Test universe presentation basics to advance simulation
Size: 3.84 MB
Language: en
Added: Jul 26, 2024
Slides: 89 pages
Slide Content
To Create A New Project
Enter The Project Name
Enter project name
Click device –plug & play
Click Siprotech 4
Com Selection in Lap top
Right Click My computer
Go to Hardware
Click Device Manager
Check Ports and Communication
Com selection in Lap top
Relay Communication Set up
After Opening the New project in Digsi
Software, click device and go to Plug &
play . It will go to new dialog box, in that
choose Direct for online communication.
Relay Communication Set up
Choose direct and check COM
selection
Communication processing
Opening on line window
After communication
By clicking settings menu, following list will present in window
1.Device configuration
2.Masking i/o configuration
3.CFC
4.Power system data 1
5.Setting group A
6.Oscillographic fault records
7.General device settings
8.Time synchronization
9.Interface
10.Password
11.Languages
Settings list contains
Definition and purpose of each
menu
Device configuration
Device configuration menu
Purpose:
According to the protective scheme, to ENABLE/
DISABLE the protection.
Select masking I/O configuration
Masking i/o menu
Purpose:
According to the protective scheme to configure the following
functions are
•Binary inputs
•Binary outputs
•LED’s
Binary inputs should be configure
in BI column
Binary outputs should be configure
in BO column
Binary outputs should be configure
in BO column
Definition for Binary output Latched
and Unlatched
Latched:continuously making output
contact till it will get reset
Unlatched:output contact will automatically
reset after clearing fault
LED’s should be configure in LED
column
CLICK CFC CHART
CFC Menu
Purpose:
To make the protective function logic by
using Logic gates
Example :And, Or, Nor, Nand and so on
CLICK POWER SYSTEM DATA1
POWER SYSTEM DATA 1
PURPOSE:
Enter the power system details like
•CT Ratios
•PT Ratios
•Transformer details
•Phase Sequence
•Temperature Units
Power system data 1 Menu
Setting group A
Purpose:
By clicking setting group A, respective
protections setting will be display
according to configuration done in the
device configuration like
•Distance protection
•Distance zones
•Back up o/c
Setting group A Menu
Oscillographic records
Purpose:
To Configure the fault record in desired
graphic form by giving suitable settings in
•Post fault duration
•Prefault duration
•Trigger time duration
Oscillographic records Menu
By clicking oscillographic records
Select General device setting
General device setting
Purpose:
•To select LCD/LED display for pickup or
trip on after simulating fault.
By clicking General device setting
CFC APPLICATION
How to Make a logic in CFC chart
CFC
Abbreviation of CFC
C-Continuous
F-Function
C-Chart
New CFC creation
Click on Insert → CFC Chart
.
Rename the CFC chart
Accept the new chart name by clicking on OK.
•Open the CFC chart:
•Right-click on the name of the CFC chart
and select Open Object... in
•the displayed context menu.
Specifying the Priority Class
Edit → Run Sequence
Specifying the Priority Class
Edit → Predecessor for Installation
•Confirm the displayed message box on the
modified priority class by
•clicking on OK.
Specifying the Priority Class
•Click in the Run-time editor on Edit →
Run Sequence.... The CFC chart is
displayed again.
Example of CFC logic creation
We take Trip circuit supervision function
In trip circuit supervision
We need two inputs and on output
Inputs:
1.Trip relay
2.Breaker relay
Output:
TCS output
Configuration input and output
For configuring input and output go
Setting → making i/o
Configuration of input
•In order to use an information as an input
signal for the CFC on the left border,
allocate the information to CFC under
Destination:
•Right-click in the corresponding field of the
column C of the configuration
•matrix and select X (configured) in the
opened context menu
Configuration of input
Configuration of output
•In order to use an information as an output
signal for the CFC on the right border,
allocate the information to CFC under
Source:
•Right-click in the corresponding cell of the
column C of the configuration
•matrix and select X (configured) in the
opened context menu.
Configuration of output
Task to create trip circuit
supervision logic in CFC
Input signal :
1.Breaker relay
2.Trip relay
Output signal :
1.TCS output
CFC block:
1.OR gate
How to proceed
• In the DIGSI configuration matrix, configure the
input signals and the output signals to the CFC
• Create a new CFC chart with the designation
TCS.
• Specify the priority class Metered value
processing (MW_BEARB)
• Position the block OR gate.
• Interconnect the input signal.
• Interconnect the output signals.
• Compile the CFC chart.
Rename the CFC
Create CFC with name TCS
Renamed the CFC
Configure input / output
•To configure input and output
•Select the Settings folder in the
navigation pane and
• Double-click on the Masking I/O
(Configuration Matrix) function in the
data pane.
Create new function in TCS name
Create new function in TCS name
Configure input information
•Click in aero showing
area
Configure input information
•T0 select annunciation
Configure input information
•Select single point on/off and drag it to
TCS function Area
Configure input information
•Rename the block with Trip relay
•Configure the input with H type
H-Active with voltage
L-Active without voltage