INTRODUCTION OF
SUBSTATION
It is situated at 26°34’2’’N & 80°32’57’’E coordinates
in Dahi Chowki 6.64 km far from Unnao railway station.
Constructed during 1994-98 by CGL.
The whole substation is divided in three parts:
132kv switchyard
400/220kv switchyard
765kv switchyard (Under construction)
2
INCOMING & OUTGOING LINE OF
SUBSTATION
•Unnao to Lucknow (400KV & 220KV both separate)
•Unnao to Bareily-1 (400KV)
•Unnao to Bareily-2 (400KV)
•Unnao to Agara (400KV)
•Unnao to Panki Kanpur(400KV & 220KV both separate)
•Unnao to Anpara (400KV)
•Unnao to PGCIL Lucknow-1 (400KV)
•Unnao to PGCIL Lucknow-2 (400KV)
•One bus bar for 400/220KV 315MVA ICT-1 & ICT-2 line.
3
OUTDOOR EQUIPMENT USED IN
SUBSTATION
Two 100MVA 220/132KV transformer
Two 315MVA 400/220KV transformer
Shunt reactor
Capacitor bank
SF6 circuit breaker
Isolators
Lightning arresters
Current transformer
Capacitor voltage transformer
Wave trap
Isolators
4
Transformer
H.V. side
bushing CT
COOLING SYSTEM
(ONAN)
ConservaterTank
L.V. side bushing
CTs
5
Oil pump
Oil pump is
used for
circulating oil
forcelly.
Radiator
plates are
used for
increasing
surface area
for natural air
cooling.
Radiator plates
Earthing
plate
6
Tertiary
terminal
Tertiary terminal mostly
opened.
The output voltage of
tertiary terminal is 11KV in
100MVA transformer and
33KV in 315 MVA
transformer
Pressure
relief valve
box
8
OLTC
chamber
9
TERMINALS ON TANK COVER
In these photos we can see fogging near transformer due to
operation fire protection system.
10
BUCHHOLZ RELAY
Buchholz relay is a safety device mounted on some oil-filled power
transformers and reactors. It is used as a protective device sensitive to
the effects of dielectric failure inside the equipment.
11
1. High Voltage terminal
2. Compensation reactor
3. Intermediate voltage
transformer
4. Ground terminal
5. Ferro-resonance
suppression device
6. Damping resistor
7. Carrier (HF) terminal
(optional)
8. Overvoltage protective
device
9. Secondary terminals
10. Link, to be opened for
test purposes
PRINCIPLE CIRCUIT DIAGRAM OF
CVT
17
CIRCUIT BREAKER
A circuit breakeris an
automatically-operated
electrical switch
designed to protect an
electrical circuit from
damage caused by
overload or short circuit.
In this image we can
see a SF6 circuit breaker
with double break
system.
18
ISOLATORS
An isolators switch are
used to completely de-
energized an electrical
circuit. High-voltage
isolation switches are used
in electrical substations to
allow isolation of apparatus
such as circuit breakers and
transformers, and
transmission lines, for
maintenance.
Isolating rod
Earth link rod
19
PANTOGRAPH ISOLATORS
In open state In close state
20
Central rotating double
break isolator
21
Wave trap
Wave trap are used in
power system for carrier
communication.
It trap the higher
frequency above 50Hz.
It is the effort to utilize
the same transmission line
between two substation for
the purpose of
communications
22
23
LIGHTNING ARRESTOR
The overvoltage protection
is obtained by the use of
lightning / surge arresters.
Lightning Arresters or
Surge Arresters are always
connected in Shunt to the
equipment to be protected,
they provide a low
impedance path for the
surge current to the ground.
Mostly in present days
zinc oxide (ZnO) gapless
arresters are in use.
24
INTERPOSING C.T.
The interposing CTs are used
for Power transformer
Differential Protection
circuit. In a delta/Star Power
transformer, the cts will be
connected star and delta
formation, for eliminating
Zero sequence current on star
side. There will be mismatch
of secondary current , to
maintain equilibrium,
interposing Cts will be
connected to Delta formed
CTs.
25
RELAYSDifferential
relay
O/F protection +FFR
Group A trip relay
CB trouble relay
Group B trip relay
DR earth switch
relay
O/C protection
relays
Breaker failure
relay
RES E/F +O/L
Protection relay
26
Relay testing boxA outer view of Relay
Relay conti….
27
SHUNT REACTOR
Shunt Reactor is a thyristor controlled high impedance
transformer.
A stable bus
voltage can be
maintained by
providing
variable reactive
power based on
the bus voltage
deviations due
to the load
variations.
28
SHUNT CAPACITOR
BANK
Shunt capacitor banks
are used to improve the
quality of the electrical
supply.
provide capacitive
reactive compensation.
Power factor correction.