Current Transformer and Potential Transformer

ridwanalvee001 4,327 views 66 slides Mar 29, 2020
Slide 1
Slide 1 of 66
Slide 1
1
Slide 2
2
Slide 3
3
Slide 4
4
Slide 5
5
Slide 6
6
Slide 7
7
Slide 8
8
Slide 9
9
Slide 10
10
Slide 11
11
Slide 12
12
Slide 13
13
Slide 14
14
Slide 15
15
Slide 16
16
Slide 17
17
Slide 18
18
Slide 19
19
Slide 20
20
Slide 21
21
Slide 22
22
Slide 23
23
Slide 24
24
Slide 25
25
Slide 26
26
Slide 27
27
Slide 28
28
Slide 29
29
Slide 30
30
Slide 31
31
Slide 32
32
Slide 33
33
Slide 34
34
Slide 35
35
Slide 36
36
Slide 37
37
Slide 38
38
Slide 39
39
Slide 40
40
Slide 41
41
Slide 42
42
Slide 43
43
Slide 44
44
Slide 45
45
Slide 46
46
Slide 47
47
Slide 48
48
Slide 49
49
Slide 50
50
Slide 51
51
Slide 52
52
Slide 53
53
Slide 54
54
Slide 55
55
Slide 56
56
Slide 57
57
Slide 58
58
Slide 59
59
Slide 60
60
Slide 61
61
Slide 62
62
Slide 63
63
Slide 64
64
Slide 65
65
Slide 66
66

About This Presentation

One of the major difference between them is that the current transformer converts the high value of current into low value whereas the potential or voltage transformer converts the high value of voltages into low voltage.


Slide Content

INSTRUMENT
TRANSFORMERS

Uses and Definitions
•Usedinacsystemformeasurementofcurrent,
voltage,powerandenergy
•Usedinmeasuringpf,frequencyandindicationof
synchronism
•Transformerusedformeasurementpurposeiscalled
“InstrumentTransformers”
•Usedformeasurementofcurrent“Current
Transformer”“C.T.”
•Usedformeasurementofvoltage“Potential
Transformer”“P.T.”

Use of Instrument Transformer
•MeasurementofHighvoltagesandCurrents
•C.T. Primarywindingisconnectedwiththe
currentbeingmeasuredandsecondarywindingto
theammeter.CTstepsdownthecurrent.
•P.T. Primarywindingisconnectedwiththe
voltagebeingmeasuredandsecondarywindingto
thevoltmeter.PTstepsdowntheVoltage.
•Extensionofrangecanbedonebytheuseofshunt
forammeterandmultipliersforvoltage
measurementind.cmeasurement.Thismethodis
suitableonlyforsmallvaluesofcurrentandvoltage

Disadvantages of Shunt
•It is difficult to achieve accuracy using shunt in ac
•The method of using shunts is limited to capacities of
few hundred amperes since power consumption by
shunts would be large
•The problem of insulation of instrument and shunt is
quite difficult if measurements are done at high
voltages
•The measuring circuit is not isolated electrically from
the power circuit

Disadvantages of Multipliers
•Thepowerconsumptionislargeasthe
voltageincreases
•Constructionofmultiplierisverycostlyand
complicatedforhighvoltagetoprotect
leakagecurrent
•Themeasuringcircuitisnotelectrically
isolatedfromthepowercircuit

Adv of Instrument Transformers
•WheninstrumentsareusedinconjunctionwithInstrument
Transformers(IT)theirreadingdonotdependuponconstants
(R,L,C)asinthecaseofshuntandmultipliers.ITproduce
samereadingregardlessofconstants
•Verycheapmoderateratingmaybeusedtomeasurelarge
currentsathighvoltages(1000A/5AOR66kv/100to120v)
•WiththestandardizationofCTandPTsecondarywinding
ratingsitispossibletostandardizeinstrumentsaroundthese
ratings.ThereforegreatreductionofthecostofITand
Instruments
•Themeasurementcircuitisisolatedfromthemaincircuit
•ReplacementofITiseasyonaccountofthestandardizationof
theratings

