Cable Sizing
Part 2
by febriansasi at gmail dot com

Cable Sizing
•Standard in my country using IEC standar
d
–Metric
–50Hz

Pick any cable from library

Pick any cable from library

Tick Load Amp to use standard cable ampacity
It means ETAP will select based on load FLA witho
ut concern with Voltage drop

Tick Vst Min to use calculated Voltage Start Minimum
It means ETAP will select based on Voltage Drop when Sta
rting Motor

Tick Short Circuit use calculated current withstand
It means ETAP will select based on shortcircuit current (we
will discuss later after I study about this)

Tick Short Circuit use calculated current withstand
It means ETAP will select based on shortcircuit current (we
will discuss later after I study about this)

Tick MF (multiplication factor)
It means ETAP will select based on multiplication factor reg
arding with the application (we will discuss later after I stud
y about this)

Tick Load Amp and Vst to combine the calculation
It means ETAP will select based on FLA and Voltage start

Load Flow

Change The cable sizing calculation

Using Motor starting simulation to calculate Vst
As we can see, even we set the Vst to 95% the result is 86.5%

Using Motor starting simulation to calculate
Vd Max

Motor reactive power demand

Motor real power demand