Fire Pump Tutorial as per NFPA 20 standard

1,141 views 238 slides May 30, 2024
Slide 1
Slide 1 of 261
Slide 1
1
Slide 2
2
Slide 3
3
Slide 4
4
Slide 5
5
Slide 6
6
Slide 7
7
Slide 8
8
Slide 9
9
Slide 10
10
Slide 11
11
Slide 12
12
Slide 13
13
Slide 14
14
Slide 15
15
Slide 16
16
Slide 17
17
Slide 18
18
Slide 19
19
Slide 20
20
Slide 21
21
Slide 22
22
Slide 23
23
Slide 24
24
Slide 25
25
Slide 26
26
Slide 27
27
Slide 28
28
Slide 29
29
Slide 30
30
Slide 31
31
Slide 32
32
Slide 33
33
Slide 34
34
Slide 35
35
Slide 36
36
Slide 37
37
Slide 38
38
Slide 39
39
Slide 40
40
Slide 41
41
Slide 42
42
Slide 43
43
Slide 44
44
Slide 45
45
Slide 46
46
Slide 47
47
Slide 48
48
Slide 49
49
Slide 50
50
Slide 51
51
Slide 52
52
Slide 53
53
Slide 54
54
Slide 55
55
Slide 56
56
Slide 57
57
Slide 58
58
Slide 59
59
Slide 60
60
Slide 61
61
Slide 62
62
Slide 63
63
Slide 64
64
Slide 65
65
Slide 66
66
Slide 67
67
Slide 68
68
Slide 69
69
Slide 70
70
Slide 71
71
Slide 72
72
Slide 73
73
Slide 74
74
Slide 75
75
Slide 76
76
Slide 77
77
Slide 78
78
Slide 79
79
Slide 80
80
Slide 81
81
Slide 82
82
Slide 83
83
Slide 84
84
Slide 85
85
Slide 86
86
Slide 87
87
Slide 88
88
Slide 89
89
Slide 90
90
Slide 91
91
Slide 92
92
Slide 93
93
Slide 94
94
Slide 95
95
Slide 96
96
Slide 97
97
Slide 98
98
Slide 99
99
Slide 100
100
Slide 101
101
Slide 102
102
Slide 103
103
Slide 104
104
Slide 105
105
Slide 106
106
Slide 107
107
Slide 108
108
Slide 109
109
Slide 110
110
Slide 111
111
Slide 112
112
Slide 113
113
Slide 114
114
Slide 115
115
Slide 116
116
Slide 117
117
Slide 118
118
Slide 119
119
Slide 120
120
Slide 121
121
Slide 122
122
Slide 123
123
Slide 124
124
Slide 125
125
Slide 126
126
Slide 127
127
Slide 128
128
Slide 129
129
Slide 130
130
Slide 131
131
Slide 132
132
Slide 133
133
Slide 134
134
Slide 135
135
Slide 136
136
Slide 137
137
Slide 138
138
Slide 139
139
Slide 140
140
Slide 141
141
Slide 142
142
Slide 143
143
Slide 144
144
Slide 145
145
Slide 146
146
Slide 147
147
Slide 148
148
Slide 149
149
Slide 150
150
Slide 151
151
Slide 152
152
Slide 153
153
Slide 154
154
Slide 155
155
Slide 156
156
Slide 157
157
Slide 158
158
Slide 159
159
Slide 160
160
Slide 161
161
Slide 162
162
Slide 163
163
Slide 164
164
Slide 165
165
Slide 166
166
Slide 167
167
Slide 168
168
Slide 169
169
Slide 170
170
Slide 171
171
Slide 172
172
Slide 173
173
Slide 174
174
Slide 175
175
Slide 176
176
Slide 177
177
Slide 178
178
Slide 179
179
Slide 180
180
Slide 181
181
Slide 182
182
Slide 183
183
Slide 184
184
Slide 185
185
Slide 186
186
Slide 187
187
Slide 188
188
Slide 189
189
Slide 190
190
Slide 191
191
Slide 192
192
Slide 193
193
Slide 194
194
Slide 195
195
Slide 196
196
Slide 197
197
Slide 198
198
Slide 199
199
Slide 200
200
Slide 201
201
Slide 202
202
Slide 203
203
Slide 204
204
Slide 205
205
Slide 206
206
Slide 207
207
Slide 208
208
Slide 209
209
Slide 210
210
Slide 211
211
Slide 212
212
Slide 213
213
Slide 214
214
Slide 215
215
Slide 216
216
Slide 217
217
Slide 218
218
Slide 219
219
Slide 220
220
Slide 221
221
Slide 222
222
Slide 223
223
Slide 224
224
Slide 225
225
Slide 226
226
Slide 227
227
Slide 228
228
Slide 229
229
Slide 230
230
Slide 231
231
Slide 232
232
Slide 233
233
Slide 234
234
Slide 235
235
Slide 236
236
Slide 237
237
Slide 238
238
Slide 239
239
Slide 240
240
Slide 241
241
Slide 242
242
Slide 243
243
Slide 244
244
Slide 245
245
Slide 246
246
Slide 247
247
Slide 248
248
Slide 249
249
Slide 250
250
Slide 251
251
Slide 252
252
Slide 253
253
Slide 254
254
Slide 255
255
Slide 256
256
Slide 257
257
Slide 258
258
Slide 259
259
Slide 260
260
Slide 261
261

About This Presentation

Fire Pump complete illustration


Slide Content

NFPA 20 1-8 (3.2) NFPA Official DefinitionsNFPA 20 1-8 (3.2) NFPA Official Definitions
Authority Having JurisdictionAuthority Having Jurisdiction.*.* The organization,
office, or individual responsible for approving
equipment, materials, an installation, or a procedure.
A-1-8 (3.2.2) Authority Having Jurisdiction.A-1-8 (3.2.2) Authority Having Jurisdiction.
The phrase “authority having jurisdiction” is used in NFPA documents in a
broad manner, since jurisdictions and approval agencies vary, as do their
responsibilities. Where public safety is primary, the authority having
jurisdiction may be a federal, state, local, or other regional department or
individual such as a fire chief; fire marshal; chief of a fire prevention bureau,
labor department, or health department; building official; electrical
inspector; or others having statutory authority. For insurance purposes, an
insurance inspection department, rating bureau, or other insurance
company representative may be the authority having jurisdiction. In many
circumstances, the property owner or his or her designated agent assumes
the role of the authority having jurisdiction; at government installations,
the commanding officer or departmental official may be the authority
having jurisdiction.

NFPA 20 (3.2.1)NFPA 20 (3.2.1)
Approved.*Approved.* Acceptable to the Acceptable to the
authority having jurisdiction.authority having jurisdiction.
A-1-8 (A.3.2.1) Approved. A-1-8 (A.3.2.1) Approved.
The National Fire Protection Association does not approve,
inspect, or certify any installations, procedures, equipment,
or materials; nor does it approve or evaluate testing
laboratories. In determining the acceptability of
installations, procedures, equipment, or materials, the
authority having jurisdiction may base acceptance on
compliance with NFPA or other appropriate standards. In
the absence of such standards, said authority may require
evidence of proper installation, procedure, or use. The
authority having jurisdiction may also refer to the listings
or labeling practices of an organization ( UL or <FM> ) ( UL or <FM> )
that is concerned with product evaluations and is thus in a
position to determine compliance with appropriate
standards for the current production of listed items.

WATER SUPPLYWATER SUPPLY NFPA 20 (5.6)NFPA 20 (5.6)
The most common sources of fire The most common sources of fire
protection water are: city water, above protection water are: city water, above
ground tank, below ground tank, well, or ground tank, below ground tank, well, or
an open body of water ( pond, river, an open body of water ( pond, river,
lake, etc. )lake, etc. )
NFPA 20 (6.1.2) NFPA 20 (6.1.2) Centrifugal pumps shall Centrifugal pumps shall
not be used where a static suction lift is not be used where a static suction lift is
required.required.
Find out how many GPM are required and how much PSI
is needed to make the sprinkler and/or stand pipe system
work… Will the “proposed” water supply water supply and fire fire
pump pump meet the system demand ?

Will the water supply be adequate at 150% of the Will the water supply be adequate at 150% of the
fire pump rated flow??? fire pump rated flow??? NFPA 20NFPA 20 (5.6.2) (5.6.2)
(5.6.5.1)(5.6.5.1)
NFPA 20 (5.6.2.2)NFPA 20 (5.6.2.2) Where the water supply Where the water supply
from a public service main is not adequate in from a public service main is not adequate in
quality, quantity, or pressure, quality, quantity, or pressure, an alternative an alternative
water source “SHALL” be provided.water source “SHALL” be provided.
NFPA 20NFPA 20 (5.6.5) Head. The head (suction
pressure) available from a water supply shall be
figured on the basis of a flow of 150 percent of
the rated capacity of the fire pump. This head
should be determined by a flow test of the water
supply prior prior to ordering the pump.

--SAMPLE----SAMPLE--
This water supply has a 6” line and an 8” that will feed a 1000 GPM pump. This water supply has a 6” line and an 8” that will feed a 1000 GPM pump.
The top curve has both lines open, the lower curve has only the 6” open. The top curve has both lines open, the lower curve has only the 6” open.
In the worst condition (6” only) the line will provide 1000 GPM @ 45 PSI. In the worst condition (6” only) the line will provide 1000 GPM @ 45 PSI.
NOTE: Water supply flow test - MUST NOTE: Water supply flow test - MUST
BE CONDUCTED BEFORE A PUMP IS BE CONDUCTED BEFORE A PUMP IS
SPECIFIED AND ORDERED! (5.6.5)SPECIFIED AND ORDERED! (5.6.5)

STATE of OHIO FIRE SCHOOL - BGSU 6
Theoretical ConditionsTheoretical Conditions
.323 ‘323 ‘
NFPA 20 Theoretical NFPA 20 Theoretical
Maximum Churn Maximum Churn
HEADHEAD “Must not “Must not
exceed” 140 % of exceed” 140 % of
RatedRated HEAD HEAD
231 ‘231 ‘
NFPA 20 100% NFPA 20 100%
“Rated” Condition “Rated” Condition
500 GPM @ 231 ‘ 500 GPM @ 231 ‘
HEADHEAD
500 GPM500 GPM
750 GPM750 GPM
NFPA 20 Theoretical NFPA 20 Theoretical
Minimum Head AT Minimum Head AT
150% of RATED FLOW 150% of RATED FLOW
- Head Must Be - Head Must Be
“Above“Above ““ 65% of 65% of
Rated Rated HeadHead
PP
UU
MM
P P

HH
EE
AA
D D
PUMP FLOW in GPMPUMP FLOW in GPM

Total Head (H), Horizontal Pumps.*Total Head (H), Horizontal Pumps.* The The
measure of the measure of the “work increase”“work increase” per pound per pound
(kilogram) of liquid, imparted to the liquid by the (kilogram) of liquid, imparted to the liquid by the
pump, and therefore the algebraic difference pump, and therefore the algebraic difference
between the total discharge head and the total between the total discharge head and the total
suction head. suction head.
Where “positive” suction head exists, Where “positive” suction head exists,
the the total headtotal head ( ( work increasework increase ) ) = the = the
total total dischargedischarge head ‘ head ‘minus’ ( - ) minus’ ( - )
the total the total suctionsuction head. head.
Total Head (H), Vertical Turbine Pumps.*Total Head (H), Vertical Turbine Pumps.* The The
distance from the pumping water level to the center of the distance from the pumping water level to the center of the
discharge gauge discharge gauge ‘plus’ ( + )‘plus’ ( + ) the total discharge head. the total discharge head.

STATE of OHIO FIRE SCHOOL - BGSU 8 PSI / PSI / HEAD (ft)HEAD (ft)
CALIBRATED ??CALIBRATED ??
CALIBRATED ??CALIBRATED ??