ADVANTAGES OF IT
•Instrumentsofmoderatesizeareusedformetering
•Instrumentsandmeterscanbestandardizedsothat
thereissavinginoverallcosts.Replacementofdamaged
instrumentiseasy
•Singlerangeinstrumentscanbeusedtocoverlarge
currentorvoltagerangeswhenusedwithsuitablemulti-
rangeITorwithseveralsinglerangeIT
•Themeteringcircuitisisolatedfromthehighvoltage
powercircuit.Isolationandsafetyisassured
•Thereislowpowerconsumptioninmeteringcircuit
•SeveralinstrumentcanbeoperatedfromthesingleIT

RATIOS OF IT phasor
Ratio R
sec phasor
winding current
; a C.T.
secondary winding current
winding voltage
; a P.T.
secondary winding voltage

min Ratio K
n
primary
Transformation
ondary
primary
For
primary
For
rated pri
No al



winding current
; C.T.
rated secondary winding current
winding voltage
; P.T.
rated secondary winding voltage
mary
For
rated primary
For

No of turns of secondary winding
Ratio=n ; C.T.
No of turns of primary winding
No of turns of primary winding
; P.T.
No of turns of secondary winding
Ration Correcton Fac
Turns For
For


tor (RCF). RCF of a transfromer is the
transformation ratio divided by nominal ratio
Transformation ratio=Ratio correction factor x Nominal ratio
R=RCF x K ; the ratio marked on tfr is the Nominal Rat
n
 io RATIOS OF IT

Burden of IT
•Itisconvenienttoexpressloadacrossthesecondarywending
terminalsastheoutputinvolt-ampattheratedsecondary
windingvoltage.Theratedburdenisthevolt-amploading
whichispermissiblewithouterrorsexceedingthelimitsforthe
particularclassofaccuracy.
•Thetotalsecondarywindingburden2
2
(secondary winding induced voltage)
( of secondary winding ckt and secondary winding)
(secondary winding current) ( of secondary-
winding ckt and secondary winding)
win
impedance
x impedance
Secondary

2
2
ding burden due to load
(secondary winding terminal voltage)
=
( of load on secondary winding)
(secondary winding current) ( of load-
on secondary winding)
impedance
x impedance

CURRENT TRANSFORMER
•Primarywindingconsistsoffewturnsandis
connectedinserieswiththelinecarrying
current
•Secondarywindinghaslargernoofturns
andconnectedwiththeinstruments
•CToperatesitssecondarywindingnearly
undershortcircuitconditions

Relationship in a CT of secondary winding turns
Ratio=
of Primary winding turns
Re tan of the secondary winding
Re tan of the secondary winding
Re tan of the external burden (resitance of meter
s
s
e
No
n Turn
No
r sis ce
x ac ce
r sis ce



 , Curent coil, leads etc)
Re tan of the external burden (reactiance of meter, Curent coil, leads etc)
E Pr winding induced voltage;E winding in duced voltage
of Primary windin
e
ps
P
x ac ce
imary Secondary
N No


 g turns; of secondary winding turns
of secondary winding terminals,
s
s
N No
V Voltage

I secondary winding current; I Primary winding current
=phase angel of transformer; Working frux of transformer
between secondary winding induced voltage and secondary winding current
sp
Angle
pha





1
1
0
angle of total burden incl inpedance of secondary winding=tan
=phase angle of scondary winding load ckt/External burden=tan
current; I magnetizing component of exiting
se
se
e
e
m
xx
se
rr
x
r
I exiting





 current
I loss component of exiting current; =angle between exing current and working flux
e
 Relationship in a CT

Transformation Ratio0
0
0
00
0
00
2 2 2
2 2 2
00
2 2 2 2
0 0 0
90 ; ; ; and oc=
bc= sin(90 ) cos( );
cos(90 ) sin( )
, (oc) (oa+ab) (bc)
( ) [ sin( )] [ cos( )]
( ) sin ( ) 2 sin( ) c
sp
ps
ss
bac ac I oa nI I
II
ab I I
Now
I nI I I
nI I nI I I

   
   
   
   
     
    
    

     
     
2
22
00
2 2 1/ 2
00
os ( )
( ) 2 sin( )
[( ) 2 sin( ) ]
ss
p s s
nI nI I I
I nI nI I I




   
    

