Unit 2 Reactive Power Management

1,925 views 35 slides Aug 20, 2020
Slide 1
Slide 1 of 35
Slide 1
1
Slide 2
2
Slide 3
3
Slide 4
4
Slide 5
5
Slide 6
6
Slide 7
7
Slide 8
8
Slide 9
9
Slide 10
10
Slide 11
11
Slide 12
12
Slide 13
13
Slide 14
14
Slide 15
15
Slide 16
16
Slide 17
17
Slide 18
18
Slide 19
19
Slide 20
20
Slide 21
21
Slide 22
22
Slide 23
23
Slide 24
24
Slide 25
25
Slide 26
26
Slide 27
27
Slide 28
28
Slide 29
29
Slide 30
30
Slide 31
31
Slide 32
32
Slide 33
33
Slide 34
34
Slide 35
35

About This Presentation

Subject-Power System Operation Control
Class-BE
Electrical Engineering


Slide Content

DEPARTMENT OF ELECTRICAL ENGINEERING JSPMS BHIVARABAI SAWANT INSTITUTE OF TECHNOLOGY AND RESEARCH , WAGHOLI, PUNE A.Y. 2020-21 (SEM-I) Class: B.E. Subject: Power System Operation Control Unit No-2 Reactive Power Management Prepared by Prof. S. D. Gadekar [email protected] Mob. No-9130827661

Content Introduction Power Triangle The Significance of Positive and Negative P & Q Necessity of Reactive Power Control Advantages of Power Factor Improvement at Load End Sources of Reactive Power Synchronous Alternator as a Source of Reactive Power Synchronous Motor as a Source of Reactive Power Loading Capability curve of a Generator Compensations in Power System Problems Associated with Series Compensation Comparison of Series and Shunt Compensation Loading Capability Curve of Generator

Introduction The required power supply to an electric circuit depends on, A ctive power  - real electrical resistance power consumption in circuit R eactive power  - imaginary inductive and capacitive power consumption in circuit The required power supply is called the  apparent power  and is a complex value that can be expressed in a Pythagorean triangle known as Power Triangle.

Power Triangle Power Triangle  is the representation of a right angle triangle showing the relation between active power, reactive power and apparent power.           When each component of the above phasor diagram is multiplied by the voltage V, a power triangle is obtained shown in the figure below,                

When an active component of current is multiplied by the circuit voltage V, it results in active power.it is this power which produces torque in the motor, heat in the heater, etc. This power is measured by the wattmeter. When the reactive component of the current is multiplied by the circuit voltage, it gives reactive power. This power determines the power factor, and it flows back and forth in the circuit. When the circuit current is multiplied by the circuit voltage, it results in apparent power. From the power triangle shown above the power factor may be determined by taking the ratio of true power to the apparent power.  

The Significance of Positive and Negative P & Q P Positive- AC System supplies real active power to network. P Negative-AC network supplies real active power to a three phase ac system. Q Positive-AC system supplies lagging reactive power to a ac network. The network consists of elements which are predominantly inductive. Q Negative-AC system supplies leading reactive power to a ac network. The network consists of elements which are predominantly capacitive.

Necessity of Reactive Power Control System losses due to reactive power flow The real power in three phase ac system is , The current is minimum if is unity, as power factor becomes less than unity, the circuit current increases.   Transmission Losses   The system needs to transmit reactive power due to the fact that most of the loads operates at lagging power factor. Examples Induction motor, Transformer, arc lamps, welding equipment's .

Necessity of Reactive Power Control 2. To meet the load requirement at a low power factor, the capacity of power plant, transmission and distribution equipment has to be more than would be necessary if the load were demanded at unity power factor. G   Bus 1 Bus 2       Unity Power Factor Load Case-1 Unity Power Factor Load            

Necessity of Reactive Power Control 2. To meet the load requirement at a low power factor, the capacity of power plant, transmission and distribution equipment has to be more than would be necessary if the load were demanded at unity power factor. G   Bus 1 Bus 2       Lagging Power Factor Load Case-1 Load At Lagging Power Factor          

Necessity of Reactive Power Control 3. For the same active power operation of an existing power system at low power factor means overloading the equipment at times of full load. 4. For the same active power , a low power factor means a greater current and hence higher energy losses. 5. The low power factor causes the voltage regulation to be poor.