To determine To determine
FEET of HEAD FEET of HEAD
multiply “ multiply “ HH “ “
(net PSI) X 2.31(net PSI) X 2.31
To determine “ To determine “
HH ” (net PSI) ” (net PSI)
subtract subtract
SuctionSuction PSI PSI
from from
DischargeDischarge PSI PSI
150 PSI150 PSI
50 PSI50 PSI
100 PSI100 PSI
231’ (ft)231’ (ft)
HORIZONTAL HORIZONTAL
PUMPSPUMPS
The suction pressure must The suction pressure must
be (0 psi) or higher when be (0 psi) or higher when
pump is operating at 150 %. pump is operating at 150 %.
When suction is from a tank When suction is from a tank
the pressure is permitted to the pressure is permitted to
drop to (-3 psi). NFPA 20 drop to (-3 psi). NFPA 20
(5.14.3)(5.14.3)

STATE of OHIO FIRE SCHOOL - BGSU 10
.
.
.
“RATED 100% FLOW “
..
AA
CC
BB
..
..
..
“ 150 %
FLOW “
““CHURN” CHURN”
PressurePressure ““RATED” RATED”
100 % 100 %
FLOWFLOW
ACTUAL CITY WATER ACTUAL CITY WATER
FROM PUMP TESTFROM PUMP TEST
FLOW IN GPMFLOW IN GPM
HH
EE
AA
DD

STATE of OHIO FIRE SCHOOL - BGSU 11
PUMP FLOW PUMP FLOW
DETERMINATIONDETERMINATION
WITH FLOW WITH FLOW
METERMETER

STATE of OHIO FIRE SCHOOL - BGSU 12
NOZZLE NOZZLE (PLAY PIPE)(PLAY PIPE)
AND PITOT TUBEAND PITOT TUBE
PUMP FLOW PUMP FLOW
DETERMINATIONDETERMINATION

<FM> FLOW CHART<FM> FLOW CHART

UL / FMUL / FM
CENTRIFUGALCENTRIFUGAL
FIRE PUMPSFIRE PUMPS

PACKAGED PUMP HOUSEPACKAGED PUMP HOUSE

Prefabricated Fire Pump HousePrefabricated Fire Pump House

SITE PREPARATION : Slab or FooterSITE PREPARATION : Slab or Footer

NOTE : NOTE :
No Spreader Bars !No Spreader Bars !

STATE of OHIO FIRE SCHOOL - BGSU 19

Field Erected Pump House or Pump RoomField Erected Pump House or Pump Room

HorizontalHorizontal
Split - CaseSplit - Case
Vertical Vertical
In-LineIn-Line

STATE of OHIO FIRE SCHOOL - BGSU 24
To Test HeadTo Test Head
Jockey Jockey
PumpPump
Vertical TurbineVertical Turbine

Horizontal Split - Case Fire PumpHorizontal Split - Case Fire Pump

Water Water
Seal Seal
PipingPiping
NOTE: Water seal NOTE: Water seal
piping is not provided piping is not provided
on UL Fire Pumps on UL Fire Pumps
with suction pressure with suction pressure
of 30 psi or more !of 30 psi or more !
#1#1
YOU MUST YOU MUST
ACCURATELY ACCURATELY
DETERMINE THE DETERMINE THE
SUCTION PRESSURE SUCTION PRESSURE
““BEFORE” BEFORE” THE PUMP THE PUMP
IS ORDERED !!IS ORDERED !!
NFPA 20 (5.2.2) NFPA 20 (5.2.2)
(5.6.2.3)(5.6.2.3)

““ACTUAL” Suction pressure MUST be ACTUAL” Suction pressure MUST be
determined BEFORE you order the pump ! determined BEFORE you order the pump !
NFPA 20 (5.2.2) (5.6.2.3)NFPA 20 (5.2.2) (5.6.2.3)
Actual Actual
suction suction
pressure pressure
MUST NOT MUST NOT
exceed exceed
this !this !

STATE of OHIO FIRE SCHOOL - BGSU 28
NO RODS !!!
SAFE ??
Look at the pipe
fittings !!
This pump installation
develops 213 PSI at
churn.
A 125 lb flanged fitting
is rated at 175 PSI
maximum working
pressure !! NFPA 20
(5.7.4.1)
NFPA 13 15.1.6.1.1NFPA 13 15.1.6.1.1

STATE of OHIO FIRE SCHOOL - BGSU 29
NFPA 20 NFPA 20
(5.7.4.1) (5.7.4.1)
(5.7.4.2)(5.7.4.2)
Variable Variable
Speed PLC Speed PLC
(5.18.1.3)(5.18.1.3)(5.18.7)(5.18.7)

STATE of OHIO FIRE SCHOOL - BGSU 30
Circulation Relief ValveCirculation Relief Valve
¾”¾” is the is the MINIMUMMINIMUM size for up size for up
to 2500 GPM Rated Pump*.to 2500 GPM Rated Pump*.
1”1” MIN.MIN. for larger pumps ??? for larger pumps ???
NFPA 20 (5.11) NFPA 20 (5.11) **

Circulation “Case” Circulation “Case”
Relief ValveRelief Valve
NFPA 20 2-6 (5.11) NFPA 20 2-6 (5.11)
NOTE : Not required on diesel NOTE : Not required on diesel
engine-driven HSC fire pumps unless engine-driven HSC fire pumps unless
the engine is radiator-cooled ! the engine is radiator-cooled ! **
55 L55 L
918918 19 - 2019 - 20 1069110691 FWCFWC

STATE of OHIO FIRE SCHOOL - BGSU 32
NOTE: Above
(optional) Back-
pressure orifice
assembly installed
in ¾” case relief
valve discharge to
create back
pressure and
reduce cavitation.
NOTE: (Optional) Y strainer can
be used when foreign material
(sand or other debris) is present
in the water.
ORIFICE
FLOWFLOW
Typical CIRCULATION (CASE) Typical CIRCULATION (CASE)
RELIEF VALVE Assembly – The RELIEF VALVE Assembly – The
valve must be installed valve must be installed
(VERTICALLY) (VERTICALLY) on the pump on the pump
discharge before the discharge discharge before the discharge
check valve NFPA 20 (5.11.1.2)check valve NFPA 20 (5.11.1.2)

Automatic Air Release
NFPA 20 2-6
Automatic Air Release
NFPA 20 2-6 (6.3.3)

STATE of OHIO FIRE SCHOOL - BGSU 34
NFPA NFPA
2020
(6.3.3)(6.3.3)
NOTE : NOTE :
Automatic Automatic
air release air release
valve valve
installedinstalled

STATE of OHIO FIRE SCHOOL - BGSU 35
!!
(5.14)(5.14)
Elbows and tees with a centerline Elbows and tees with a centerline
plane parallel to a horizontal split-case plane parallel to a horizontal split-case
pump shaft shall be avoided. See pump shaft shall be avoided. See
Figure A-2-9.6. (5.14.6.3.1)Figure A-2-9.6. (5.14.6.3.1)
If there is a parallel elbow : YOU If there is a parallel elbow : YOU
MUST HAVE 10 PIPE DIAMETERS MUST HAVE 10 PIPE DIAMETERS
of STRAIGHT PIPE BETWEEN THE of STRAIGHT PIPE BETWEEN THE
ELBOW AND PUMP SUCTION ELBOW AND PUMP SUCTION
FLANGE (5.14.6.3.2)FLANGE (5.14.6.3.2)
PIPE SIZE ? PIPE SIZE ?
NFPA 20 NFPA 20
(5.14.3.4)(5.14.3.4)

STATE of OHIO FIRE SCHOOL - BGSU 36
NFPA 20NFPA 20
2-9.6.42-9.6.4
(5.14.6.4)(5.14.6.4)

SUCTIONSUCTION
SUCTIONSUCTION
NFPA 20NFPA 20
2-9.6.42-9.6.4
(5.14.6.4)(5.14.6.4)

STATE of OHIO FIRE SCHOOL - BGSU 38
NFPA 20 2-9.6.3NFPA 20 2-9.6.3Elbows and tees Elbows and tees
with a centerline with a centerline
plane parallel to plane parallel to
a horizontal a horizontal
split-case pump split-case pump
shaft shall be shaft shall be
avoided. See avoided. See
Figure A-2-9.6.Figure A-2-9.6.
SUCTIONSUCTION
(5.14.6.3.1)(5.14.6.3.1)

STATE of OHIO FIRE SCHOOL - BGSU 39
CORRECTED !!!CORRECTED !!!
NOTE: No ELBOWSNOTE: No ELBOWS

STATE of OHIO FIRE SCHOOL - BGSU 41
OSY OSY
Suction Suction
ValveValve
NOTE: Backflow Preventer!
NOTE: The long straight run of
suction pipe after a
HORIZONTAL 90 DEGREE
ELBOW !
More than 10 pipe diameters ?
(5.14.6.3.2)

SUCTION SUCTION
SUPPLY -SUPPLY -
City WaterCity Water
Is this Is this
Suction Suction
Piping Piping
OK ?OK ?
(5.14.6.3.3)(5.14.6.3.3)

STATE of OHIO FIRE SCHOOL - BGSU 43
SUCTION SUCTION
DISCHARGEDISCHARGE
Is this HSC vertical Is this HSC vertical
installation installation
“REALLY” a space “REALLY” a space
saver ?? saver ??
IS IT CORRECT ??IS IT CORRECT ??
OK ?OK ?
NFPA 20 NFPA 20
(5.14.6.3.1)(5.14.6.3.1)

STATE of OHIO FIRE SCHOOL - BGSU 44
NOTE: Backflow NOTE: Backflow
Preventer on DISCHARGE Preventer on DISCHARGE
side of Pump !! (5.26) side of Pump !! (5.26)
(5.14.9)(5.14.9)
PUMP PUMP
SuctionSuction
City By-Pass
City By-Pass
NOTE : Left Hand NOTE : Left Hand
Rotation ! *Rotation ! *
Counter Clockwise ! Counter Clockwise !
CONFIRM CONFIRM
BEFOREBEFORE you order you order
the PUMP !!the PUMP !!
NFPA 20 (5.22)NFPA 20 (5.22)
Study and Study and
understand the understand the
piping !piping !
Ask questions Ask questions
if you are not if you are not
sure !sure !
#2#2

??

NOTE: Test Header Piping is NOTE: Test Header Piping is
Connected Between the Connected Between the
Pump Discharge Check Valve Pump Discharge Check Valve
and the Discharge (System) and the Discharge (System)
Shut - Off Valve.Shut - Off Valve.
NFPA 20 (A.5.19.3.1)NFPA 20 (A.5.19.3.1)
Test Header Test Header
Control Valve Control Valve
and Pipingand Piping
City Water By-Pass
City Water By-Pass
What is the SUPPLY Voltage ?What is the SUPPLY Voltage ?
Is a Transfer Switch required ?Is a Transfer Switch required ?
DOUBLE CHECK and DOUBLE CHECK and CONFIRMCONFIRM
BEFOREBEFORE you order the pump you order the pump #3#3

Test Header
Control
Valve and
Piping
NOTE : No drain valve on NOTE : No drain valve on
bottom of test head pipe !bottom of test head pipe !
NFPA 20 (5.19.3.3.1)NFPA 20 (5.19.3.3.1)
FLOWFLOW

FIRE PUMP TEST FIRE PUMP TEST
CONNECTIONCONNECTION
(5.19.3)(5.19.3)
What hose threads are What hose threads are
required on the hose valves required on the hose valves
in your jurisdiction ?in your jurisdiction ?
CHECK and CONFIRMCHECK and CONFIRM
beforebefore you order the you order the
pump ! NFPA 20 pump ! NFPA 20
(5.19.3.2)(5.19.3.2)
#4#4

Fire Pump Test Fire Pump Test
HeadHead
Must be located where the
motor and controller will
not be damaged by
spraying or splashing
water.
Preferably outside of Preferably outside of
the pump house or the the pump house or the
pump room !pump room !
NFPA 20 (A.5.19.3.1)NFPA 20 (A.5.19.3.1)
FIRE FIRE
PUMP PUMP
TEST TEST
HEADHEAD

STATE of OHIO FIRE SCHOOL - BGSU 50
NFPA 20 A-2-14.3.1NFPA 20 A-2-14.3.1
(A.5.19.3.1)(A.5.19.3.1)
T
E
S
T
H
E
A
D
?
?
T
E
S
T
H
E
A
D

?
?
H
O
S
E

/
T
E
S
T


V
A
L
V
E
S
H
O
S
E

/
T
E
S
T


V
A
L
V
E
S

STATE of OHIO FIRE SCHOOL - BGSU 51FALK Steel Flex – APPROVED ??FALK Steel Flex – APPROVED ??
What coupling will be What coupling will be
accepted by LAHJ ? accepted by LAHJ ? FIND FIND
OUTOUT ! ASK ! “UL” ! ASK ! “UL”
Listed ?? NFPA 20 (6.5)Listed ?? NFPA 20 (6.5)
#5#5

STATE of OHIO FIRE SCHOOL - BGSU 52
Drive Shaft – APPROVED ?Drive Shaft – APPROVED ?