2 2 1/ 2
00
00
2 2 2 1/ 2
00
0
[( ) 2 sin( ) ]
Ratio=R=
a well designed CT ; Usually is less than 1 % of
[( ) 2 sin( ) sin ( )]
R
sin( )
p ss
ss
sp
ps
p ss
ss
s
s
I nI nI I I
Transformation
II
In I nI I I
I nI
I nI nI I I
II
nI I
n
I

   

  


   
  

  
=
0
0
00
sin( )
sin cos
(sin cos cos sin )
, cos and sin
s
me
ss
me
I
I
I I I
R n n
II
Where I I I I


   



     
 Transformation Ratio

Phase Angle
•Theanglebywhichthesecondarycurrentphasor
whenreversed,differsinphasefromtheprimary
current,isknownasthephaseangleofthe
transformer
•Thisangleistobetaken+veifthesecondarycurrent
reversedleadstheprimarycurrent.Theangleistaken
–veifsecondarycurrentlagsbehindtheprimary
current

Phase Angle0
0
0
0
0
angle between I reversed and I is . therfore the phse angle
I cos( )
tan
I I sin( )
I cos( )
is very small we can write,
I I sin( )
I is very small compa
sp
s
s
The
bc bc
ob oa ab n
As rad
n








   
  



0
0 0 0
red to I , we can neglect the term I sin( )
I cos( ) I cos cos I sin sin )
II
I cos I sin ) I cos I sin )180
deg
II
s
ss
m e m e
ss
n
rad
nn
rad x ree
nn

     

   



  



Error in CT
•Thevalueoftransformationrationisnotequaltotheturns
ratio.Thevalueisnotconstant;dependsuponthemagnetizing
andthelosscomponentoftheexcitingcurrent,thesecondary
windingloadcurrentanditspf.
•Thesecondarywindingcurrentisnotaconstantfractionofthe
primarywindingcurrentbutdependsupontheabovefactors
•Itisnecessarythatthephaseofthesecondarywindingcurrent
shallbedisplacedbyexactly180
0
fromtheprimarywinding
current.Thephasedifferenceisdifferentthanthatof180
0
by
theta
•Hencetwotypesoferror;oneduetoactualtransformationratio
beingdifferentfromtheturnsratioandtheotherdueto
secondarywindingcurrentnotbeing180outofphasewiththe
primarywindingcurrent

Ratio Error & Phase Angle Errormin ratio-Actual ratio
Percentage ratio errror= 100
Actual ratio
100
I cos I sin )180
angle error. Phase Angle = deg
I
Formula for Error
n
me
s
No al
x
KR
x
R
Phase x ree
n
Approximate






: The usual instrument burden is largely
resistive with some inductive and is positive and small
Hence sin 0 and cos 1
I180
= deg
I
I180
I I =n(1 ) And = deg
I
em
ss
e e m
ps
p p p
I
R n x ree
In
nI I
As n R n x
II







  
     ree

Characteristic of CT
Effect of PF of Secondary Winding Burden on Error
RatioError: Forinductiveburdensthesecondary
windingcurrentI
slagsthesecondaryinducedvoltageE
s
so,δispositive.Underthisconditiontheactual
transformationratioisalwaysgreaterthantheturnsratio
ForsufficientlycapacitiveI
sleadsE
sandδisnegative;the
actualTransformationratiodecreasesbecominglessthan
theturnratioforvaluesofδapproaches-90
0

•PhaseAngle:Forinductiveburden,the
phaseangleθispositiveforsmallvaluesofδ
(highpf)butbecomesnegativeasthesecondary
burdenbecomesmoreinductiveandδapproaches
90
0
•Fornegativevaluesofδ,sufficientlycapacitive
burdenθisalwayspositive
•Itisassumedthatthemagnitudeofsecondary
impedanceisconstant
Characteristic of CT

Effect of Change of Primary
Winding Current
•Iftheprimarywindingcurrentchangesthe
secondarywindingcurrentchanges
proportionately.AtlowvaluesofcurrentI
pI
s;
thecurrentI
mandlosscurrentI
eareagreater
proportionofandtheerrorsaregreater.
•AsthecurrentI
pincreases,thereisanincrease
inI
Sandthereisadecreaseinratioerrorand
phaseangel

•Anincreaseinsecondarywindingcircuits
burdenimpedancemeansanincreaseinvolt
amprating.Thisnecessitatesandincreasein
thesecondarywindinginducedvoltagewhich
canbegeneratedbyanincreasedfluxandflux
density.Thereforeboththemagnetization
currentincreased
Effect of Change of Secondary
Winding Circuit Burden

