c'N
c
s
c
d
c
i
c
b
c
g
c
'
zD
N
q
s
q
d
q
i
q
b
q
g
q
0.5'BN
s
d
i
b
g
q
ult
q'
ult
u
D
For totalstressparameters,
T
and c
T
,
q
ult
c
T
N
c
s
c
d
c
i
c
b
c
g
c
zD
N
q
s
q
d
q
i
q
b
q
g
q
0.5BN
s
d
i
b
g
96
w
w
D D
1
B
GroundwaterEffects
B
w
B
D
w
D
B
B
D
w
D
w
+
97
w
w
D D
1
B
q
50
L
s10.4
B
10.4
30
0.76
L
50
s1
B
tan'1
30
tan30
o
1.35
'
zD
Du
D
18.5
10
0185kPa
For ' 30
o
:N18.5,N22.4
9.4kN/m
3
Example 3 –A 30-m by 50-m mat foundation is to be built as shown
in the Figure below. Compute the ultimate bearingcapacity.
Case2:DD
w
DB
q
q
d1
d12ktan'
1sin'
2
12
0.33
tan30
o
1sin30
o
2
1.10
q
ult
'
zD
N
q
s
q
d
q
0.5' BN
s
d
u
D
185
18.4
1.35
1.10
0.5
9.4
30
22.4
0.76
1.0
0
7455kPa
(Check q
ult
using undrained strengthparameters)
Using Vesic'smethod:
98
w
w
D D
1
B
12 10
9.81 1
30
Allowable BearingCapacity
F
q
a_net
q
ult _ net
99
Factors affecting the deign factor of safety, and typical values of F
Example 4 –A column has the following design vertical loads: P
D
=1335 kN,
P
L
=623 kN will be supported on a spread footing located 0.9 m below the
ground surface. The underlying soil has an undrained shear strength of 96 kPa
and a unit weight of 17 kN/m
3
. The groundwater table is at a depth of 1.2m.
Determine the required footing width to maintain a factor of safety of 3 against
a bearing capacityfailure.
D
P
D
P
L
13356231958kN
UsingTerzaghi'smethod(Square footing):
For0,N
c
5.7,N
q
1.0
zD
D
17
0.9
15.3kPa
q
ult
1.3s
u
N
c
zD
N
q
1.3
96
5.7
15.3
1.0
727kPa
P1335kN
q
0.9m
3F
q
B
2
a
22 3
f
a
B 3m
A
195821.2B
2
242
P W
f
W
B
23.6 kN/m
21.2B
727
242kPa
Determinedesignworkingloadasworstcaseof:
q
ult
100
Bearing Capacity on LayeredSoils
Evaluate bearing capacity based on lowest
values of c’, ’ and in the zone B below the
footing –mostconservative
Use weighted values c’, ’ and based on
layer thickness in the zone B below the
footing –may or may not beconservative
Use a series of trial failure surfaces similar to
slope stability analysis. The trial failure
surface that gives the lowest q
ult
is the critical
failure surface –complexanalysis
101
Example 5 –Using the second method, compute the factor of safety
against a bearing capacity failure in the square footing shown below.
102
EC 7 –Limit statedesign
The characteristic value of a geotechnical
parameter shall be selected as a cautiousestimate
of the value affecting the occurrence of the limit
state.
108
Example 6.4 –A column has the following design vertical loads: P
D
=1335 kN,
P
L
=623 kN will be supported on a spread footing located 0.9 m below the
ground surface. The underlying soil has an undrained shear strength of 96 kPa
and a unit weight of 17 kN/m
3
. The groundwater table is at a depth of 1.2m.
Determine the required footing width according to EC 7 Approach 1
Combination1.