<FM> and IRI Bulletin 91-9

LOOSE SET-SCREWS ????LOOSE SET-SCREWS ????
DO NOT USE Elastomer
Couplings ON UL/FM
FIRE PUMPS !
< FM> 9-2006< FM> 9-2006
IRI Bulletin 91-9IRI Bulletin 91-9

STATE of OHIO FIRE SCHOOL - BGSU 57
TB Woods TB Woods
Elastomer Elastomer
CouplingCoupling

Diesel Driven Diesel Driven
HSC Fire PumpsHSC Fire Pumps
Engine HP De-rateEngine HP De-rate (11.2.2) (11.2.2) **
3% for every 1000’ 3% for every 1000’ ALT.ALT. above 300’above 300’
1% for every 10 degrees (F) above 771% for every 10 degrees (F) above 77
#6#6

(5.18.6.3)(5.18.6.3)
NEW: NFPA 20 (11.2.4.2) NEW: NFPA 20 (11.2.4.2)
Pressure-Limiting DriversPressure-Limiting Drivers

NOTE : With a PLD NOTE : With a PLD
All pump discharge All pump discharge
fittings, fittings, TOTO and and
including the including the
system shut off system shut off
valve, must be valve, must be
rated for the rated for the
MAXIMUM MAXIMUM
discharge (CHURN) discharge (CHURN)
pressure (5.15.2)pressure (5.15.2)
100 PSI100 PSI
170 PSI170 PSI
240 PSI240 PSI
FOR TESTING FOR TESTING
(14.2.7.3.7.3)(14.2.7.3.7.3)

CLARKE Fire Protection ProductsCLARKE Fire Protection Products

System Relief Valve is
Required when a Variable
Speed – OR --
Pressure Limiting Driver
is used (5.18.1.3 ) *

-------also---------
Required when
diesel fire pump churn
pressure X 1.21 (plus
maximum static suction)
exceeds the maximum
working pressure of the
system components
NFPA 20 (5.18.1.1) *
##77 REQUIRED ? REQUIRED ?

STATE of OHIO FIRE SCHOOL - BGSU 63
(5.18.1.1)(5.18.1.1)
NOTE: NOTE: This This
Pump did not Pump did not
require a main require a main
relief valve since relief valve since
the sum of the the sum of the
churn pressure churn pressure
times 121% times 121%
plus the max. plus the max.
suction pressure suction pressure
is only 142 PSI.is only 142 PSI.
No Relief No Relief
Valve ?Valve ?

NOTE: Flexible NOTE: Flexible
Dresser Pipe Dresser Pipe
Couplings to allow for Couplings to allow for
tank settling! tank settling!
( A.5.17 )( A.5.17 )
Water Water
supply is supply is
from a from a
ground ground
storage storage
tanktank
Combustion Air LouverCombustion Air Louver
NOTE: Relief NOTE: Relief
valve is piped to valve is piped to
waste outside waste outside
of building of building
(5.18.6) (5.18.6)
(A.5.18.5)(A.5.18.5)
Relief valve discharge is Relief valve discharge is
permitted to be piped permitted to be piped
back to the above ground back to the above ground
storage tank (5.18.6.3)storage tank (5.18.6.3)
Note: Packing drain Note: Packing drain
lines run to a floor lines run to a floor
drain.(5.12.6.2)drain.(5.12.6.2)

STATE of OHIO FIRE SCHOOL - BGSU 65
When Pump When Pump
Maximum Maximum
Discharge Discharge
Pressure is Pressure is
evaluated evaluated
with the 121 with the 121
% rule% rule
NFPA 20NFPA 20
(A.5.18.1)(A.5.18.1)

STATE of OHIO FIRE SCHOOL - BGSU 66
Relief Valve Waste
Relief Valve Waste
(5.18.6)
(5.18.6)
Engine Cooling Engine Cooling
Water PipingWater Piping – –
NFPA 20 (11.2.6.3) NFPA 20 (11.2.6.3)
NOTE: System (Main) Relief Valve (if
used) is connected to the pump
discharge BEFORE the Discharge
Check Valve !! (5.18.3)
(5.18.5)(5.18.5)

STATE of OHIO FIRE SCHOOL - BGSU 67
Where the cooling water contains
foreign material such as leaves, grass,
wood chips, etc – duplex filter type
strainers should be provided.
NFPA 20 (A.11.2.6.4)

ENGINE cooling ENGINE cooling
waste water waste water
MUST be piped so MUST be piped so
the flow can be the flow can be
VISUALLY VISUALLY
observed and observed and
confirmed. confirmed.
The discharge The discharge
pipe MUST be at pipe MUST be at
least one size least one size
larger than the larger than the
inlet. inlet.
NFPA 20 NFPA 20
(11.2.6.6)(11.2.6.6)

Cooling W
ater W
aste
Cooling W
ater W
aste
To Open D
rain
To Open D
rain
NFPA 20 (11.2.6.6)
NFPA 20 (11.2.6.6)

EMERGENCY MANUAL STARTING EMERGENCY MANUAL STARTING
PROCEDURE - NFPA 20 (11.6.6)PROCEDURE - NFPA 20 (11.6.6)
CC = Cooling Water = Cooling Water
F F = Fuel = Fuel
CC = Crank = Crank

#1#1
CCOOLING OOLING
WATERWATER
#2 #2
FFUELUEL
# 3# 3

CCRANKRANK
NOTE !NOTE !
SET at 120 % of
Rated RPM *****
EMERGENCY EMERGENCY
MANUAL MANUAL
STARTING STARTING
PROCEDUREPROCEDURE
(11.6.6)(11.6.6)
BE SURE THAT YOU
KNOW WHERE
THE OVERSPEED
RESET IS ON
EVERY TYPE OF
ENGINE THAT YOU
SELL or INSTALL !!
INSTRUCT THE
OWNER’S
REPRESENTATIVE
OR OPERATOR.
CUMMINS

# # 11 For EMERGENCY For EMERGENCY
OPERATION of “ANY ENGINE” OPERATION of “ANY ENGINE”
the by-pass the by-pass ANDAND normal normal
COOLING WATER VALVES must COOLING WATER VALVES must
ALL be - OPEN ! ALL be - OPEN !

STATE of OHIO FIRE SCHOOL - BGSU 74
##3 3 CRANKCRANK
BATTERY 1 or 2BATTERY 1 or 2
#2#2
With Newer Engines, the toggle switch, when in With Newer Engines, the toggle switch, when in MANUALMANUAL
will turn on both will turn on both FUELFUEL and and COOLING WATERCOOLING WATER

NFPA 20 (11.5.3) NFPA 20 (11.5.3)
Exhaust pipes Exhaust pipes
shall be installed shall be installed
with clearances of with clearances of
at least 9” to at least 9” to
combustible combustible
material.material.
Insulate or guard exhaust Insulate or guard exhaust
pipe???pipe???

NFPA 20 NFPA 20
(11.5.3.3)(11.5.3.3)

NOTE: Victaulic NOTE: Victaulic
fittings with fittings with
rubber gaskets ?rubber gaskets ?
FLEX CONNECTORFLEX CONNECTOR
¼” MAX. ¼” MAX.
MISALIGNMENT ??MISALIGNMENT ??

Exhaust FanExhaust Fan andand Air Intake Louver Air Intake Louver
NFPA 20NFPA 20
(11.3.2.4)(11.3.2.4)
NFPA 20NFPA 20
(11.3.2.3)(11.3.2.3)
MAX 120 MAX 120
degrees Fdegrees F

NOTE : UL Listed tanks must NOTE : UL Listed tanks must
have a metal “ UL ” have a metal “ UL ”
nameplate attached to the nameplate attached to the
tank !tank !
LOOK FOR IT !LOOK FOR IT !
(12.4.1.3 - 11) Tank must (12.4.1.3 - 11) Tank must
be kept 2/3 full !be kept 2/3 full !
Fuel Fuel
ReturnReturn

STATE of OHIO FIRE SCHOOL - BGSU 80

FUEL Tank Drains FUEL Tank Drains
NFPA 20 NFPA 20
A-8-4.6 (A.11.4.6)A-8-4.6 (A.11.4.6)
Top 5% Top 5% andand bottom 5% of bottom 5% of
tank volume is not used in tank volume is not used in
determining capacity of tank. determining capacity of tank.
NFPA 20 8-4.3 (11.4) *NFPA 20 8-4.3 (11.4) *
Bottom 5%
Bottom 5%

Fuel Supply Valve Fuel Supply Valve
locked in OPEN locked in OPEN
position …NFPA 20 position …NFPA 20
A-8-4.6 (A.11.4.6)A-8-4.6 (A.11.4.6)
NEW: 2003 NEW: 2003
NFPA 20 NFPA 20
(11.4.6.2) (11.4.6.2)
Fuel linesFuel lines
no copper no copper
or or
galvanizedgalvanized
The fuel supply The fuel supply
opening to the engine opening to the engine
shall be no lower shall be no lower
than the engine fuel than the engine fuel
pump centerline.pump centerline.
NFPA 20 (11.4.5.4)NFPA 20 (11.4.5.4)

STATE of OHIO FIRE SCHOOL - BGSU 83
Fuel tank capacity NFPA 20 (11.4.3) *
Tank location inside NFPA 20 (11.4.5.6)
Fill and vent piping NFPA 20 (11.4.5.8)
Fuel Level Fuel Level
(11.4.5.7)(11.4.5.7)
Low Fuel Low Fuel
Switch * Switch *
SET AT 2/3 SET AT 2/3
(12.4.1.3)(12.4.1.3)
Fuel Fuel
ReturnReturn

10 ‘
The flash arrester The flash arrester
should be a minimum should be a minimum
11’- 0” above the top 11’- 0” above the top
of the fuel tank NFPA of the fuel tank NFPA
20 (A.11.4.6)20 (A.11.4.6)

NOTE : Dual Flash NOTE : Dual Flash
Arresters Arresters
(VENTS) for (VENTS) for
“DOUBLE WALL” “DOUBLE WALL”
Fuel Tanks !Fuel Tanks !

Tank Fill SHOULD BE Piped Tank Fill SHOULD BE Piped
to the outside to the outside
(A.11.4.5)(A.11.4.5)

Some “LAHJ” REQUIRE a containment dike, Some “LAHJ” REQUIRE a containment dike,
even when a double wall tank is provided ! even when a double wall tank is provided !
CHECK and LEARN CHECK and LEARN
THE LOCAL CODES !THE LOCAL CODES !
5 PSI Hydro-test at the JOB ??5 PSI Hydro-test at the JOB ??
To To
EngineEngine
#8#8

Vertical In-Line Fire PumpVertical In-Line Fire Pump
SuctionSuction
InletInlet

STATE of OHIO FIRE SCHOOL - BGSU 89
ALL Pump Rooms are
Required to have a FLOOR
DRAIN!!! (5.12.6.2)
Circulation “CASE” Relief
Valve Piped To A Floor
Drain. (5.11)*

Packing Drain
Lines Run to a
Floor Drain. Do
not combine
with case relief
valve piping! !!
(5.11.1.5)

STATE of OHIO FIRE SCHOOL - BGSU 90
NOTE STRAINER!NOTE STRAINER!

1
0
p
ip
e

1
0
p
ip
e
d
ia
. ?
?
d
ia
. ?
?
NFPA 20 (6.3.4) NFPA 20 (6.3.4)
NOTE: Strainer requirement NOTE: Strainer requirement
was removed after 2007 !was removed after 2007 !
#9#9

STATE of OHIO FIRE SCHOOL - BGSU 91
(6.3.4) A Hand Hole is “NOT” a (6.3.4) A Hand Hole is “NOT” a
Strainer!! Strainer!! Could You Get Rocks Could You Get Rocks
and Boards out of this small “ and Boards out of this small “
PIPE PLUG “ opening ??PIPE PLUG “ opening ??
NO SUCTION STRAINER ?? WHY NOT ?NO SUCTION STRAINER ?? WHY NOT ?

Could YOU get this stuff out of a “PIPE PLUG Could YOU get this stuff out of a “PIPE PLUG
OPENING” in the bottom of an Inline Fire Pump ? OPENING” in the bottom of an Inline Fire Pump ?
Could this be why a strainer Is “REQUIRED” ?Could this be why a strainer Is “REQUIRED” ?

Vertical Turbine Fire PumpVertical Turbine Fire Pump
NFPA 20 (7.4.1)NFPA 20 (7.4.1)

NOTE: Automatic air releaseNOTE: Automatic air release
NFPA 20 (7.3.5.2.3)NFPA 20 (7.3.5.2.3) “SHALL BE”“SHALL BE”
Located between the fire pump and Located between the fire pump and
the discharge check valve. *the discharge check valve. *
Motor HP and Motor HP and
THRUST limits THRUST limits must must
meet or exceedmeet or exceed
those of the Fire those of the Fire
Pump. Pump. CHECK !CHECK !
(7.5.1.1) (9.5.2)(7.5.1.1) (9.5.2)
#10#10

STATE of OHIO FIRE SCHOOL - BGSU 95
NOTE:NOTE: Automatic air release “SHALL BE” Located Automatic air release “SHALL BE” Located
in the highest point in the discharge line, between in the highest point in the discharge line, between
the fire pump and the discharge check valve. the fire pump and the discharge check valve. NFPA NFPA
20 (7.3.5.2.3)20 (7.3.5.2.3) **

STATE of OHIO FIRE SCHOOL - BGSU 96
NFPA 20 (7.6.2.3)NFPA 20 (7.6.2.3)
ACCESS FOR REMOVAL ?ACCESS FOR REMOVAL ?