•Theeffectofincreaseinfrequencywillresult
inproportionatedecreesinfluxdensity.Thus
theeffectofincreaseinfrequencyissimilarto
thatproducedbydecreaseinimpedanceof
secondarywindingburden
•Acurrenttransformerisseldomusedata
frequencywhichisverydifferentfromtheone
orwhichisdesignedandconsiderationofthis
effectisnotveryimportant
Effect of Change of Frequency

Causes of Error in CT
•Thereissomeexitingmmfrequiredbytheprimary
windingtoproducefluxandthetransformerdrawsa
magnetizingcurrent
•Thetransformerinputmusthaveacomponentwhich
suppliesthecorelosses(eddycurrentandhysterisis)and
I
2
Rlosses
•Thefluxdensityinthecoreisnotalinearfunctionofthe
magnetizingforce
•Thereisalwaysamagneticleakageandconsequentlythe
primaryfluxlinkagesarenotequaltothesecondaryflux
linkages
Effect of Change of Primary
Winding Current

Means to Reduce Error in CT
•There are some design featurewhich helps to
minimize the errors
–Core
–Primary winding current ratings
–Leakage reactance
–Turns compensation
–Use of shunts
–Wilson compensation method
–Two stage design

Construction of CT
•WoundType ACThavingaprimary
windingofmorethanonefullturnwounded
oncore
•BarType ACTinwhichtheprimary
windingconsistsofabarofsuitablesizeand
materialforminganintegralpartof
transformer

CLAMP ON AMMETERS
•ACTwithasingleconductorisusedin
combinationwithabridgerectifierandadc
milli-ammetertoproduceaveryusefulservice
meter
•Bychangingtheshuntresistanceofthemilli-
ammetercircuitrangesfrom0-5Ato0-600A
•Thesamemilli-ammeterandrectifierareused
withtwoexternalbindingpostsandarange
selectingswitchforamulti-rangeacvoltmeter

Effect of Secondary Open Ckt
•CTalwaysusethesecondarywindingclosed
throughammeterswattmetercurrentcoilsor
relay.
PRECAUTION
•NEVER OPEN THE SECONDARY
WINDING CKTOFACTWHILEITS
PRIMARYWINDINGISENERGISED
•ifthesecondaryisopen,theprimarymmf
remainsthesamebuttheopposingsecondary
mmfreducestozero.Thelargemmfproduce
HIGHVOLTAGE atthesecondary;destroy
insulation

POTENTIAL TRANSFORMER

Connection of CT and PT

Potential Transformer
•PTisusedtooperatevoltmeters,thepotential
coilsofwattcmetersetc
•Theprimarywindingisconnectedacrossthe
linevoltagetobemeasuredandthevoltage
circuitisconnectedacrossthesecondary
winding
•ThedesignofPTissimilartothepower
transformerbuttheloadingofaPTisalways
small
•Secondaryvoltageisnormally100-120V

Difference Between CT & PT
•PTmaybeconsideredas‘parallel’transformerwithits
secondaryoperatingnearlyunderopencircuit;whereasCT
maybea‘series’undervirtualshortcircuit.Thesecondaryof
PTcanbeopencircuitwithoutanydamage
•TheprimarywindingcurrentinaCTisindependentofthe
secondarywindingcircuitconditionswhiletheprimarywinding
currentinaPTcertainlydependsuponthesecondarycircuit
burden
•InaPT,fulllinevoltageisimpresseduponitsterminal
whereasaCTisconnectedinserieswithonelineandasmall
voltageexistsacrossitsterminals.TheCTcariesthefullline
currents
•undernormaloperationthelinevoltageisnearlyconstantand
thefluxdensityandtheexitingcurrentofaPTvariesonlyover
arestrictedrangewhereastheprimarywindingcurrentand
excitationofaCTvaryoverwidelimitsinnormaloperation

RELATIONSHIPS IN A PT
•ThepowerloadingofPTisverysmalland
consequentlytheexitingcurrentisofthesame
orderasthesecondarywindingcurrentwhile
inaPTtheexitingcurrentisverysmall
fractionofsecondarywindingloadcurrent
•Theequivalentcircuitandthevectordiagram