Factoredload:
P
D
D
P
L
L
1335
1.35
623
1.5
2734 kN
Vertical effectof actions: E
d
27341.35W
f
kN
Design strength of soil
s
u
96
96kPa
γ
m
1
EC7partialfactorsassumeHansenbearingfactorsasbasis
forbearingcapacitycalculations(Square footing):
For0,N
c
5.14,N
q
1.0,s
c
1.3
q
ult
forlimitstates
u
N
c
s
c
q
96
5.14
1.3
0.9(17) 657 kPa
Bearing resistance R
d
657
B
B
657BkN
2
A
ult
657B
2
273428.7B
2
B 2.1m
qforlimitstate
27341.35W
f
109
Foundations with Eccentric or Moment Loads
These are called eccentric loads, and they produce a non-
uniform bearing pressure distribution. Assuming a linear
distribution of the bearing pressure, the eccentricity, e, of the
bearing pressure is given by
L
f
Pe
e
P W
where
e = eccentricity of bearing pressure distribution
P = applied vertical load (or the same per unit length for continuous footings)
e
L
= eccentricity of applied vertical load
W
f
= weight of footing (or the same per unit length for continuous footings)
M = applied moment load (or the same per unit length for continuous footings)
or
f
M
e
P W
110
One-Way Eccentric or Moment Loading
If the eccentric or moment loads occur only in the B direction,
then the bearing pressure distribution
Distribution of bearing pressure beneath
footings with various eccentricities:
(a) e < B/6;
(b) e = B/6; and
(c) e > B/6.
111
One-Way Eccentric or Moment Loading
If e B/6 the bearing pressure distribution is trapezoidal, as shown in Figure a,
the minimum and maximum bearing pressures on square or rectangular
foundations are:
where;
q
min
= minimum bearing pressure
q
max
= maximum bearing pressure
P = column load
A = base area of foundation
u
D
= pore water pressure along base of foundation
e = eccentricity of bearing pressure distribution
B = width of foundation
min
6
1
f
D
P W e
q u
A B
max
6
1
f
D
P W e
q u
A B
If e = B/6 (i.e., the resultant force acts at the third-point of the foundation), then
q
min
= 0 and the bearing pressure distribution is triangular (Fig.b).
If e > B/6, the resultant of the bearing pressure acts outside the third-point and the
pressure distribution is as shown in Figure c
112
Two-Way Eccentric or Moment Loading
If the resultant load acting on the base is eccentric in both the B and L directions,
it must fall within the diamond-shaped kern shown in Figure b for the contact
pressure to be compressive along the entire base of the foundation.
Pressure distribution beneath spread
footing with vertical load
that is eccentric in both the B and L
directions;
where
e
B
= eccentricity in the B direction
e
L
= eccentricity in the L direction
6 6
1
f
D
P W e e
q u
A B L
113
A 3 m square footing supports a vertical column load of 200 kNand two moment
loads with axes parallel to the sides of the footing, each having a magnitude of 124
kN-m. The embedment of the footing is 1 m, and the groundwater table is at a great
depth.
Determine whether eccentric loading requirements will be met. If these
requirements are not met, determine the minimum footing width, B, needed to
satisfy these requirements.
Example 1
114
Therefore, a 3.6 m x 3.6 m square footing would be required to keep the
resultant within the kern.
115
Equivalent Uniformly Loaded Footing
When we have a footing with an eccentric or moment loading, it is
convenient, for computational purpose, to determine the dimensions of an
equivalent uniformly loaded footing.
The equivalent footing is a footing that carries the same applied load
as the original footing but has different dimensions such that the resulting
bearing pressure is uniform (Meyerhof, 1963; BrinchHansen, 1970).
This is accomplished by decreasing the
footing width, B, to an equivalent width, B,
and the length, L, to an equivalent length, L.
The equivalent dimensions Band Lare
selected such that the net resultant load acts
through the centroid of the equivalent
footing.
116
Equivalent dimensions Band L
First determine the eccentricities e
B
and e
L
from the applied load and moments
(Slide 1).
Next, check to ensure that the resultant footing load acts within the kern. If not,
increase B and L such that this criterion is satisfied. Then compute the
dimensions Band Lusing
B= B -2e
B
L= L -2e
L
The equivalent bearing pressure for this footing, q
eq
, will be greater than the
average bearing of the true footing and computed as:
f
eq
P W
q
BL
117
ShallowFoundations
Settlement
118
PerformanceRequirements
119
Strength
Geotechnical (For shallow foundations, this is
referred as bearingcapacity)
Structural
Serviceability
Constructibility
Economic
Introduction
Settlement analysis is important for shallow
foundations especially when B islarge.
Besides structural loading, settlement may
also be causedby:
Weight of recently placedfill
Lowering of groundwatertable
Underground mining ortunneling
Formation ofsinkholes
Secondarycompression
Lateral movements due to adjacentexcavation
120
Design Requirements forSettlement
a
D
Da
The values of allowable total settlement,
a
and
Da
depends on the type of structure supported by the
foundation.
and
D
arecomputed using the unfactored
downward loads (Actualloads).