NFPA 20 ( 7.4.3.7 ) NFPA 20 ( 7.4.3.7 )
I– beams must be parallel I– beams must be parallel
to the driver !to the driver !

STATE of OHIO FIRE SCHOOL - BGSU 99
One degree of off-set is the preferred One degree of off-set is the preferred
angle, per drive shaft manufacturers!! angle, per drive shaft manufacturers!!
NFPA 20 (6.5) (7.5.1.7.2)NFPA 20 (6.5) (7.5.1.7.2)

CHECK the pump HP and THRUST requirements. CHECK the pump HP and THRUST requirements.
CHECK the gear HP and THRUST limits. CHECK the gear HP and THRUST limits.
CHECK the engine HP rating.CHECK the engine HP rating.
THIS MUST BE DONE BEFORE THE PUMP IS THIS MUST BE DONE BEFORE THE PUMP IS
ORDERED !!ORDERED !! ( 7.5.1.6.4 ) ( 7.5.1.6.4 )
#11#11

STATE of OHIO FIRE SCHOOL - BGSU 101
Top Shaft Nut is Top Shaft Nut is
used to raise used to raise
shaft and shaft and
impellers impellers
approximately approximately
1/81/8 “ inch. (see “ inch. (see
instruction instruction
book)book)
NFPA 20 (7.6.1.3)

Water Vel,
2’/sec Max
Water Vel.Water Vel.
1’/sec Max1’/sec Max
Screen openings equal to 1 Screen openings equal to 1
sq. in. for every GPM sq. in. for every GPM
(pump capacity at 150%) (pump capacity at 150%)
(at LOWEST Water LEVEL) (at LOWEST Water LEVEL)
NFPA 20 (5.14.8)NFPA 20 (5.14.8)
Confirm proper Confirm proper
submergence submergence
(Pump Length) *(Pump Length) *
(7.2.2.2)(7.2.2.2)
NFPA 20 (A.7.2.2.2) (5.14.8)NFPA 20 (A.7.2.2.2) (5.14.8)
#12#12
**

Removable screens NFPA 20 (5.14.8.3)Removable screens NFPA 20 (5.14.8.3)
Intake size NFPA 20 (5.14.8.4)Intake size NFPA 20 (5.14.8.4)

Removable screens NFPA 20 A4-2.2.2Removable screens NFPA 20 A4-2.2.2 (5.14.8.3)(5.14.8.3)
Intake size NFPA 20 A4-2.2 Intake size NFPA 20 A4-2.2 (5.14.8.4)(5.14.8.4)

STATE of OHIO FIRE SCHOOL - BGSU 106
NFPA 20 2003 NFPA 20 2003
Zebra Mussel Infestation Zebra Mussel Infestation
(5.14.8.12)(5.14.8.12)
With a vertical turbine fire With a vertical turbine fire
pump a plugged screen will pump a plugged screen will
affect the water level in the affect the water level in the
sump and a plugged basket sump and a plugged basket
strainer on the bottom of the strainer on the bottom of the
pump will reduce the total pump will reduce the total
pump performance.pump performance.

VTFP INTAKE PROBLEMS………..VTFP INTAKE PROBLEMS………..
Removable screens NFPA 20 A4-2.2.2 (5.14.8.3)(5.14.8.3)
Intake size ???Intake size ??? NFPA 20 A4-2.2 NFPA 20 A4-2.2 (5.14.8.4)(5.14.8.4)

2 ft/sec and 2 ft/sec and
1 Sq. Inch per 1 Sq. Inch per
GPM at GPM at
150% Flow ?150% Flow ?

Pond Maintenance Pond Maintenance
-OR--OR-
Lack of !!!Lack of !!!

Proper pond Proper pond
MaintenanceMaintenance

PART 2PART 2
FIRE PUMPFIRE PUMP
Acceptance Testing Acceptance Testing
In The State of In The State of
OHIOOHIO

FIRE PUMPFIRE PUMP ACCEPTANCE TEST ACCEPTANCE TEST
1. Check for company and individual LICENSING.1. Check for company and individual LICENSING.
2. Check for HYDRO and FLUSHING CERTIFICATES.2. Check for HYDRO and FLUSHING CERTIFICATES.
3. Check for CERTIFIED shop test curve vs. SYSTEM DEMAND.3. Check for CERTIFIED shop test curve vs. SYSTEM DEMAND.
4. Has the pump been properly ALIGNED and PRE-TESTED???4. Has the pump been properly ALIGNED and PRE-TESTED???
5. Record all pump, driver, and controller data. (HP, VOLTAGE, etc.)5. Record all pump, driver, and controller data. (HP, VOLTAGE, etc.)
6. Look system over…sensing lines, reducers, piping , water supply….6. Look system over…sensing lines, reducers, piping , water supply….
7. Check for CERTIFICATE of CALIBRATION for test equip. (SAFE??)7. Check for CERTIFICATE of CALIBRATION for test equip. (SAFE??)
8. Decide in advance just what is to take place during the test8. Decide in advance just what is to take place during the test
9. Operate the pump at churn (no flow)….temp., brgs., packing, etc.9. Operate the pump at churn (no flow)….temp., brgs., packing, etc.
10. Record PSI, RPM, AMPS, VOLTS, (compare and plot results).10. Record PSI, RPM, AMPS, VOLTS, (compare and plot results).
11. Operate the pump at additional flow points 50%, 100%, 150%,. 11. Operate the pump at additional flow points 50%, 100%, 150%,.
12. Record PSI, RPM, AMPS, VOLTS, (compare and plot results).12. Record PSI, RPM, AMPS, VOLTS, (compare and plot results).
13. 6 AUTO Starts and 6 MANUAL Starts. (One Full Load Start)13. 6 AUTO Starts and 6 MANUAL Starts. (One Full Load Start)
14. Controller and Driver alarms connected / tested (electric and diesel)14. Controller and Driver alarms connected / tested (electric and diesel)
15. Start and Stop PSI for Main Fire Pump and Jockey Pump.15. Start and Stop PSI for Main Fire Pump and Jockey Pump.
16. Low Suction Control Set Point AND Alarm Connected???16. Low Suction Control Set Point AND Alarm Connected???
17. Operators trained in maintenance and weekly testing???17. Operators trained in maintenance and weekly testing???
18. Review test results - ASK QUESTIONS!!!!!! Do it again ???18. Review test results - ASK QUESTIONS!!!!!! Do it again ???
19. STOP!!!! Don’t accept it if the data is not CORRECT!!!!19. STOP!!!! Don’t accept it if the data is not CORRECT!!!!

1. Check for company and 1. Check for company and
individual LICENSING as individual LICENSING as
REQUIRED by STATE or REQUIRED by STATE or LAHJLAHJ..
CHECK EVERYONE who touches the
equipment…pump guy, fitters, controller
guy, and engine guy!!! They all must have
a license to service, test, repair, or install
any fire protection equipment in the State
of Ohio.
Compare with driver’s license…..
Check every year…..
RECORD the information…….

RECORD NAMES OF ALL FIELD RECORD NAMES OF ALL FIELD
ACCEPTANCE TEST PERSONNELACCEPTANCE TEST PERSONNEL
(LAHJ)(LAHJ) FIRE DEPT OFFICIAL FIRE DEPT OFFICIAL
OWNER’S REPRESENTATIVEOWNER’S REPRESENTATIVE
MAINTENANCE PERSONNELMAINTENANCE PERSONNEL
INSTALLING CONTRACTORINSTALLING CONTRACTOR
AUTHORIZED FIRE PUMP REPAUTHORIZED FIRE PUMP REP
AUTHORIZED CONTROLLER REPAUTHORIZED CONTROLLER REP
AUTHORIZED ENGINE REPAUTHORIZED ENGINE REP
INSURANCE REPRESENTATIVEINSURANCE REPRESENTATIVE

STATE of OHIO FIRE SCHOOL - BGSU 114

1.1.Check for HYDRO and Check for HYDRO and
FLUSHING CERTIFICATES.FLUSHING CERTIFICATES.
NFPA 20 11-1.1 (14.1)
Was the UUnderground and AAboveground piping
installed, flushed, and hydro-tested by a “Licensed”
contractor ?
Did “YOU”“YOU” witness flushing and hydro-test??
Did installing contractor “OFFER” to have you witness
the above and provide you with the mandatory test
certificates …… NFPA 20 11-1.3 (14.1.3)
Someone had to sign and witness (WHO ??)(WHO ??)
NO TEST CERTIFICATES???? WHY NOT???
NFPA 20 (14.1.3)
What happens when the pump plugs with rocks or a
pipe fitting blows apart?????

Table (14.1.1.1[a]) Table (14.1.1.1[a]) Minimum Flush RatesMinimum Flush Rates. .
Contractor may have a calculated system Contractor may have a calculated system
demand which, if greater, will require higher demand which, if greater, will require higher
flush rates than those listed below.flush rates than those listed below.
Pipe SizePipe Size Flow RateFlow Rate
in.in.mmmm gpm gpm L/minL/min
44 102102 590 590 2,2332,233
66 152152 1,360 1,360 5,1485,148
88 203203 2,350 2,350 8,8958,895
1010254254 3,670 3,670 13,89113,891
1212305305 5,290 5,290 20,02320,023
NFPA 20 (14.1.1.1) FLUSHINGNFPA 20 (14.1.1.1) FLUSHING

ROCKS IN IMPELLERROCKS IN IMPELLER
Was this system properly flushed?? NFPA 20 (14.1)

System was flushed for 2 hours with 3 hoses !System was flushed for 2 hours with 3 hoses !
Problem : Hoses were ¾” garden hoses !!!Problem : Hoses were ¾” garden hoses !!!

3. Check for PUMP CERTIFIED
SHOP TEST CURVE. Compare
it to the SYSTEM DEMAND.
NFPA 20 2-162-16 and 11-2.3 (14.2.4)
Find out how many GPM are required and
how much PSI is needed to make the
sprinkler system work… Will the fire
pump and water supply do it ?
Fire Pumps are selected for “SYSTEM
DESIGNS” which can utilize any pump
flow up to 150% of rated capacity.
NFPA 20 2-3 and A-2-3 (5.8)

Sample Pump CurveSample Pump Curve

4. Has the Pump and Driver 4. Has the Pump and Driver
been ALIGNED, LUBRICATED, been ALIGNED, LUBRICATED,
and PRE-TESTED???and PRE-TESTED???
Pump and driver MUSTMUST be field-aligned
NFPA 20 3-5 (6.5.2) and pre-tested PRIORPRIOR to
the field acceptance test - includes electrical includes electrical
NFPA 20 (14.2.3) NFPA 20 (14.2.3) so that inspector’s time is
not wasted standing around…….. MANY
jurisdictions charge an additional fee if re-
testing is required due to problems with a
system which has not been pre-tested prior
to the acceptance test!!!!

STATE of OHIO FIRE SCHOOL - BGSU 124

STATE of OHIO FIRE SCHOOL - BGSU 125

STATE of OHIO FIRE SCHOOL - BGSU 126
GAP MUST BE GAP MUST BE
EQUAL - TOP TO EQUAL - TOP TO
BOTTOM AND BOTTOM AND
SIDE TO SIDE. SIDE TO SIDE.
Within .005”Within .005”
USE OF DIAL USE OF DIAL
INDICATORS OR INDICATORS OR
LASERS IS LASERS IS
PREFERRED.PREFERRED.
Angular Angular
AlignmentAlignment

STATE of OHIO FIRE SCHOOL - BGSU 127
Parallel alignment should be less than .005 Parallel alignment should be less than .005
“VERTICAL and HORIZONTAL”“VERTICAL and HORIZONTAL”
NOTE : The NOTE : The
coupling halves coupling halves
should remain should remain
disconnected disconnected
until rotation until rotation
has been has been
checked!checked!

STATE of OHIO FIRE SCHOOL - BGSU 128
AFTER AFTER alignment and alignment and
rotation have been rotation have been
checked the coupling checked the coupling
should be lubricated should be lubricated
and re-assembled. and re-assembled.
Be sure to check the Be sure to check the
set screws for set screws for
tightnesstightness
FALK FALK
Steelflex Steelflex
CouplingCoupling

After checking the alignment, leave the pump and
driver uncoupled until after rotation check !
Pump rotation should be checked with the
coupling not not connected……..**
Pump was 6 % Low.
4 Year Old 4 Year Old
PumpPump

STATE of OHIO FIRE SCHOOL - BGSU 130

STATE of OHIO FIRE SCHOOL - BGSU 131
NOTE: The quarter on a NOTE: The quarter on a
properly installed, grouted, properly installed, grouted,
aligned, and lubricated aligned, and lubricated
fire pump!!!fire pump!!!
125 HP, 1760 RPM Motor - 125 HP, 1760 RPM Motor -
in operationin operation, ,
NO VIBRATION ! NO VIBRATION !
NFPA 20 ( 14.2.6 )NFPA 20 ( 14.2.6 )

Add Grease Add Grease
slowly !slowly !
Check For Check For
Excess GreaseExcess Grease
After greasing be After greasing be
sure to check sure to check
torque of ALL torque of ALL boltsbolts
and and set screws !set screws !