Advantages of Power Factor Improvement at Load End Reduction in circuit current Increase in voltage level at load Reduction in copper losses in the system due to reduction in current Reduction in investment in the system facilities per kW of the load demand Improvement in power factor of the generators Reduction in kVA loading of the generators and circuits Reduction in kVA demand charges for large consumers

Sources of Reactive Power (VARS) Synchronous Machines (Alternator & Motor) Shunt Static Capacitors Series Capacitors Synchronous Condensers FACTS Controllers

Synchronous Alternator as a source of reactive power Consider the equivalent circuit of cylindrical rotor synchronous generator under steady state conditions. G     R   ) Where, E-Induced Emf R-Armature Winding Resistance per phase I-Current per phase   I

  E         Case-1 E Over excitation At Lagging Power Factor Positive P & Positive Q     E         Case-2 E Under Excitation At Leading Power Factor Positive P & Negative Q   I I

    G   Bus 1 Bus 2       Generalised Power System PF MW MVar 1 100 0.9 90 43 0.8 80 60 0.7 70 70 0.5 50 86.5 1 100 0.9 90 43 0.8 80 60 0.7 70 70 0.5 50 86.5 Rating of Synchronous Alternator is 100MVA  

Synchronous Motor as a source of reactive power Consider the equivalent circuit of cylindrical rotor synchronous motor under steady state conditions. M     R   ) Where, V-Supply AC Voltage E-Induced Emf in the motor R-Armature Winding Resistance per phase I-Current per phase   I  

  E         Case-1 E Under excitation At Lagging Power Factor           Case-2 E Over Excitation At Leading Power Factor   I I   E

Synchronous Motor as a source of Reactive Power When motor is under excited i.e power factor is lagging, the motor absorbs lagging VARs from the mains and delivers leading VARs. When motor is over excited i.e power factor is leading, the motor absorbs leading VARs from the mains and delivers lagging VARs . The synchronous motor can be made to deliver lagging or leading VARs to the system as per the system requirement. This can be done by controlling the excitation. Synchronous motor which do not supply any mechanical load and are used for supply of VARs are known as synchronous condenser.

Compensations in Power System Series Compensation It consists of capacitors connected in series with line at suitable locations. The effective reactance is given by Where = Line Reactance = Capacitor Reactance   G1       Uncompensated Transmission Line  

This results in improvement in performance of the system as Increase in Transmission Capacity This equation is called as power angle equation. The above equation shows that the power transmitted depends upon the transfer reactance and the angle between the two voltages .   b. Voltage drop in the line reduces (gets Compensated ) and thus it prevents voltage collapse. G1          

c. Improvement of System Stability For same amount of power transfer and same value of E and V , the δ in the case of series compensated line is less than that of uncompensated line . Compensated Transmission Line   Uncompensated Transmission Line   ,E and V in both the cases are same. A lower δ means better system stability.  

Compensations in Power System Shunt Compensation For high voltage transmission line the line capacitance is high and plays a significant role in voltage conditions of the receiving end. When the line is loaded then the reactive power demand of the load is partially met by the reactive power generated by the line capacitance and the remaining reactive power demand is met by the reactive power flow through the line from sending end to the receiving end . When load is high (more than SIL) then a large reactive power flows from sending end to the receiving end resulting in large voltage drop in the line. To improve the voltage at the receiving end shunt capacitors may be connected at the receiving end to generate and feed the reactive power to the load so that reactive power flow through the line and consequently the voltage drop in the line is reduced .

To control the receiving end voltage a bank of capacitors (large number of capacitors connected in parallel) is installed at the receiving end and suitable number of capacitors are switched in during high load condition depending upon the load demand. Thus the capacitors provide leading VAR to partially meet reactive power demand of the load to control the voltage. During light load or no load conditions the voltage at the receiving end of the line may even exceed the sending end voltage. This is due to the charging current drawn by the shunt capacitance of the line. To limit this voltage rise shunt reactors have to be used. Examples-Static Var Compensators(SVC), Static Synchronous Compensator(STATCOM), Synchronous Condenser.