121
Design Requirements forSettlement
122
Typical Allowable Total Settlements For Foundation Design
If the predicted settlement, , is greater than
a
, we could consider any or all ofthe
following measures:
1.Adjust the foundation design
2.Use a more elaborate foundation -Piles
3.Improve the properties of the soil –removal of compressible soil and replacing
it with engineering soils
4.Redesign the structure so it is more tolerant of settlements —For example,
flexible joints could be installed on pipes
Design Requirements forSettlement
123
Engineersnormallydesignthefoundationsforastructuresuch
thatallofthemhavethesamecomputedtotalsettlement.Thus,in
theory,thestructurewillsettleuniformly.Unfortunately,the
actualperformanceofthefoundationswillusuallynotbeexactly
aspredicted,withsomeofthemsettlingmorethanexpectedand
othersless.
Thedifferentialsettlement,
D
,isthedifferenceintotal
settlementbetweentwofoundationsorbetweentwopointsona
singlefoundation.Differentialsettlementsaregenerallymore
troublesomethantotalsettlementsbecausetheydistortthe
structure,
DifferentialSettlement
Therefore, we define a maximum allowable differential settlement,
Da
, and design
the foundations so that:
D
Da
SettlementAnalysis
124
Based on plate loadtest
Based on laboratory or in-situtests
Plate LoadTestProcedure Cont….
129
Aseatingloadofabout70gm/cm
2
isfirstappliedandreleased
aftersometime.Ahigherloadisnextplacedontheplateand
settlementsarerecordedbymeansofthedialgauges.Observations
oneveryloadincrementshallbetakenuntiltherateofsettlement
islessthan0.25mmperhour.
Loadincrementsshallbeapproximatelyone-fifthoftheestimated
safebearingcapacityofthesoil.
Theaverageofthesettlementsrecordedby2or3dialgaugesshall
betakenasthesettlementoftheplateforeachoftheload
increments.
The test should continue until a total settlement of 2.5 cm or the
settlement at which the soil fails, whichever is earlier, is obtained.
After the load is released, the elastic rebound of the soil should be
recorded.
Pressure
Settlement
25mm
130
q
a
Uses a plate size of approximately 0.3
m to 1m square or diameter. The
allowable bearing pressure for design
is taken as that corresponding to a
settlement of 1 inch (typically2.5cm).
131
If the sand were to behave like an elastic material, then the settlement could be calculated
from
where
p
p
is the plate settlement,
q
ap
is the applied stress,
B
p
is the width or diameter of the plate,
vis Poisson’s ratio,
Eis the elastic modulus, and
I
p
is an influence factor (0.82 for a rigid plate).
The settlement of the real footing () of width B is related to the plate settlement by
132
Load-settlement curve of a plate-load test
133
For a plate of 1 ft square, the above equation may be expressed as
134
ThepermissiblesettlementS
f
,foraprototypefoundation
shouldbeknown.Normallyasettlementof2.5cmis
recommended.Inaboveequations,thevaluesofS
f
,andbp
areknown.TheunknownsareS
p
andB.ThevalueofS
p
for
anyassumedsizeBmaybefoundfromtheequation.
Usingtheplateloadsettlementcurvethevalueofthe
bearingpressurecorrespondingtothecomputedvalueofS
P
isfound.
Thisbearingpressureisthesafebearingpressureforagiven
permissiblesettlementS
f
.Thevalueofimmediatesettlement
only.Iftheunderlyingsoilissandyinnatureimmediate
settlementmaybetakenasthetotalsettlement.Ifthesoilisa
clayeytype,theimmediatesettlementisonlyafractionofthe
totalsettlement.
Settlement Analyses by Lab or In-situ Test
137
Laboratory tests will involve some determination
of compressibility interms of amodulus
SPT and CPT has been commonlyused.
Especially suitable for sandy deposits where
sampling isdifficult.
Divide1.2mx1.2mfootinginto4equalquadrants(i.e.0.6mx0.6m).
141
z
2
f
B
2
L
2
f
222
1.5
2
0.6
2
0.6
2
z
2
f
B
2
L
2
f
B
2
BLz
0.0576
L
2
z
2
0.6
2
0.6
2
1.5
2
2.97
I
0.0602
Forthe4equalquadrants,
z
4I
q
zD
4
0.0602
1816
42kPa
A l.2m x 1.2m square footing supports a column load of 250 kN.The
bottom of this footing is 0.3m below the ground surface, the groundwater
table is at a great depth, and the unit weight of the soil is 19.0 kN/m3.