NOTE: NOTE: Insert Insert
clean grease clean grease
slowly until old slowly until old
grease is forced grease is forced
out of the drain out of the drain
hole withhole with PLUG PLUG
REMOVED !!REMOVED !!
NOTE : Operate the NOTE : Operate the
pump for 15 – 30 min. pump for 15 – 30 min.
before replacing the before replacing the
plug !plug !

Motor oil full ? Motor oil full ?
Check it ! Check it !
Gear oil full ? Gear oil full ?
Check it !Check it !
What oil did they use ?? What oil did they use ??
ASK !! ASK !!

Coolant level full ? Coolant level full ?
Engine Lube Engine Lube
Oil and Oil and
Coolant Coolant
Checked ?Checked ?
Engine Guy ?Engine Guy ?

STATE of OHIO FIRE SCHOOL - BGSU 136
HAS THE PUMP HAS THE PUMP
BEEN PRE-TESTED ??BEEN PRE-TESTED ??
Is it required ?Is it required ?

5. 5. RECORD RECORD all equipment data: all equipment data:
pump, driver, and controller. (HP, pump, driver, and controller. (HP,
RPM, VOLTAGE, SN, etc.)RPM, VOLTAGE, SN, etc.)
Are the fire pump, driver, and controller
ALL “ULUL” listed or “FMFM” approved????
CHECK THE NAME PLATES !!!CHECK THE NAME PLATES !!!
Motor and controller voltage and HP must
be the same!!! 200 volt is “not” the same
as 230 volt!!! The required pump HP must
not exceed the driver rated HP X 1.15 SF!!!

STATE of OHIO FIRE SCHOOL - BGSU 139

STATE of OHIO FIRE SCHOOL - BGSU 140
Incoming Power SupplyIncoming Power Supply (voltage) MUST (voltage) MUST
Be the “SAME” as the Main Fire Pump Be the “SAME” as the Main Fire Pump
Controller “AND” the UL Listed Fire Pump Controller “AND” the UL Listed Fire Pump
MotorMotor !! NFPA 20 (9.1.3)NFPA 20 (9.1.3)
NFPA 70 Article 695NFPA 70 Article 695 CHECK IT !!*CHECK IT !!*

THE AVAILABLE POWER MUST THE AVAILABLE POWER MUST
MATCH THE FIRE PUMP MOTOR MATCH THE FIRE PUMP MOTOR
NAMEPLATE AND CONTROLLER NAMEPLATE AND CONTROLLER
NAMEPLATE VOLTAGES - LOOK FOR NAMEPLATE VOLTAGES - LOOK FOR
CHANGED OR ALTERED CHANGED OR ALTERED
NAMEPLATES THAT ATTEMPT TO NAMEPLATES THAT ATTEMPT TO
COVER UP A MISTAKE !!!!COVER UP A MISTAKE !!!!
**

**
NFPA 20 (10.3.4.4)NFPA 20 (10.3.4.4)
Means shall be provided on Means shall be provided on
the exterior of the the exterior of the
controller for measuring all controller for measuring all
line amps and volts.line amps and volts.

6. Look the 6. Look the ‘‘SYSTEM”‘‘SYSTEM” over… over…
Is it “Is it “SAFESAFE”? Is it “CORRECT”? ”? Is it “CORRECT”?
Power, sensing lines, reducers, Power, sensing lines, reducers,
UL/FM piping , water supply UL/FM piping , water supply.
Jockey and main fire pump must each have a separate ½ “
sensing line with 2 ea. 3/32 “ orifices located at least 5’ – 0”
apart . `NFPA 20 7-5.2.1 and appendix!! (10.5.2.1.6)NFPA 20 7-5.2.1 and appendix!! (10.5.2.1.6)
Case relief valve (electric fire pumps) piped to a REQUIRED REQUIRED
floor drain inin the pump room??? NFPA 20 2-6.1 and 2-7.6
(5.12.6.2)
Do not pipe Case Relief Valve discharge and Packing Drain lines
together into a common drain line (5.11.1.5)

Pump coupling and guard secured???

IS THIS A CONFINED SPACE????IS THIS A CONFINED SPACE????
Is the “TEST SET UP” (test hoses, rack, Is the “TEST SET UP” (test hoses, rack,
and play pipes) pump location “and play pipes) pump location “SAFE”SAFE”??

Would Would
““YOUYOU” go ” go
down here down here
to test this to test this
pump????pump????
OSHA APPROVED ???OSHA APPROVED ???
NFPA 25 4.7.1 NFPA 25 4.7.1
and A.4.8and A.4.8

( A.5.12) DRAINAGE and VENTILATION ( A.5.12) DRAINAGE and VENTILATION
))

STATE of OHIO FIRE SCHOOL - BGSU 146
Note : Rods on Note : Rods on
transition piece!!transition piece!!
NOTE : This fire pump
develops 165 psi at churn !
The class 125 fittings are
good for a maximum
working pressure of 175 psi.
(5.7.4.1)

STATE of OHIO FIRE SCHOOL - BGSU 147
NO RODS !!!
SAFE ??
Look at the pipe
fittings !!
This pump installation
develops 213 PSI at
churn.
A 125 lb flanged fitting
is rated at 175 PSI
maximum working
pressure !! NFPA 20
(5.7.4.1)
NFPA 13 15.1.6.1.1NFPA 13 15.1.6.1.1

STATE of OHIO FIRE SCHOOL - BGSU 148
TEST HEAD ??TEST HEAD ??
Test Header outside Test Header outside
of the pump house or of the pump house or
“IN” the pump room “IN” the pump room
??
NFPA 20 (A.5.19.3.1)NFPA 20 (A.5.19.3.1)

STATE of OHIO FIRE SCHOOL - BGSU 149
Has the Voltage Been Checked ??Has the Voltage Been Checked ??
Check NFPA 70E and NFPA 25 A.4.8Check NFPA 70E and NFPA 25 A.4.8
WHERE DOES THE POWER COME FROM ? WHERE DOES THE POWER COME FROM ?
IS THERE ANOTHER DISCONNECT OR IS THERE ANOTHER DISCONNECT OR
FUSES ??? FUSES ???
PRESSURE PRESSURE
RECORDERRECORDER

Each “Fire Pump” Controller MUST have IT’S Each “Fire Pump” Controller MUST have IT’S
OWN Pressure Sensing Line and Pressure OWN Pressure Sensing Line and Pressure
Recorder Recorder
NFPA 20 (10.5.2.1.6) and (12.5.2.1.6) *NFPA 20 (10.5.2.1.6) and (12.5.2.1.6) *

NOTE: Main fire pump NOTE: Main fire pump
controller sensing line is controller sensing line is
connected between the connected between the
pump discharge check pump discharge check
valve and the system shut valve and the system shut
- off valve. (10.5.2.1.6) - off valve. (10.5.2.1.6)

NFPA 20 10.5.2.1*NFPA 20 10.5.2.1*
One sensing line One sensing line
Two (2) CONTROLLERS ??Two (2) CONTROLLERS ??
NFPA 20NFPA 20
(10.5.2.1.6)(10.5.2.1.6)
PressurePressure
RecorderRecorder
MISSING!MISSING!

One sensing line for 3 controllers ??One sensing line for 3 controllers ??

Pressure RecorderPressure Recorder
Each fire pump controller must have it’s own recorder !!Each fire pump controller must have it’s own recorder !! (10.5.2.1.6)(10.5.2.1.6)

*On the pump suction, a listed OSY valve is
required: no valve, other than a listed OSY valve
is allowed within 50 feet of the pump suction
flange NFPA 20 (5.14.5.2)*
*When located in the suction pipe of a fire pump,
back flow prevention devices, check valves, and
pipeline strainers (for in-line pumps) shall be no shall be no
closer than 10 pipe diameters from the pump closer than 10 pipe diameters from the pump
suction flangesuction flange. NFPA 20 (5.14.6.3.1) (5.26.3)*

STATE of OHIO FIRE SCHOOL - BGSU 156
NOTE ROTATION ?NOTE ROTATION ?
Counter-Clockwise Counter-Clockwise
LEFT Hand *LEFT Hand *
Impeller Turns Impeller Turns
Toward The Suction !Toward The Suction !
Have The Wire Have The Wire
Connections Been Connections Been
Checked By the Checked By the
Electrician and/or Electrician and/or
Controller Guy ?Controller Guy ?
SUCTION
OSY OSY
ValveValve

STATE of OHIO FIRE SCHOOL - BGSU 157
!!
(5.14.6.4)(5.14.6.4)
Elbows and tees with a centerline Elbows and tees with a centerline
plane parallel to a horizontal split-case plane parallel to a horizontal split-case
pump shaft shall be avoided. See pump shaft shall be avoided. See
Figure A-2-9.6. (5.14.6.3.1)Figure A-2-9.6. (5.14.6.3.1)
If there is a parallel elbow : YOU If there is a parallel elbow : YOU
MUST HAVE 10 PIPE DIAMETERS MUST HAVE 10 PIPE DIAMETERS
of STRAIGHT PIPE BETWEEN THE of STRAIGHT PIPE BETWEEN THE
ELBOW AND PUMP SUCTION ELBOW AND PUMP SUCTION
FLANGE (5.14.6.3.2)FLANGE (5.14.6.3.2)

STATE of OHIO FIRE SCHOOL - BGSU 158
OSY OSY
Suction Suction
ValveValve
NOTE: Backflow Preventer!
NOTE: The long straight run of
suction pipe after a
HORIZONTAL 90 DEGREE
ELBOW !
More than 10 pipe diameters ?
(5.14.6.3.2)

NOTE STRAINER!NOTE STRAINER!

1
0
p
ip
e

1
0
p
ip
e
d
ia
. ?
?
d
ia
. ?
?
OSY OSY
ValveValve
NFPA 20 3-3.4 (6.3.4)NFPA 20 3-3.4 (6.3.4)

Batteries Properly Connected and Batteries Properly Connected and
Electrolyte Topped Off ?? USE CAUTION Electrolyte Topped Off ?? USE CAUTION
WHEN FILLING AND CONNECTING WHEN FILLING AND CONNECTING
LEAD ACID BATTERIES !!!LEAD ACID BATTERIES !!!
Dual Dual
BatteriesBatteries
Have The Wire Connections been
Checked at “BOTH”“BOTH” The Engine and
Controller ???
Wires Correct and Terminals “TIGHT”Wires Correct and Terminals “TIGHT”

DO NOT USE FORKED DO NOT USE FORKED
CONNECTORS FM F27-92CONNECTORS FM F27-92

7. Check for CERTIFICATE of 7. Check for CERTIFICATE of
CALIBRATION for test equip.CALIBRATION for test equip.
““TEST GAUGES”TEST GAUGES” and “CLAMP-ON VOLT/AMMETERS” should be re-
calibrated and certified every 12 months (by an approved testing and
calibration facility)….Most never get calibrated and certified ! NFPA 20 NFPA 20
(A.14.2.7.1) (A.14.2.7.1)
““TEST GAUGES”TEST GAUGES” will have an accuracy of; will have an accuracy of;
0.25%0.25% (ASME Grade 3A) (ASME Grade 3A)
or sometimes-
0.5%0.5% (ASME Grade 2A) pocket (ASME Grade 2A) pocket “TEST GAUGES”“TEST GAUGES” or inspectors or inspectors
“TEST GAUGES”.“TEST GAUGES”.
DEMAND a “Certificate of Calibration” from an approved testing and
calibration facility –then- Check and Verify the Serial Numbers! If you
suspect a problem, write down the phone number of the calibration
facility and phone them!!

Look for Look for “TEST GAUGE”“TEST GAUGE” on the dial. on the dial.

Calibrated “TEST GAUGES” Calibrated “TEST GAUGES”
plus CALIBRATION plus CALIBRATION
DOCUMENTATION as per DOCUMENTATION as per
NFPA 20 A-11-2.6.1 NFPA 20 A-11-2.6.1
(A.14.2.7.1)(A.14.2.7.1)

8. Decide in advance just what is 8. Decide in advance just what is
to take place during the testing….to take place during the testing….
WHO WILL TAKE CHARGE ?WHO WILL TAKE CHARGE ?
What test equipment will be used ?
What flow points (PITOTS) will be targeted ?
Who will do what ????
TAKE THE PITOT READINGS ?
ADJUST and HOLD THE TEST VALVES ?
TAKE PRESSURE AND RPM READINGS ?
RECORD and PLOT THE TEST RESULTS ?
TAKE THE ELECTRICAL READINGS ?
PRE RUN EQUIPMENT CHECK LIST ??PRE RUN EQUIPMENT CHECK LIST ??

