Earthing test report for dg

2,913 views 1 slides Apr 13, 2020
Slide 1
Slide 1 of 1
Slide 1
1

About This Presentation

Earthing Test Report 3 pole method using fluke meter


Slide Content

EARTH TESTING OF CAMP DG 125KVA
CONTRACTOR: SAVRONIK SISTEM INDIA PVT LTD. Spike 1

Spike 2

33kV Pole





Method of testing: (Three Probe Method) as per IS: 3043
Spacing B/w Spike: 10 Meters
Depth of Spike: 0.25Meter
Earth Tester Specification: Fluke 1621 Earth/Ground Tester (Serial No: S182814118A3)
Reading s at Particular Locations:
S.No Location
Earth Resistance (In
Ohms )
Voltage
Applied
Terrain
1
DG Pit No:1
DG1 Safety Earthing
36.4 0.5Volt Loose gravel soil
2
DG Pit No:2
DG2 Safety Earthing
63.6 0.5Volt Loose gravel soil
3
DG Pit No:3
DG1 System Earthing
56.1 0.7Volt Loose gravel soil
4
DG Pit No:3
DG2 System Earthing
55.0 0.5Volt Loose gravel soil

DG Details
S.No DG Name Make Serial No Specification
1. DG 1 Sudhir Power Ltd 84879705 125KVA, 415V
2. DG 2 Sudhir Power Ltd 84893859 125KVA, 415V


DG PIT

Reference Earth

E/C1 S/P2 H/C2