Compute the induced vertical stress,
z
, at a point 1.5 m below the
centreof this footing.
Example 2 –Using SimplifiedMethod
Forsquarefooting:
142
Example 2 –Using ApproximateMethod
144
Forsquarefooting:
SettlementAnalyses
145
Immediate settlement (independent oftime)
Consolidation settlement(time-dependent)
Secondary compression(time-dependent)
Total settlement = Immediate + consolidation +secondary
Immediatesettlement,S
e
,isthatpartofthetotalsettlement,S,
whichissupposedtotakeplaceduringtheapplicationofloading.
Theconsolidationsettlement,S
c
isthatpartwhichisduetothe
expulsionofporewaterfromthevoidsandistime-dependent
settlement.
Secondarysettlement,S
s
normallystartswiththecompletionof
theconsolidation.Itmeans,duringthestageofthissettlement,the
porewaterpressureiszeroandthesettlementisonlyduetothe
distortionofthesoilskeleton.
ImmediateSettlement
Skempton and BjerrumMethod:
Distortion settlement,
d
, (also called immediate
settlement, initial settlement, or undrainedsettlement)
146
Distortion settlement beneath a spread
footing
ImmediateSettlement
(Assumes0.5)
147
d 0 1
qB
E
I I
Influence factors for computing settlement (after Christian and Carrier, 1978).
where
q = average bearing stress (Total service load)
B = footing width
E = average soil modulus over depth of compressible layer
I
0
= influence factor accounting for footing depth
I
1
= influence factor accounting for footing shape and thickness
of compressible layer
ImmediateSettlement
148
100 E1500
(Duncan andBuchignani,1976)
Typically, E300s
u
d 0 1
qB
E
II
Chart for estimating the undrained modulus of clays based on
overconsolidationratio, plasticity, and undrained shear strength
Undrained
E
s
u
Drained
E= 0.67 1 E
where = 0.1 to 0.4
Immediate settlement –Cohesivesoils
For a uniformly loaded circular or rectangular areas
near the surface of a relatively deep stratum, the
vertical settlementis:
149
C
s
Shapeandrigidityfactor
quniformload
Bwidth offoundation
s
Poisson' s ratio ofsoil
E
s
Young' s modulusof soil
2
s
d s
s
1
CqB
E
C
s
for infinitedepth
150
AverageEdge / Middleof
longside
CornerCentreShape &Rigidity
0.850.641.0Circle(flexible)
0.790.790.79Circle(rigid)
0.950.760.561.12Square(flexible)
0.820.820.820.82Square(rigid)
Rectangle(flexible)
1.301.120.761.53L/B =2
1.821.681.052.10L/B =5
2.242.101.282.56L/B =10
Rectangle(rigid)
1.121.121.121.12L/B =2
1.601.601.601.60L/B =5
2.02.02.02.0L/B =10
C
s
for
limited
depth
over
Rigid
Base
151
Corner of Flexible RectangularAreaCentre of Circular
Area
(diameter=B)
H/B
L/B=∞L/B=10L/B=5L/B=2L/B=1
=0.50
0.00.00.00.00.00.00
0.040.040.040.040.050.140.5
0.100.100.100.120.150.351.0
0.180.180.180.220.230.481.5
0.260.260.270.290.290.542.0
0.270.380.390.400.360.623.0
0.520.540.550.520.440.695.0
0.730.770.760.640.480.7410.0
=0.33
0.00.00.00.00.00.00
0.080.080.080.080.090.200.5
0.160.160.160.180.190.401.0
0.250.250.250.280.270.511.5
0.340.340.340.340.320.572.0
0.450.450.460.440.380.643.0
0.610.610.600.560.460.705.0
0.810.820.800.660.490.7410.0
43200
B1.8m
1.8m
1.8m
A
1
z
h
B
0
u u
zD
f
152-11
1.8
0.98
0.7
4mm
I0.7
L
1,
B
I0.98
D
0.6m
0.3
43200kPaE300s300144kPa
0.6m
18kN/m
3
11kPa
q
P W
f
445kN 46kN
152 kPa
W(1.8m)(1.8m)(0.6m)(23.6kN/m
3
) 46kN
152
Example Find the allowable settlement for the proposed square footing in