Let,0
flux; I = magnetizing component of no load current
I = iron loss component of no load (exiting) current
I = no load (exiting) current
E = Secondary winding induced voltage; V = Secondary windin
m
e
ss
working
g terminal voltage
= Primary winding turns; = Secondary winding turns
= Secondary winding currents
= Resistance of secondary winding; x = Reactance of secondary winding
= Resistance of seconda
Ps
s
ss
e
NN
I
r
r ry load ckt; x = Reactance of secondary load ckt
angle of secondary load ckt
E =Primary winding induced voltage; I = primary winding current;
= Resistance of primary winding; x = Reactance of
e
pp
pp
phase
r

primary winding
Turns ratio n=N /N ; n=E /E
p s p s

Ratio (voltage) Error

ERRORS IN PT
Ratio (voltage) Error
•Theactualratiooftransformationvaries
withoperatingconditionsandtheerrorin
secondaryvoltagemaybedefined;
•percentagerationerror=[(K
n-R)/R]x100

•In an ideal PT there should not be any phase
difference between primary winding voltage and
the secondary winding voltage reversed. In actual
transformer there exists phase angle error between
V
Pand V
s reversed.
ERRORS IN PT
Phase Angle Error

Reduction of Error in PT
•Considerableimprovement inthe
performancecanbemadebyreducingthe
valuesofmagnetisingcurrentsandrequires
shortmagneticpath,goodqualitycore
material,lowfluxdensityincoreandsuitable
precautionsinassemblingandinterleaving
thecore
Reduction of Magnetizing and Loss Components

Reduction of Resistance and
Leakage Reactance's
•Windingresistancecanbeminimizedbyusingthick
conductorsanbyadoptingthesmallestlengthof
meanturn
•Theleakagereactancedependsuponthemagnitudeof
primaryandsecondarywindingleakagefluxesand
shouldkeepthetwowindingsascloseaspossible.
•Thefluxdensityinthecoreshouldbekeptashighas
possible
•Highfluxdensitymeansahighfluxinthecoreandso
thewindingshavelessernumberofturns.Asmaller
noofturnsnaturallyresultsinsmallerleakage
reactanceofthewindings

Turns Compensations
•Atnoloadtheactualratioexceedstheturnsratiobyan
amount(I
er
p+I
mx
p)/V
s.Withandinductiveorresistive
loadthereisfurtherincreaseinratiobecauseofvoltage
dropsinresistanceandleakagereactanceofthe
windings
•Iftheturnsrationisequaltothenominalratio,the
actualratiodiffersfromthenominalratioandthus
thereareerrors
•Thesolutionliesintheturnsratiomustbelessthan
nominalratio.Thiscanbedonebyeitherreducingthe
numberofprimarywindingturnsofincreasingthe
mumberofsecondarywindingturns

Construction of PT
ThedesignandconstructionofPTisbasicallythe
sameasthoseofpowertransformerwithafew
majordifferences:
PThaslargercoreandconductorsizes.Economic
designmayleadtolargeratioandphaseangle
errorswhichareundesirable
TheoutputofPTisalwayssmallandthesizeis
quitelarge,nothermalproblem.
LoadingofPTislimitedbyaccuracy
considerationswhileinapowertransformerthe
loadlimitationisonheatingbasis.

•Core.Thecoremaybecoreorshelltype.Shelltype
isforlowvoltage.Laminationsshouldbesuchthat
theeffectoflargeairgapsatthejointmaybe
minimized
•Windings. Theprimaryandthesecondary
windingsareco-axialtoreduceleakagereactanceto
minimum.Theprimarywindingmaybeasinglecoil
inlowvoltagetransformersbutmustbesib-divided
intoanumberofshortcoilsinhighvoltage
transformerinordertoreducetheinsulationneeded
betweencoillayers
Construction of PT

•Insulationscottontapeandvarnishedcambric
areusedasinsulationforcoilconstruction.Atlow
voltagesthetransformersarefilledwithout
compoundbutPTvoltageabove7KVareoil
immersed
•Bushingsoilfilledbushingsareusedforoil
filedPTasthisminimizetheoverallsizeofthe
transformer.Twobushingsareusedwhenneither
sideofthelineisatgroundpotential
Construction of PT