SOMEONE HAS SOMEONE HAS
TO TAKE CHARGE TO TAKE CHARGE
OF THE PUMP OF THE PUMP
TEST ?TEST ?
Will It Be The Sprinkler Will It Be The Sprinkler
Guy, The Local Fire Guy, The Local Fire
Official, The Pump Guy, Official, The Pump Guy,
The Insurance Guy, or The Insurance Guy, or
The Owners Rep ?The Owners Rep ?
SOMEONE HAS TO SOMEONE HAS TO
STEP UP TO THE STEP UP TO THE
PLATE !!PLATE !!

FLOW TEST EQUIPMENTFLOW TEST EQUIPMENT

STATE of OHIO FIRE SCHOOL - BGSU 170
FLOW METERFLOW METER
When a flow meter is When a flow meter is
used, you must have an used, you must have an
air vent valve or auto air air vent valve or auto air
release valve to eliminate release valve to eliminate
ALLALL air from the flow air from the flow
meter piping !meter piping !
10 X D10 X D
4 X D4 X D

<FM> Short Play Pipe
Underwriters Play Pipe
1 ¾ ” Nozzle
1 1/8 ” Nozzle
Pitot
Tube

STATE of OHIO FIRE SCHOOL - BGSU 172
FREE FLOW WITH HOSES AND PLAYPIPESFREE FLOW WITH HOSES AND PLAYPIPES

STATE of OHIO FIRE SCHOOL - BGSU 173
Each additional pitot Each additional pitot
tube, used during the tube, used during the
test, will increase the test, will increase the
chance for error! chance for error!
Use 1 pitot tube and 1 Use 1 pitot tube and 1
gauge which has gauge which has
been checked prior to been checked prior to
the start of the test!the start of the test!

STATE of OHIO FIRE SCHOOL - BGSU 174

STATE of OHIO FIRE SCHOOL - BGSU 175
In Areas where water shortages exist, In Areas where water shortages exist,
the test water can be discharged back the test water can be discharged back
to the stored supply !to the stored supply !

STATE of OHIO FIRE SCHOOL - BGSU 176
THERBOLIZER 6THERBOLIZER 6

STATE of OHIO FIRE SCHOOL - BGSU 177
Test Header Test Header
arranged to SAFELY arranged to SAFELY
discharge directly to discharge directly to
the Pondthe Pond

STATE of OHIO FIRE SCHOOL - BGSU 178

STATE of OHIO FIRE SCHOOL - BGSU 179
AA
BB
CC
.
.
.
““CHURN” CHURN”
Pressure Pressure
“RATED 100% FLOW “ 1
Hose, Pitot of 32 PSI
“ 150 % FLOW “
2 Hoses, Pitots
of 18 PSI
What Flow Points Will Be Targeted?What Flow Points Will Be Targeted?

<FM> FLOW CHART<FM> FLOW CHART

To determine To determine
FEET of HEAD FEET of HEAD
multiplymultiply (H) (H)
(net PSI) X 2.31*(net PSI) X 2.31*
To determine (H) To determine (H)
(net PSI) (net PSI) subtract subtract
Suction PSI Suction PSI from from
Discharge PSIDischarge PSI
150 PSI150 PSI
50 PSI50 PSI
100 PSI100 PSI
231’ (ft)231’ (ft)
Who will observe Who will observe
and record the and record the
test results ??test results ??

STATE of OHIO FIRE SCHOOL - BGSU 182
WHO Will Take The
Pitot Readings ??
Does that person know
the CORRECT Procedure ?

To Obtain a To Obtain a
Correct Correct
Pressure Pressure
Reading With A Reading With A
Pitot Tube, It Pitot Tube, It
“MUST” Be “MUST” Be
Held In The Held In The
Center of The Center of The
Flow Stream Flow Stream
And It “MUST” And It “MUST”
Be Kept Be Kept
Perpendicular Perpendicular
To the Flow To the Flow
StreamStream

STATE of OHIO FIRE SCHOOL - BGSU 184
Hold The HOSE TEST VALVES After the Hold The HOSE TEST VALVES After the
Pitot Readings have been obtained.Pitot Readings have been obtained.
Will These Hose Valves Vibrate or Chatter Open ?Will These Hose Valves Vibrate or Chatter Open ?

NFPA 70E and NFPA 70E and
OSHA OSHA 1910.3331910.333
OnlyOnly “QUALIFIED” “QUALIFIED”
persons are persons are
permitted to work on permitted to work on
or near “LIVE” or near “LIVE”
exposed parts of exposed parts of
electrical equipment.electrical equipment.
3.3.Distinguish live parts. Distinguish live parts.
(WHAT’S HOT, WHAT’S NOT ?)(WHAT’S HOT, WHAT’S NOT ?)
4.4.Determine nominal voltage and Determine nominal voltage and
protection required.protection required.
5.5.Determine the minimum Determine the minimum
required safe clearance or safe required safe clearance or safe
working distances. working distances.
(4 feet / 12 inches ) * (4 feet / 12 inches ) *
ARC-FLASH ARC-FLASH
12 Inches 12 Inches
MINIMUMMINIMUM
NEC Digest - Feb. 2006NEC Digest - Feb. 2006

OSHA may cite non-compliance with OSHA may cite non-compliance with
29CFR 1910.335(a)(1)(i)29CFR 1910.335(a)(1)(i) which requires which requires
the use of protective equipment when working the use of protective equipment when working
where a potential electrical hazard does where a potential electrical hazard does
exist.**exist.**
-OR- -OR-
29CFR 1910.132(d)(1),29CFR 1910.132(d)(1), which requires which requires
employer assessment of workplace hazards employer assessment of workplace hazards
and the use of personal protective equipment. and the use of personal protective equipment.
These regulations are supported by NFPA 70E. These regulations are supported by NFPA 70E.
NFPA 70E, is NFPA 70E, is NOT LAWNOT LAW, however, it helps , however, it helps
employers by providing education, guidance, employers by providing education, guidance,
and and “how-to” “how-to” for compliance. for compliance.

CONFIRM THAT PUMP BASE IS PROPERLY GROUTEDCONFIRM THAT PUMP BASE IS PROPERLY GROUTED
CONFIRM THAT ALL EQUIPMENT IS ALIGNED AND LUBRICATEDCONFIRM THAT ALL EQUIPMENT IS ALIGNED AND LUBRICATED
CONFIRM THAT COUPLING GUARDS ARE INSTALLEDCONFIRM THAT COUPLING GUARDS ARE INSTALLED
CONFIRM CASE RELIEF, AIR RELEASE, COOLING WATER ALL CORRECTCONFIRM CASE RELIEF, AIR RELEASE, COOLING WATER ALL CORRECT
CONFIRM THAT POWER IS CORRECT and “ON” CONFIRM THAT POWER IS CORRECT and “ON”
CONFIRM THAT WATER IS AVAILABLE and “ON” (PUMP PRIMED)CONFIRM THAT WATER IS AVAILABLE and “ON” (PUMP PRIMED)
CONFIRM THAT PUMP HAS PROPER ROTATION CONFIRM THAT PUMP HAS PROPER ROTATION
CONFIRM THAT VALVES ARE IN CORRECT POSITION FOR TESTINGCONFIRM THAT VALVES ARE IN CORRECT POSITION FOR TESTING
CONFIRM SAFE TEST SET UP (HOSES, PLAYPIPES, WATER DISPOSAL)CONFIRM SAFE TEST SET UP (HOSES, PLAYPIPES, WATER DISPOSAL)
CONFIRM THAT SYSTEM PRESSURE IS AT OR ABOVE EXPECTED FIRE CONFIRM THAT SYSTEM PRESSURE IS AT OR ABOVE EXPECTED FIRE
PUMP CHURN PRESSURE (USE THE JOCKEY PUMP) -OR- PUMP CHURN PRESSURE (USE THE JOCKEY PUMP) -OR-
IT IS PREFERABLE TO ISOLATE THE SYSTEM IT IS PREFERABLE TO ISOLATE THE SYSTEM
“ “CLOSE THE DISCHARGE CLOSE THE DISCHARGE
(SYSTEM) VALVE”(SYSTEM) VALVE”
KEEP IT CLOSED DURING FLOW TESTING KEEP IT CLOSED DURING FLOW TESTING
! **! **
FIRE PUMP “PRE-RUN” CHECK LISTFIRE PUMP “PRE-RUN” CHECK LIST
LAST CHANCELAST CHANCE - PRIOR TO TEST - PRIOR TO TEST

Base is not Base is not
grouted!!!grouted!!!
(6.4.1)(6.4.1)

Motor Oil Full ? Motor Oil Full ?
Check It !Check It !
LAST CHANCE !!!LAST CHANCE !!!
Gear Oil Full ?Gear Oil Full ?
Double Check Double Check
It !It !
What Oil Did They What Oil Did They
Use ?? Use ?? ASK !!ASK !!

Is The Engine Oil and Is The Engine Oil and
Coolant Correct ?Coolant Correct ?
Checked By Engine GuyChecked By Engine Guy ?? ??
Block Block
Heater Heater
Working ??Working ??
120 Degrees F 120 Degrees F
(11.6.5.2)(11.6.5.2)

NOTE : Guard Is In Place !NOTE : Guard Is In Place !
NFPA 20 (5.12.7) **NFPA 20 (5.12.7) **
NOTE : Cooling NOTE : Cooling
Water For Gear Water For Gear
Connected ! Connected !
Flow Visible ?? Flow Visible ??
(7.5.1.6.5)(7.5.1.6.5)

ENGINE ENGINE
COOLING WATER ON COOLING WATER ON

IS THE POWER ONIS THE POWER ON ?? ??
Has the Voltage Been CONFIRMED and Has the Voltage Been CONFIRMED and
controller digital readout controller digital readout (amps/volts) (amps/volts)
compared to readings taken with a compared to readings taken with a
“CALIBRATED” hand held amp / volt “CALIBRATED” hand held amp / volt
multimeter ??multimeter ??

Supply “OSY” Valve OPEN, Water Supply “OSY” Valve OPEN, Water
Available, and pump primed ??Available, and pump primed ??
NOTE ROTATION ?NOTE ROTATION ?
Clockwise / Right HandClockwise / Right Hand
Impeller Turns Toward Impeller Turns Toward
The Suction ! **The Suction ! ** SUCTION
This Pump This Pump
Base Has Base Has
Been Properly Been Properly
Grouted ! Grouted !
(6.4.1)(6.4.1)

FIRE PUMP FIRE PUMP
TEST HEAD TEST HEAD
OUTSIDE ! ! OUTSIDE ! !
Hose valves Hose valves
closed and closed and
hoses hoses
connected ?connected ?

Playpipes secured so water can be SAFELY Playpipes secured so water can be SAFELY
disposed of during flow testing ??disposed of during flow testing ??

OPEN Test OPEN Test
Header ValveHeader Valve
System Pressure at or System Pressure at or
above “EXPECTED” above “EXPECTED”
Fire Pump Churn Fire Pump Churn
Pressure -or-Pressure -or-
Discharge (System) Discharge (System)
Valve Valve CLOSED During CLOSED During
the Flow Testthe Flow Test ??** ??**
1/2” Test 1/2” Test
Head Drain Head Drain
Valve Valve
Closed ?? Closed ??
(Bottom of (Bottom of
Test Head Test Head
Pipe ! )Pipe ! )
Outside Hose Outside Hose
Valves Closed ??Valves Closed ??

TEST HEAD TEST HEAD
CONTROL CONTROL
VALVE OPEN VALVE OPEN
FOR TEST ???FOR TEST ???
½” TEST HEAD ½” TEST HEAD
DRAIN VALVE DRAIN VALVE
CLOSED FOR CLOSED FOR
TEST !TEST !