Figure
d 0 1
qB
E
I I
Proposed square footing
One-Dimensional Consolidation Settlement –
ClassicalAnalysis
153
where
c
= ultimate consolidation settlement
r = rigidity factor
C
c
= compression index
C
r
= recompression index
e
0
= initial void ratio
H = thickness of soil layer
z0
= initial vertical effective stress at midpoint of soil layer
zf
= final vertical effective stress at midpoint of soil layer
c
= preconsolidation stress at midpoint of soil layer
'
zf
'
z0
z
Definition of OC-I andOC-II
CaseI CaseII
154
One-Dimensional Consolidation
Settlement –ClassicalAnalysis
155
r -VALUES FOR COMPUTATION OF TOTAL SETTLEMENT AT THE CENTER OF A SHALLOW FOUNDATION, AND METHODOLOGY
FOR COMPUTING DIFFERENTIAL SETTLEMENT
Entirefootingsettlesuniformly,solongasbearing
pressureisuniform.Computedifferential
settlementbetweenfootingsoralonglengthof
continuousfootingusingthetotalsettlement
analysisorthe
D
/ratiomethod
One-Dimensional Consolidation
Settlement –ClassicalAnalysis
156
APPROXIMATE THICKNESSES OF SOIL LAYERS FOR MANUAL
COMPUTATION OF CONSOLIDATION SETTLEMENT OF SPREAD FOOTINGS
Theclassicalmethoddividesthesoilbeneaththe
footingintolayers.Thebestprecisionisobtained
whentheuppermostlayeristhin,andtheybecome
progressivelythickerwithdepth
One-Dimensional Consolidation Settlement –
ClassicalAnalysis
157
Influence factors for induced vertical
stress under a semi-infinite strip load
Influence factors for induced vertical
stress under a square loaded area
Example –The allowable settlement for the proposed continuous
footing in the Figureis 25 mm. Using the classical method, compute its
settlement and determine if it satisfies thiscriterion.
158
zD
B1.2
W
f
18kN/m
3
0.5m
9kPa
P
W
f
q
bb
65 14
66kPa
1.2m
0.5m
23.6kN/m
3
14kN/m
P 65kN/m
Proposed footing
2.60
z zD 2
f
1
1 q -
B
1
2z
Example (cont’d)
23.40.040.13OCI3186951180.501.01
7.10.040.13OCI3365418361.501.02
2.90.040.13OCI61576512.751.53
1.60.040.13OCI75683654.502.04
0.70.050.15OCI487881877.003.05
35.7=
For continuous footing,
c
= r x 35.7mm = 0.85 x 35.7mm 31mm
c
= 31 mm>
a
Settlement criterion is notsatisfied
159
'
zf
'
z0
z
Skempton and BjerrumMethod
d
c
160
Settlement Analyses based on In-situTests
161
Standard Penetration Test(SPT)
Cone Penetration Test(CPT)
Dilatometer Test(DMT)
Pressuremeter Test(PMT)
Suitable method for all soil types,
especially suitable for sandy soils as they
are difficult tosample.
Settlement Analyses based on In-situ Tests
(cont’d)
162
Schmertmann’s Method (1970,1978)
Meyerhof’s Method(1965)
Burland and Burbidge’s Method(1985)
Schmertmann’s Method(cont’d)
Consider the soil from the base of the foundation
depth of influence below the base. Divide this zone into
several soil layers.
Compute the peak strain influencefactor,
164
zD
p
zp
I = 0.5 + 0.1
q
where
I
p
= peak strain influence factor
q = bearing stress
zD
= initial vertical effective stress at a depth D below the ground surface
zp
= initial vertical effective stress at depth of peak strain influence factor
(for square and circular footings (L/B = 1), compute
zp
at a depth of
D + B/2 below the ground surface; for continuous footings (L/B 10),
compute it at a depth of D + B)
Schmertmann’s Method(cont’d)
Compute the strain
influence factor, I
є
, in the
middle of each soillayer.