High Voltage PT
•ConventionaltypePTusedinhighvoltagesof
100kvandabove,areverylargeinsizeand
costlytobuildbecauseofinsulationrequirement
•Recentdevelopmentindesignandconstruction
hasreducedthesizeconsiderably.The
eliminationsofbushingreducesthesizeandcost
oftransformer.Designsareintendedtomeasure
linetogroundvoltagesin3phasesystem:
•Thedesignemploy:

•InsulatedCasing Thetransformerisbuiltentirely
inanoiledfiledhighvoltageinsulator
•MouldedRubberPTMoulded rubberinsulated
transformerhasreplacetheinsulatingoiland
porcelainbushingsandislessexpensive
•CascadedTransformerThevoltagesisamonga
numberoftransformers.Inthiswayinsulationreduces
tothelowervoltagesandsavescostsandspaces
Construction of PT

Characteristics of PT
Increaseinsecondaryburden,thesecondarycurrent
increasesi.e.primarycurrentincrease;foragiven
valueofV
PthevalueofV
sdecreasesandtheactual
rationincreasesastheburdenincreases
Theratioerrorincreasesbecomingmorenegative
withincreaseinburden.Thisvariationofratioerror
isalmostlinearwithchangeinburden
V
pismoreadvancedinphasebecauseofincreased
voltagedropswithincreaseinsecondaryburden.The
phasorV
sisretardedinphaseowingtincreasein
secondaryvoltagedrop;thusthephaseanglebetween
V
PandV
sreversedincreases,becomingmorenegative
Effect of Secondary Current or VA

•Ifthepfofsecondarycircuitburdenis
reduced,ΔincreasedandI
PshiftedtowardsI
0
•ThevoltagesV
PandV
Snearlycomesinphase
withE
PandE
S;sincethevoltagedropis
almostconstant.
•Thetransformationratioincreasesasthepf
ofsecondaryburdenreduces
Characteristics of PT
Effect PF of Secondary Burden

Effect of Frequency
•Thefluxisinverselyproportionaltofrequencywith
constantvoltage.Increaseinfrequencyreducesthe
fluxandmagnetizationcurrentdecreasesandthe
voltageratiodecrease
•Asregardstophaseangleerror,botheffectsdueto
increaseinfrequencyadvanceV
Pandtheincreasein
secondaryreactanceretardsV
sandphaseangleis
increasedasthefrequencyincreases

Effect of Primary Voltage
•Thereisnowidevariationofsupply
voltagetowhichtheprimarywindingof
thePTisconnected.Thereforethestudy
ofvariationofratioandphaseangle
errorswithsupplyvoltageareofno
importance

Polarity of CT & PT
•Anunderstandingofpolarityisessentialtocorrectlyconstructthree-
phasetransformerbanksandtoproperlyparallelsingleorthree-phase
transformerswithexistingelectricalsystems.Aknowledgeofpolarity
isalsorequiredtoconnectpotentialandcurrenttransformerstopower
meteringdevicesandprotectiverelays.
•Thebasictheoryofadditiveandsubtractivepolarityistheunderlying
principleusedinstepvoltageregulatorswheretheserieswindingof
anautotransformerisconnectedtoeitherbuckorboosttheapplied
linevoltage.
•TransformerPolarityreferstotherelativedirectionoftheinduced
voltagesbetweenthehighvoltageterminalsandthelowvoltage
terminals.DuringtheAChalf-cyclewhentheappliedvoltage(or
currentinthecaseofacurrenttransformer)isfromH1toH2the
secondaryinducedvoltagedirectionwillbefromX1toX2.In
practice,Polarityreferstothewaytheleadsarebroughtoutofthe
transformer.
The Importance of Polarity

•BushingArrangement ThepositionoftheHighVoltage
Bushingsisstandardizedonallpowerandinstrument
transformers.Theruleisthis:whenfacingthelowvoltage
bushings,thePrimaryBushingH1isalwaysontheleft-handside
andthePrimaryBushingH2isontheright-handside(ifthe
transformerisathree-phaseunit,H3willbetotherightofH2).
•DistributionTransformersareAdditivePolarityandtheH1and
X1bushingsarephysicallyplaceddiagonallyoppositeeach
other.SinceH1isalwaysontheleft,X1willbeontheright-hand
sideofadistributiontransformer.Thisstandardwasdeveloped
veryearlyinthedevelopmentofelectricaldistributionsystems
andhasbeenadheredtoinordertopreventconfusioninthe
fieldwhentransformersneedtobereplacedorparalleledwith
existingequipment.
•InstrumentTransformers(PT’sandCT’s)andlargesubstation
transformersareSubtractivePolarity,sotheH1andX1
Bushingswillbeonthesamesideofthetransformer.This
standardwaslateradoptedtomakeiteasiertoreadelectrical
schematicsandconstructphasordiagrams.