9. 9. Operate the pump at Operate the pump at CHURNCHURN PSI PSI
(POINT A on CURVE)(POINT A on CURVE)
Momentarily Operate the PumpMomentarily Operate the Pump - Check for - Check for
rotation, vibration, pressures, leaks, unusual sounds.rotation, vibration, pressures, leaks, unusual sounds.
Start The Pump Again:Start The Pump Again:
Check the pump for vibration, temperature, Check the pump for vibration, temperature,
case relief valve operation (Electric) or cooling water case relief valve operation (Electric) or cooling water
flow (Diesel), bearing temp, packing leakage, pump flow (Diesel), bearing temp, packing leakage, pump
pressures, RPM, Electrical (Controller Guy), etc.pressures, RPM, Electrical (Controller Guy), etc.
““DO NOT”DO NOT” stand in front of electrical panels or motor
junction boxes and keep the controller doors closed
during the initial starts (THINK SAFETY - 4 Foot Rule).
Note theNote the test start timetest start time… Pump must be operated for
AT LEAST ONE HOUR AT LEAST ONE HOUR for “ENTIRE” acceptance test !
NFPA 20 11-2.11 ( 14.2.12 )

PACKING LEAKAGE: 1 – 2 PACKING LEAKAGE: 1 – 2
Drops per second +/- Drops per second +/-
Adjust as Needed ¼ Turn !Adjust as Needed ¼ Turn !
Packing and bearings Packing and bearings
SHOULD stay cool or SHOULD stay cool or
warm to the touch!!warm to the touch!!
(14.2.5)(14.2.5)

Case Relief Valve Case Relief Valve
“FULL” Stream “FULL” Stream
Discharge To an Discharge To an
Open Floor Drain ? Open Floor Drain ?
Packing Drain Packing Drain
Lines Piped to a Lines Piped to a
Floor Drain !!Floor Drain !!
Does the pump and Does the pump and
motor stay COOL ? motor stay COOL ?
(14.2.5)(14.2.5)

10. Record 10. Record ChurnChurn PSI Readings, PSI Readings,
RPM, AMPS, VOLTS,RPM, AMPS, VOLTS,
Look at the factory shop test curve and plot the
Churn Pressure in feet of headfeet of head, (no-flow POINT AA).
How close is it ???? NFPA 20 11-2.3 ( 14.2.4.2 )NFPA 20 11-2.3 ( 14.2.4.2 )
NOTE: Some pumps will require a correction for
(RPM) speed !!! NFPA 20 A-11-2.6.3 ( A.14.2.7.3.f ) NFPA 20 A-11-2.6.3 ( A.14.2.7.3.f )
REMEMBER THISREMEMBER THIS - TO GET FEET OF HEAD !! - TO GET FEET OF HEAD !!
1 PSI = 2.31 FEET OF HEAD -or- 1 PSI = 2.31 FEET OF HEAD -or-
.433 PSI = 1 FOOT OF HEAD.433 PSI = 1 FOOT OF HEAD

AA
.
““CHURN” CHURN”
Pressure Pressure

11. Operate the pump at additional “TARGETED” 11. Operate the pump at additional “TARGETED”
flow points : 50%, 100%, flow points : 50%, 100%,
150%, Etc. 150%, Etc.
With the hose valves closed, SLOWLY open test head valve
to pressurize test head (If it is not already open and
pressurized). (DISCHARGE (SYSTEM) VALVE and TEST (DISCHARGE (SYSTEM) VALVE and TEST
HEAD DRAIN VALVE SHOULD ALREADY BE CLOSED)HEAD DRAIN VALVE SHOULD ALREADY BE CLOSED)
OpenOpen and adjustadjust appropriate number of hose valves to
obtain each targeted flow point (PITOT). You should
already know how many hose streams and what Pitot
Readings will be required to obtain “EACH” Targeted
Flow point!!
Double check pitot readings, do not allow hose valves to
vibrate open after obtaining the targeted pitot readings, and
make sure that there are “NO” kinks in the hoses !!!
NOTE: On High Pressure Systems (above 150 PSI) it may be NOTE: On High Pressure Systems (above 150 PSI) it may be
desirable to desirable to OpenOpen the proper number of hose valves and regulate the the proper number of hose valves and regulate the
pitot pressures with the pitot pressures with the Test Header Control ValveTest Header Control Valve. .
AVERAGEAVERAGE the pitot readings (NO MATTER HOW CAREFUL YOU the pitot readings (NO MATTER HOW CAREFUL YOU
ARE, ALL OF THE PITOT READINGS WILL NOT BE THE SAME) !!ARE, ALL OF THE PITOT READINGS WILL NOT BE THE SAME) !!

12. Record PSI, RPM, AMPS, 12. Record PSI, RPM, AMPS,
VOLTS, (compare and plot VOLTS, (compare and plot
results on the factory curve).results on the factory curve).
Do the field test results duplicate the factory shop test curve
for EACHEACH flow point ??? NFPA 20NFPA 20 11-2.3 ( 14.2.4.2)11-2.3 ( 14.2.4.2)
If any results are “OFF” Double Check PITOT Readings?
Correct for RPM ? ( On Small Pumps check the Case Relief ( On Small Pumps check the Case Relief
Valve flow. The case relief discharge flow could be as much Valve flow. The case relief discharge flow could be as much
as 5% to 10% of the rated flow of smaller pumps !! ) as 5% to 10% of the rated flow of smaller pumps !! )
If Total Head (Total Head (Net PSINet PSI) is STILLSTILL low, do we need to correct
for velocity head? Triple Check PITOT Readings, hose
valves vibrating open, gauge piping plugged, RPM low???
AS A LAST RESORT : before you pull the cover to check AS A LAST RESORT : before you pull the cover to check
for rocks - retest using a backup set of calibrated “TEST for rocks - retest using a backup set of calibrated “TEST
GAUGES” and backup pitot tube with gauge!GAUGES” and backup pitot tube with gauge!

STATE of OHIO FIRE SCHOOL - BGSU 208
BB
CC
.
.
.
“RATED 100% FLOW
“1 Hose, Pitot of 32 PSI
“ 150 % FLOW “
2 Hoses, Pitots
of 18 PSI

LOW TEST RESULTS ? WHY ?LOW TEST RESULTS ? WHY ?
Are there any kinks Are there any kinks
in the hoses??in the hoses??
Hose Valves Hose Valves
Vibrating Open ?Vibrating Open ?


Is this guy doing his job ?Is this guy doing his job ?

STATE of OHIO FIRE SCHOOL - BGSU 210
Did Did SomeoneSomeone Stay Outside to Adjust and Stay Outside to Adjust and HoldHold
The HOSE VALVES (especially ANGLE Valves) to The HOSE VALVES (especially ANGLE Valves) to
Keep Them From Vibrating Open Keep Them From Vibrating Open ? ?

STATE of OHIO FIRE SCHOOL - BGSU 211
DOUBLE or TRIPLE Check DOUBLE or TRIPLE Check
Pitot Readings !! Pitot Readings !!
CONFIRMCONFIRM Pitot Gauge Pitot Gauge
accuracy prior to testing !accuracy prior to testing !

??
Check pitot tube and Check pitot tube and
gauge for fouling , which gauge for fouling , which
might occur during test?might occur during test?

Each additional pitot Each additional pitot
tube, used during the tube, used during the
test, will increase the test, will increase the
chance for error! chance for error!
Use 1 pitot tube and 1 Use 1 pitot tube and 1
gauge which has been gauge which has been
checked prior to the checked prior to the
start of the test!start of the test!
Half of all field Half of all field
test problems test problems
involve the involve the
“USE” of, or the “USE” of, or the
“MIS-USE” of, “MIS-USE” of,
Hose MonstersHose Monsters

STATE of OHIO FIRE SCHOOL - BGSU 214
Calibrated Test Gauges ( Calibrated Test Gauges (
liquid filled gauges are liquid filled gauges are NOTNOT Test gauges )* Test gauges )*

STATE of OHIO FIRE SCHOOL - BGSU 215
Gauge connection Gauge connection
piping must have a full piping must have a full
flow when flushed flow when flushed
(checked) PRIOR to (checked) PRIOR to
flow testing of the flow testing of the
fire pump.fire pump.
Check for an Check for an
obstruction during obstruction during
testing, if test results testing, if test results
are not correct !are not correct !

STATE of OHIO FIRE SCHOOL - BGSU 216
DO NOT DO NOT
connect test connect test
gauges to gauges to
case relief case relief
valve piping !valve piping !

STATE of OHIO FIRE SCHOOL - BGSU 217
On small fire pumps the On small fire pumps the
case relief valve case relief valve
discharge may be as discharge may be as
much as 10% of the much as 10% of the
rated flow - if it has not rated flow - if it has not
shut off during the test.shut off during the test.

STATE of OHIO FIRE SCHOOL - BGSU 218
Main system relief Main system relief
valve must be closed valve must be closed
for testing !**for testing !**
Failure to do so will Failure to do so will
result in low (POOR) result in low (POOR)
test results !test results !

STATE of OHIO FIRE SCHOOL - BGSU 219
!!
(5.14)(5.14)
Elbows and tees with a centerline Elbows and tees with a centerline
plane parallel to a horizontal split-case plane parallel to a horizontal split-case
pump shaft shall be avoided. See pump shaft shall be avoided. See
Figure A-2-9.6. (5.14.6.3.1)Figure A-2-9.6. (5.14.6.3.1)
If there is a parallel elbow : YOU If there is a parallel elbow : YOU
MUST HAVE 10 PIPE DIAMETERS MUST HAVE 10 PIPE DIAMETERS
of STRAIGHT PIPE BETWEEN THE of STRAIGHT PIPE BETWEEN THE
ELBOW AND PUMP SUCTION ELBOW AND PUMP SUCTION
FLANGE (5.14.6.3.2)**FLANGE (5.14.6.3.2)**
PIPE SIZE ? PIPE SIZE ?
NFPA 20 NFPA 20
(5.14.3.4)(5.14.3.4)

Curve will continue Curve will continue
to drop off as the to drop off as the
flow increasesflow increases

Impeller is not Impeller is not
centered in the case.centered in the case.

Pump Not Pump Not
De-burredDe-burred

STATE of OHIO FIRE SCHOOL - BGSU 225
Top Shaft Nut is Top Shaft Nut is
used to raise shaft used to raise shaft
and impellers and impellers
approximately approximately
1/81/8 “ inch. (see “ inch. (see
instruction book) instruction book)
VTFP Best Lateral Setting
LOW LOW
PERFORMANCE PERFORMANCE
MAY RESULT IF MAY RESULT IF
LATERAL IS NOT LATERAL IS NOT
CORRECT !CORRECT !

STATE of OHIO FIRE SCHOOL - BGSU 226
Check Submergence Check Submergence
(MEASURE) how far (MEASURE) how far
down down (feet)(feet) the the
water level is from water level is from
the gauge center the gauge center
line, line, at each flow at each flow
point !point !
REMEMBER : This REMEMBER : This
must be must be addedadded to to
the reading ( TH ) the reading ( TH )
on the discharge on the discharge
TEST GAUGE !TEST GAUGE !
WL ??WL ??
ADD +ADD +

VTFP INTAKE PROBLEMS………..VTFP INTAKE PROBLEMS………..
Removable screens NFPA 20 A4-2.2.2 (5.14.8.3)(5.14.8.3)
Intake size ???Intake size ??? NFPA 20 A4-2.2 NFPA 20 A4-2.2 (5.14.8.4)(5.14.8.4)

2 ft/sec and 2 ft/sec and
1 Sq. Inch per 1 Sq. Inch per
GPM at GPM at
150% Flow ?150% Flow ?

STATE of OHIO FIRE SCHOOL - BGSU 229
Removable screens? Check Removable screens? Check
for fouling (build-up) ! for fouling (build-up) !

STATE of OHIO FIRE SCHOOL - BGSU 230
With a vertical With a vertical
turbine fire pump turbine fire pump
a plugged screen a plugged screen
will affect will affect
(lower)(lower) the water the water
level in the sump!level in the sump!
Check Check (measure)(measure)
the water level in the water level in
the sump during the sump during
each and every each and every
flow point !flow point !

A plugged basket strainer on A plugged basket strainer on
the bottom of the pump will the bottom of the pump will
reduce the total pump reduce the total pump
performance.performance.

