Seminar guide Seminar coordinator Ms. Aanchal Baranwal Mr. Alok pandey (Assistant professor) (Assistant professor) Department of Electrical Department of Electrical Engineering Engineering A Seminar on High voltage testing of Electrical Transformer PRESENTED BY Hari Shankar Singh:- 1308220902

CONTENTS Introduction of transformer and HV transformer Types of testing of transformer and explain with detail Advantages of HV testing of transformer Disadvantages of HV testing of transformer Conclusion References

What is Transformer ? Transformer is an electrostatic device which transfer electrical energy one circuit to another circuit by magnetic flux without change of frequency . Transformer has based on principle of electromagnetic induction(EMI). Formula used as measured a value, Vs / V p = Ns / N p = I p / Is

HIGH VOLTAGE TRANSFORMER High voltage transformers convert voltages from one level or phase configuration to another, usually from higher to lower. They can include features for electrical isolation, power distribution, and control and instrumentation applications. High voltage transformers usually depend on the principle of magnetic induction between coils to convert voltage and current levels .

TYPES OF HV TESTING OF ELECTRICAL TRANSFORMER Partial discharge test Impulse transformer test Transformer turns ratio test Insulation resistance test Routine test Temperature rise of oil testing of transformer

PARTIAL DISCHARGE TEST Partial discharge is a small localised dielectric breakdown of an electrical insulation system under high voltage stress. Each discrete partial discharge is the result of an electrical breakdown of an air pocket within the insulation. These discharges erode insulation and eventually result in insulation failure.

Acoustic techniques are used by manufacturers to locate discharges that occur during HV testing factory. PD occurs if the electric field strength applied to a dielectric exceeds the dielectric withstand strength of an insulation system locally. This may be caused by either increased field strengths , e.g. due to design problems, sharp edges on electrodes, small clearances , ageing , manufacture defect , insulation failure , damage etc.

PDT TEST CIRCUIT DIAGRAM Fig.1

CAUSES OF FAILURE IN PDT Fig.2

FAILURE LOCATION OF PDT Fig.3

FUTURE APPLIANCES FROM PDT Cables and Power transformers and bushings. Switchgear. Motors and generators Conclusion PDT testing prevents failure, Off-line testing is a critical pre-commissioning check. On- line testing is an extremely powerful non-instructive condition monitoring tool.

IMPULSE TRANSFORMER TEST This test is made to prove that the transformer insulation will withstand voltage surges which may be caused by lightning or switching. This includes insulation to ground, insulation between turns and windings, and the flashover value of the associated bushings. A high-voltage wave of standard values, and approximating a lightning surge, is imposed on the unit to be tested.

By a lightning pulse method used as measured for impulse transformer testing followed as full wave, half wave and front of wave show in Fig.4. Fig.4:- Graph between ultra frequency and time

CONNECTION DIAGRAM OF IMPULSE TRANSFORMER TEST Fig.5:-Connection of Impulse transformer test

TRANSFORMER TURN’S RATIO TEST The Transformer Turns Ratio test is used to make sure that the Turns Ratio between the winding of the transformer is correct. With this information, you can decide what the output voltage of the transformer will be. The ratio is calculated under no-load conditions using formula given below, V pri /V sec = Z pri / Z sec  = (N pri /N sec ) 2

INSULATION RESISTANCE TEST (IR VALUE TEST) Insulation ages and deteriorates because of moisture, dust and electrostatic stress. Insulation should be monitored continually to avoid sudden failure of the equipment. An insulation resistance test detects insulation quality within the transformer. The conductive impurities or mechanical flows in the dielectric can be analysis based on this test.

CONNECTION OF IR VALUE TESTING DIAGRAM Fig.6:- IR Value testing connection diagram

Normally, MEGGERS have a test voltage of 500V , 2500V , or 5000V . IR between HV and LV as well as windings to earth. Minimum IR value for Tap changer is 1000 ohm per volt service voltage

FACTORS AFFECTING ON IR VALUE OF TRANSFORMER The IR value of transformers are influenced by Surface condition of the terminal bushing. Quality of oil. Quality of winding insulation. Temperature of oil. Duration of application and value of test voltage.

IR VALUE TESTING FORMULAS 1 Phase Transformer IR Value (MΩ) = C X E / (√KVA) 3 Phase Transformer (Star) IR Value (MΩ) = C X E (P-n) / (√KVA) 3 Phase Transformer(Delta) IR Value (MΩ) = C X E (P-P) / (√KVA) Where C= 1.5 for Oil filled T/C with Oil Tank, 30 for Oil filled T/C without Oil Tank or Dry Type T/C.

ROUTINE TEST FOR TRANSFORMER A Routine test of transformer is mainly for confirming operational performance of individual unit in a production lot. Routine tests are carried out on every unit manufactured. All transformers are subjected to the following Routine tests: Insulation resistance Test. Winding resistance Test. Turns Ratio / Voltage ratio Test .

Polarity / Vector group Test Open circuit and short circuit Test. Continuity Test. High Voltage Test. Partial discharge Test. Separate source AC voltage. Induced overvoltage. Lightning impulse Tests. On -load tap changers Test.

TEMPERATURE OIL TESTING OF TRANSFORMER Temperature rise test of oil of Transformer is included in type test of transformer. In this test we check whether the temperature rising limit of transformer winding and oil as per specification or not. Faults detects at above 75˚C by the help of Buchholz relay and work as ALARM and TRIP circuit.

BUCHHOLZ RELAY, EXPAIL BY THE THIS VIDEO

ADVANTAGES OF HV TESTING TRANSFORMER Pure conductivity by IR Value test. Controlling of HV surges by Impulse test. Removing of discrete waveform by the help of Partial Discharge test. Terminals has used connected correctly by Transformer Turn’s Ratio test. Units measured a correctly and manufacturing defect check by Routine test.

DISADVANTAGES OF HV TESTING OF TRANSFORMER After failure, transformer is removed and replaced with new/repaired one without removing the cause of failure which results in immediate or short time failure. Insufficient Oil level. Faulty operation of tap changer switch. Lack of installation checks. Prolonged Over loading.

CONCLUSION Knowledge of the construction of high voltage test transformers, their design and use in high voltage testing system gives the solution of the most adjustment transformer in respect of parameters and prices. HV testing are main advantages of safety , higher efficiency , lower cost ,savings of energy , avoiding of failures ,trouble shooting for failure detection , accurate detection , quality assurance.

REFERENCES R.S. Jha , “High Voltage Engineering”, Dhanpat Rai & Sons, Second Edition in 1996. C. L. Wadhwa , “High Voltage Engineering”, Wiley Eastern Ltd. Third Edition in 2012. E.Kuffel and W.S. Zaengl , “High Voltage Engineering” , Pergamon Press, First Edition in1984.

?