Polarity of CT & PT

Polarity of CT & PT

POLARITY TEST
•Insituationswherethesecondarybushingidentificationisnotavailableor
whenatransformerhasbeenrewound,itmaybenecessarytodeterminethe
transformerpolaritybytest.Thefollowingprocedurecanbeused.
•TheH1(left-hand)primarybushingandtheleft-handsecondarybushing
aretemporarilyjumperedtogetherandatestvoltageisappliedtothe
transformerprimary.Theresultantvoltageismeasuredbetweentheright-
handbushings.
•Ifthemeasuredvoltageisgreaterthantheappliedvoltage,thetransformer
isAdditivePolaritybecausethepolarityissuchthatthesecondaryvoltageis
beingaddedtotheappliedprimaryvoltage.
•If,however,themeasuredvoltageacrosstheright-handbushingsislessthan
theappliedprimaryvoltage,thetransformerisSubtractivePolarity.
•Note:Forsafetyandtoavoidthepossibilityofdamagingthesecondary
insulation,thetestvoltageappliedtotheprimaryshouldbeatareduced
voltageandshouldnotexceedtheratedsecondaryvoltage.

POLARITY TEST

•PolarityMarksToinsurecorrectwiring,polaritymarksare
shownonInstrumentConnectionDiagrams,ControlSchematics,
andThree-LinePowerDiagrams.Thepolaritymarkisusually
shownasarounddot,onoradjacentto,theH1andX1terminals
ofPT’sandCT’s.Sometimesalternatemarking,intheformofa
squaredot,slashmark(/),orplus/minussign(+)willbeused
toidentifythepolarityterminalsonelectricaldrawings.
•Instrumenttransformersmayalsohavetheterminalsidentified
withpolaritymarksasshownintheillustrationofthe300:5CT
onSheet3.Ifinstrumenttransformersdonothavepolarity
marksonthem,itisunderstoodthattheH1(primary)andthe
X1(secondary)terminalsarepolarity.
•Meters,relays,andotherequipmentwhichrequireproper
polarityconnectionsmayalsohavepolaritymarks,butusually
thisinformationmustbeobtainedfromtheInstrument
ConnectionDiagram.
POLARITY MARKING

POLARITY MARKING

•ThePT,CT,andinstrumentpolaritymarksare
shownbythereddotsontheabovedrawing.(Red
dotswereusedinthisexampleonlyforclarity.)
•Currentelementsoftheinstrumentsareconnectedin
series,voltageinputsareconnectedinparallel.
•Polarityisnotaconsiderationonsingle-element
devicessuchasanammeterorvoltmeter,butis
essentialforproperoperationofpowermeasuring
devices,andfordirectionalordifferentialprotective
relays.
POLARITY MARKING

Current Flow Analysis
•InanalyzingthecurrentflowinasystemutilizingCT’sthe
followingobservationcanbemade:
•WhencurrentflowsintheCTprimaryfromtheH1lead
(polarity±)tothenon-polarityH2lead,currentwillbeforced
outthesecondaryX1(polarity±)lead,throughtheburden
(load),andreturntothesecondaryX2non-polaritylead.The
nexthalf-cyclethecurrentwillreverse,butforthepurposeof
analysisandforconstructingphasordiagrams,onlytheabove
indicatedone-halfcycleisanalyzed.
ElectricalDrawingConventions
•Thepolaritymarkingonelectricaldrawingsmaybemadein
severaldifferentways.Thethreemostcommonschematic
conventionsareshownbelow.Thedrawingsymbolformeters
andrelaysinstalledinadraw-outcasethatautomaticallyshort
theCTsecondaryisshowninthedrawingatthelowerright.