STATE of OHIO FIRE SCHOOL - BGSU 232
Underwater Inspection of Basket StrainerUnderwater Inspection of Basket Strainer

13. * “6” AUTO starts
and “6” MANUAL starts *
(one “FULL LOAD” start)
When an electric fire pump is provided with an automatic
transfer switch, at least half of the starts should be performed
while the fire pump is connected to the emergency power
source (with one start under peak load). **
NFPA 20 (14.2.8) (14.2.7.4) ** NFPA 20 (14.2.8) (14.2.7.4) **
NOTE: Pumps should be operated for 5 Min. for each NOTE: Pumps should be operated for 5 Min. for each
start (This will allow the Motor and Controller time to start (This will allow the Motor and Controller time to
Cool Down)Cool Down)
When a diesel driven fire pump is provided, the starts shall be When a diesel driven fire pump is provided, the starts shall be
divided between both sets of batteries.divided between both sets of batteries.
NFPA 20 (14.2.8.7) NFPA 20 (14.2.8.7)

1.1.Controller and Driver alarms Controller and Driver alarms
connected, tested, and connected, tested, and
demonstrated + low suction…demonstrated + low suction…
A. Electric requires Power Available, Phase Reversal, Pump
Running, and Controller Connected to Alt. Source …..…
NFPA 20 (10.4.7.2)
(These are “TROUBLETROUBLE” or “SUPERVISORYSUPERVISORY”” alarmsalarms)
B. Diesel engine is much more involved…..* Engine Trouble -
High temp, low oil pressure, over crank - fail to start,
charger fail, battery fail, over speed, low fuel, Switch Not
in Auto, and Engine Run…….NFPA 20 (12.6.7.3)…….NFPA 20 (12.6.7.3)
(These are “TROUBLETROUBLE” or “SUPERVISORYSUPERVISORY”” alarmsalarms)
Pressure Recorder Installed / Operational ???Pressure Recorder Installed / Operational ???
EACHEACH Fire Pump Controller is required to be furnished
with a pressure recorder. (ELECTRONIC or CHART TYPE)(ELECTRONIC or CHART TYPE)
NFPA 20 NFPA 20 (10.5.2.1.6 and 12.6.9.1)(10.5.2.1.6 and 12.6.9.1)

1515. . Start and Stop Settings for Start and Stop Settings for
Main Fire Pump and Jockey Pump. Main Fire Pump and Jockey Pump.
Use a “TEST GAUGE” to Use a “TEST GAUGE” to
confirm set points.confirm set points. NFPA NFPA
20 A-11-2.6 (A.14.2.7)20 A-11-2.6 (A.14.2.7)
Jockey “STOP”Jockey “STOP” = Fire Pump churn pressure plus (+)
lowest static suction pressure !
Jockey “START”Jockey “START” = Jockey Stop PSI less (-) 10 PSI
Fire Pump “START”Fire Pump “START” = Jockey Start less (-) 5 –10 PSI

““MANUAL” Fire Pump “STOP”MANUAL” Fire Pump “STOP” = ( Must be used when Fire
Pump is a sole supply pump) !
- or - (if permitted by L.A.H.J.)
““AUTOMATIC” Fire Pump “STOP”AUTOMATIC” Fire Pump “STOP” = (Fire Pump churn +
lowest static suction)

STATE of OHIO FIRE SCHOOL - BGSU 239
J
o
c
k
e
y
J
o
c
k
e
y

P
u
m
p
P
u
m
p

STATE of OHIO FIRE SCHOOL - BGSU 240
Jockey Pump Control
Jockey Pump Control
Set Jockey Pump to STOP At /OR Near The Maximum
(CHURN) Discharge Pressure of the Main Fire Pump !!
Set Jockey Pump To START at 10 - 20 PSI Less

16. Low Suction Shut Down 16. Low Suction Shut Down
Panel/Device Listed, Tested Panel/Device Listed, Tested
AND “Alarm” Connected ?AND “Alarm” Connected ?
Required by some states to protect the public water supply, when it is
used as the main water source.
Set to lock out the fire pump at 20 PSI,20 PSI, after a 30 second 30 second delay - delay - with with
manual re-set only (OHIO) and ALARM must be monitored (5.23)manual re-set only (OHIO) and ALARM must be monitored (5.23).
Must be FM or UL listed for Fire Protection Equipment – Must be FM or UL listed for Fire Protection Equipment –
not UL Industrial !!not UL Industrial !! NFPA 13 15.1.8.3
Is the “EQUIPMENT” or “DEVICE” listed in the UL or FM Is the “EQUIPMENT” or “DEVICE” listed in the UL or FM
Directory for Fire Protection Equipment Directory for Fire Protection Equipment ?

CHECK THE BOOK !CHECK THE BOOK !

-
See if you
can find this
low suction
control
listed in the
UL or FM
Directory
for Fire
Protection
Equipment
??????

See if you can See if you can
find this low find this low
suction suction
“DEVICE”“DEVICE” listed listed
in the UL or FM in the UL or FM
Directory for Directory for Fire Fire
Protection Protection
EquipmentEquipment ?? ??

Ohio EPA and Ohio Department of HealthOhio EPA and Ohio Department of Health
CHECK WITH “ YOUR” LAHJ ?CHECK WITH “ YOUR” LAHJ ?

Suction Control ValveSuction Control Valve
Should be located Should be located
between the pump between the pump
discharge and the discharge and the
discharge check valve !discharge check valve !
Sensing line for suction control valve Sensing line for suction control valve
and/or low suction shut down panel and/or low suction shut down panel
should be at least should be at least ½” ½” (Copper, 300 (Copper, 300
Stainless, or Brass) and include provision Stainless, or Brass) and include provision
for testing ! for testing !

UL/FM Suction UL/FM Suction
Control ValveControl Valve
½” ½”
Suction Suction
Pressure Pressure
sensing sensing
line !line !
In the State of Ohio
a UL or FM Listed
low suction shut
down control is
required to protect
a public water
supply – this is in
addition to any
suction control
valve (which may
“ALSO” “ALSO” be required
by others) .

15.1.8* Connection from Waterworks System.
15.1.8.1 Where connections are made from public waterworks systems, it
might be necessary to guard against possible contamination of the public
supply.
15.1.8.2 The requirements of the public health authority having jurisdiction
shall be determined and followed.
FIND OUT WHAT “ YOUR ” STATE or CITY REQUIRES !!FIND OUT WHAT “ YOUR ” STATE or CITY REQUIRES !!
NFPA 13 15.1.8.3 NFPA 13 15.1.8.3 Where equipment is installed to guard
against possible contamination of the public water system, such
“EQUIPMENT”EQUIPMENT” and “DEVICES”“DEVICES” SHALL SHALL be listed for be listed for
““FIRE PROTECTION SERVICE”FIRE PROTECTION SERVICE”.
NFPA 13 - Chapter 15NFPA 13 - Chapter 15

17. Operators trained in required 17. Operators trained in required
maintenance, weekly operation, maintenance, weekly operation,
testing, and record keeping ???testing, and record keeping ???
Did the pump rep provide a weekly check
list and go over the required weekly
testing, maintenance, and inspections of
the pump, driver, and controller ???
NFPA 20 (14.3 ) NFPA 25 4.1 - 4.3NFPA 20 (14.3 ) NFPA 25 4.1 - 4.3
If not, he is not doing his job!!!
Weekly Check list should include those
items required by NFPA 25 Chapter 8NFPA 25 Chapter 8.

Develop a check list Develop a check list
of your own for of your own for
both “electric” and both “electric” and
“diesel” Fire “diesel” Fire
Pumps. Pumps.
-OR- -OR-
Make a copy of Make a copy of
NFPA 25, Chapter 8 NFPA 25, Chapter 8
for the owner or his for the owner or his
representative to representative to
use as a guide for use as a guide for
weekly checks. weekly checks.
““TRAIN THEM !!TRAIN THEM !!

NOTE: Clean Grease NOTE: Clean Grease
Forced out of the Forced out of the
Drain hole with Drain hole with
PLUG REMOVED !!PLUG REMOVED !!
Check For Check For
Excess Excess
GreaseGrease
Review ALL Required Review ALL Required WeeklyWeekly//AnnualAnnual Maintenance Maintenance

STATE of OHIO FIRE SCHOOL - BGSU 254
AFTER AFTER alignment has alignment has
been re-checked been re-checked
(ANNUALLY) the (ANNUALLY) the
coupling should be coupling should be
lubricated and re-lubricated and re-
assembled. Be sure assembled. Be sure
to check the set to check the set
screws for tightnessscrews for tightness
Annual Annual
Alignment Alignment
CheckCheck

HAVE HAVE
THESE THESE
FOLKS FOLKS
BEEN BEEN
PROPERLY PROPERLY
TRAINED? TRAINED?

STATE of OHIO FIRE SCHOOL - BGSU 256
??????
This is the ONLY “WM” case relief valve – This is the ONLY “WM” case relief valve –
on record, that had a tight shut off with on record, that had a tight shut off with
“NO” nuisance leakage - until they had to “NO” nuisance leakage - until they had to
buy a new pump !!buy a new pump !!

STATE of OHIO FIRE SCHOOL - BGSU 257
#1#1
CCOOLING OOLING
WATERWATER
#2 #2
FFUELUEL
# 3# 3

CCRANKRANK
NOTE !NOTE !
SET at 120 % of
Rated RPM **
EMERGENCY EMERGENCY
MANUAL MANUAL
STARTING STARTING
PROCEDUREPROCEDURE
(11.6.6)(11.6.6)
BE SURE THAT YOU
KNOW WHERE THE
OVERSPEED RESET
IS ON EVERY TYPE
OF ENGINE THAT
YOU SELL !!
INSTRUCT (TRAIN)
THE OWNER’S
REPRESENTATIVE
OR OPERATOR.
CUMMINS

18. Review test results … 18. Review test results …
ASK QUESTIONS ! Do it ASK QUESTIONS ! Do it
again if the results do not again if the results do not
look correct ???look correct ???
Did the pump rep try to rush the testing????Did the pump rep try to rush the testing????
Did the pump rep get nervous or defensive Did the pump rep get nervous or defensive
when you questioned any of the results or test when you questioned any of the results or test
procedures???procedures???
Were the PUMP test results at or above the Were the PUMP test results at or above the
factory shop test curve and within ½ % ( factory shop test curve and within ½ % (
the minimum accuracy of a CALIBRATED the minimum accuracy of a CALIBRATED
TEST GAUGE ) ??? NFPA 20 (14.2.4.2)TEST GAUGE ) ??? NFPA 20 (14.2.4.2)
Did the pump run for Did the pump run for one hourone hour (all testing)??? (all testing)???
NFPA 20 (14.2.12)NFPA 20 (14.2.12)

19. 19. STOP !STOP ! Don’t accept it if Don’t accept it if
the pump test results do not the pump test results do not
duplicate the shop test curve or duplicate the shop test curve or
the system is not CORRECT !the system is not CORRECT !
L.A.H.J. ( INSPECTOR )L.A.H.J. ( INSPECTOR ) : YOUR NAME YOUR NAME andand
REPUTATIONREPUTATION goes on the bottom line:
Approved and Accepted By:
NAMENAME : ………………………………………….………………………………………….

FIRE PUMP ““Annual”Annual” FLOW TEST
1. 1. Check Check for company and individual LICENSING. for company and individual LICENSING.
2. 2. CheckCheck for HYDRO and FLUSH CERTIFICATES (if work has been done). for HYDRO and FLUSH CERTIFICATES (if work has been done).
3. Look system over…housekeeping, sensing lines, leaks, piping , etc. 3. Look system over…housekeeping, sensing lines, leaks, piping , etc.
4. Record all pump, driver, and controller data. (HP, VOLTAGE, etc.)4. Record all pump, driver, and controller data. (HP, VOLTAGE, etc.)
5. Has the pump been properly Maintained and ALIGNED ANNUALY??? 5. Has the pump been properly Maintained and ALIGNED ANNUALY??? (CHECK)(CHECK)
6. Review Records of weekly testing and maintenance that was performed.6. Review Records of weekly testing and maintenance that was performed.
7. 7. CheckCheck for CERTIFICATE of CALIBRATION for for CERTIFICATE of CALIBRATION for ALLALL flow test equip. (SAFE??) flow test equip. (SAFE??)
8. Decide in advance just what is to take place during the flow test.8. Decide in advance just what is to take place during the flow test.
9. Operate the pump at Churn (no flow)….temp., brgs., packing, relief, etc.9. Operate the pump at Churn (no flow)….temp., brgs., packing, relief, etc.
10. Record Churn Test Results (compare with test results from previous year).10. Record Churn Test Results (compare with test results from previous year).
11. Operate the pump at additional flow points 100%, 150%,. 11. Operate the pump at additional flow points 100%, 150%,.
12. Record Test Results , compare with previous year ( within 5 % nameplate?).12. Record Test Results , compare with previous year ( within 5 % nameplate?).
13. 1 AUTO Start and 2 MANUAL Starts (One Full Load Start)13. 1 AUTO Start and 2 MANUAL Starts (One Full Load Start)
14. Controller and Driver alarms 14. Controller and Driver alarms TESTED TESTED (electric and diesel) (electric and diesel) (CHECK)(CHECK)
15. 15. ConfirmConfirm Start and Stop PSI for Main Fire Pump and Jockey Pump. Start and Stop PSI for Main Fire Pump and Jockey Pump.
16. Low Suction Control Operation, Set Point, Time Delay, 16. Low Suction Control Operation, Set Point, Time Delay, ANDAND Alarm Alarm TESTEDTESTED ? ?
17. Review 17. Review ALL ALL results - ASK QUESTIONS!! - ANY CONCERNS?? - Do it again ? results - ASK QUESTIONS!! - ANY CONCERNS?? - Do it again ?
18. STOP ! INVESTIGATE ! If the PUMP is more than 5 % below nameplate !18. STOP ! INVESTIGATE ! If the PUMP is more than 5 % below nameplate !
Tags