Comparison of Series and Shunt Compensation Sr. No Series Compensation Shunt Compensation 1 In series capacitors the reactive power generation is proportional to square of the load current ( ). In series capacitors the reactive power generation is proportional to square of the voltage ( ). 2 The cost of installation of series capacitor is higher due to the complicated protective equipment. The cost of installation of shunt capacitor or reactor is lower. 3 Comparatively small rating capacitor can be used to achieved the same amount of voltage improvement. For the same voltage improvement the rating of shunt capacitor will be higher. 4 Series capacitors are generally employed to improve the stability of the system. Shunt capacitors are generally employed to improve the power factor of the system. Sr. No Series Compensation Shunt Compensation 1 2 The cost of installation of series capacitor is higher due to the complicated protective equipment. The cost of installation of shunt capacitor or reactor is lower. 3 Comparatively small rating capacitor can be used to achieved the same amount of voltage improvement. For the same voltage improvement the rating of shunt capacitor will be higher. 4 Series capacitors are generally employed to improve the stability of the system. Shunt capacitors are generally employed to improve the power factor of the system.

Comparison of Series and Shunt Compensation Objective Series Compensation Shunt Compensation Improving Power Factor Secondary Primary Improving voltage level in overhead line system with low power factor Primary Secondary Improving voltage level in overhead line system with high power factor Not Used Primary Reduces line losses Secondary Primary Reduces voltage fluctuations Primary Not Used

Location of Series Capacitor Location along the line In this method the capacitor bank is located at the middle of the line. Location at one or both ends of line section on the line sides of in the switching station Location between bus bars within the switching station

Problems associated with series compensations Sub synchronous resonance The natural frequency of oscillation for line elements series with series compensation is given by Where F is a system Frequency The series capacitor introduces a sub synchronous frequency (proportional to the square root of the compensation) in the system.  

Problems associated with series compensations 2. Ferro Resonance- When an unloaded or lightly loaded transformer is energized through a series compensation line, ferro resonance occurs. 3. Line Protection- Series compensation can lead to mal-operation of the distance relay of the line protection if the degree of compensation and capacitor location are not proper. 4. High Recovery Voltage- Capacitors bank produce high recovery voltages across the circuit breaker contacts.

Basics of Three Phase Synchronous Alternator Motor Generator Set- 2.2 kVA, 415V, 3.2 A, 220 V dc, Cylindrical Pole Alternator , 3 HP, 1500 rpm, 220 V, 12 A, DC Shunt Motor

Loading Capability Curve of a Generator The capability curve of a synchronous generator defines a boundary within which the machine can operate safely. The permissible region of operation is restricted to the following points given below. The MVA loading should not exceed the generator rating. This limit is determined by the armature of stator heating by the armature current. The MW loading should not exceed the rating of the prime mover. The field current should not be allowed to exceed a specified value determined by the heating of the field winding. For steady state or stable operation, the load angle must be less than 90 . The steady state stability limit occurs at .  

The Continuous reactive power output capability is limited by three considerations, Armature Current Limit- The armature current results in to an power loss and the energy associated with this loss must be removed so as to limit the increase in temperature of the conductor and its immediate environment. So the limitations on generator rating is the maximum current that can be carried by the armature without exceeding the heating limitations. Therefore on P-Q plane the armature current limit appears as the circle with centre at the origin and radius equal to the MVA rating.           Over excited Under excited Rated MVA         Over excited Under excited Rated MVA

The Continuous reactive power output capability is limited by three considerations, Field Current Limit- The heat resulting due to an power loss, the field current also imposes a second limit on the operation of the generator. During this analysis the resistance is neglected. The phasor diagram will become,     E       Case-1 E Over excitation At Lagging Power Factor Positive P & Positive Q   I      

Now multiply by to each phasor , the phasor diagram of alternator at lagging power factor will become.             I     O

mark the arc for minimum and maximum limit of field current   Min   Max     Min   Max