Soil layers are determined from
stiffnessprofile
166
Distribution of strain influence factor with
depth under square and continuous footings
(Adapted from Schmertmann1978)
Schmertmann’s Method(cont’d)
Compute the correction factors, C1, C2 andC3:
167
Footingshape,
Secondarycreep,
Depthfactor,
zD
1
zD
C = 1 - 0.5
q -
2
t
C = 1 + 0.2log
0.1
Compute thesettlement:
s
zD123
E
I
H
CCC
q
for t 0.1 year
3
L
1.03 0.03
C = max B
0.73
Schmertmann’s Method(cont’d)
168
where
= settlement of footing
C
1
= depth factor
C
2
= secondary creep factor
C
3
= shape factor
q = bearing stress
zD
= effective vertical stress at a depth D below the ground surface
I
e
= influence factor at midpoint of soil layer
H = thickness of soil layer
E
s
= equivalent modulus of elasticity of soil layer
t = time since application of load (year) (t 0.1 year)
B = footing width
L = footing length
These formulas may be used with any consistent set of units, except that t must be
expressed in years. Typicallywe use t = 50 years (C
2
= 1.54).
E
s
from CPTResults
169
ESTIMATING EQUIVALENT SOIL MODULUS, E
S
, VALUES FROM CPT
RESULTS [Adapted from Schmertmannet al. (1978), Robertson and
Campanella (1989), and other sources.]
E
s
from SPTResults
170
0.6
N
60
E
m
C
B
C
S
C
R
N
E
s
0
OCR
1
N
60
Example –The results of a CPT sounding performed at McDonald’s Farm near Vancouver,
British Columbia, are shown in Figure shown. The soils at this site consist of young, normally
consolidated sands with interbedded silts. The groundwater tables is at a depth of 2.0 m
below the ground surface.
171
A 375 kN/m load is to be
supported on a 2.5 m x 30 m
footing to be founded at a depthof
2.0 m in this soil. Use
Schmertmann’s method to
compute settlement of this footing
soon after construction and the
settlement 50 yearsafter
construction.
=17kN/m
3
=20kN/m
3
CPT results
Solution
1kPa0.0102kg/cm
2
172
From the Table, use E
s
= 2.5q
c
Depth of influence = D + 4B = 2.0 + 4(2.5) = 12.0 m
Example (cont’d)
W
f
2.5m
2.0m
23.6kN/m
3
118kN/m
59kPa
173
zp
zD
0.50.1
197kPa 34kPa
0.666
'
q
zD
I0.50.1
'
D
17kN/m
3
2m
34kPa
p
375kN/m 118kN/m –0
197kPa
2.5m
'
zp
atzDB
Hu
17kN/m
3
2m
20kN/m
3
2.5m
9.8kN/m
3
2.5m
59kPa
f
D
p w
q u
B
Example(cont’d)
174
Example 7.6(cont’d)
s
175
zD123
E
I
H
CCC
q
E
s
zD123
At t50yr,
At t = 0.1 yearC
2
1.0
C C C
q
I
H
Example (cont’d)
0.896
1.0
0.73
19734
35.73x10
5
38mm
176
zD
1
zD
34
C = 1 - 0.5 = 1 - 0.5 = 0.896
q - 197 - 34
3
3
L
C = 1.03 0.03 0.73
B
30
= 1.03 - 0.03x = 0.67 Use C = 0.73
2.5
0.896
1.54
0.73
19734
35.73x10
5
59mm
2
t 50
C = 1 + 0.2log = 1 + 0.2log = 1.54
0.1 0.1
Accuracy of SettlementPredictions
177
Uncertainties in defining soilprofile
Disturbances of soilsamples
Errors in in-situtests
Errors in laboratorytests
Uncertainties in defining serviceloads
Constructiontolerances
Errors in determining degree ofconsolidation
Inaccuracies in the analysismethodologies
Neglecting soil-structure interactioneffects
Accuracy of Settlement Predictions
(cont’d)
•
Settlement predictions are
more oftenconservative
•
Settlement predictions based
on Schmertmann’s method
with CPT data are more
reliable than with those based
onSPT.
•
Settlement predictions in
clays, especially clays that
are overconsolidated, are
usually more reliablethan
those insands.
178
Comparison between computed and measured settlements of spread footings. Each bar
represents the 90 percent confidence interval (i.e., 90 percent of the settlement
predictions will be within this range). The line in the middle of each bar represents the
average prediction, and the number to the right indicates the number of data points used
to evaluate each method (based on data from Burlandand Burbridge, 1985; Butler, 1975;
Schmertmann, 1970; and Wahls, 1985).