BASIC CONCEPT OF
HOUSE WIRING
By HarminderPal Singh, MMS
PGSC conducts “Assistant Electrician”
Skill development Course
under
PradhanMantriKaushalVikasYojna.
Interested candidates may contact
HarminderPal Singh (81465 68350)
For Age Group > 15 years

Some basics :
What is Electricity ?
Electricity is a form of energy resulting from the existence of charged particles
(such as electrons or protons)
An electric currentis the rate of flow of electric charge past a point or region. In
electric circuits this charge is often carried by electrons moving through a wire.
Voltage, also called electromotive force, is the potential difference in charge
between two points in an electrical field
It results in Current
There are two types of currentused widely:
o Directcurrent(DC), in which electrons flow in one direction.DCpower is
widely used inlow voltage applications such as charging batteries,
automotive applications, aircraft applications and low current applications.
Solar panels produce DCpower
o Alternating current, ( AC) in which the electric charge changes direction
periodically.Householdoutlets are Alternating Current

Importance of Electricity
•Electricityhasmanyusesinourdaytodaylife.Itisusedfor
lightingrooms,workingfansanddomesticapplianceslikeusing
electricstoves,ACandmore.
•Infactories,largemachinesworksonelectricity.
•Onecannotimaginecomfortwithoutelectricity.Allhospitals,
agriculture,cinemahouses,educationalinstitutes,railways,
business,entertainmentsandmanymoredependsupon
electricity.
•Hence,electricityplaysawideroleintheprogressofanynation.

> Volts : Electromotive force or potential difference, expressed in volts(V)
> W: Wattis the unit of power. One wattis defined as the energy consumption
rate of one joule per second. 1W = 1J / 1s. One wattis also defined as the
current flow of one ampere with voltage of one volt.
It is named after James Watt, the inventor of the steam engine.
> kW: 1000 Watt
> kWh: The kilowatt-houris a unit of energy equal to 3600 kilojoules (3.6
megajoules). 1 kWhequals one hour of electricity usage at a rate of 1 kW, and
thus the 2 kWappliance would consume 2 kWhin one hour, or 1 kWhin half an
hour.
> The equation is simply kWx time = kWh
> The kilowatt-houris commonly used as a billing unit for energy delivered to consumers
by electric utilities.
Some common terms used

MCB: Miniature circuit breaker : Itautomatically switches off electrical circuit during an
abnormal condition or overload of the network. Nowadays we usean MCBin low voltage
electrical network instead of a fuse
SP-MCB:A Single Pole Breakeris used with a typical 120v circuit, having one hot wire and one
neutral wire.
DP-MCB: However, a Double Pole Breaker is used with a typical 220v circuit (like for a dryer or
heater) having two hot wires. If there is a short circuit to either hot wire, both poles are ganged
together so both trip together
Based on the number of poles, the breakers are classified as : SP –Single Pole, SPN–Single Pole
and Neutral, DP–Double pole, TP–Triple Pole, TPN–Triple Pole and Neutral, 4P–Four Pole.
ELCB: An Earth-Leakage Circuit Breaker (ELCB) is a safety device used in electrical installations
with high Earth impedance to prevent shock. It detects small stray voltages on the metal
enclosures of electrical equipment, and interrupts the circuit if a dangerous voltage is detected.
PSPCL: Punjab State Power Corporation Limited, the agency which supplies electric power in
Punjab
Some common terms used

House Wiring (Single Phase)
•Singlephasesupplyconsistsofonephasewirecalledhotwireandoneneutralwire
connectedinEnergymeterbyPSPCLasinputsupply220V.
•Theoutput220VsupplyistakenfromEnergymetertoMCBdistributionbox.
•ELCB,DPMCB/Isolatorareusedasmaincontrol.
•NumberofSP-MCBsareinstalledinMCBBoxtoprovidephasetoindividualswitch
boardofroomsetc.inahouse.
•NeutralwirefromMCBBoxneutrallinkisconnectedtoeachswitchboardsocketand
otherloads.
•Switchesareinstalledonswitchboardofeachroomtooperateitsrespectiveloadi.e.
fan,lightandTV,fridge,press,washingmachineetc.throughsockets.
•Anyload(singlephase)whenconnectedwith220Vsupplydulycontrolledbyswitchis
calledacircuit.

House Wiring (Single Phase) Wiring Diagram

Circuit
•Following load point are usually provided in each room:
oTube lights
oFan
oLamp Point/s
oSockets
oTV
oAC etc.
Each load / point (on/off) is controlled by its switch connected
through wire/s, MCB / fuse, etc. which makes a circuit.

•Opencircuit:Circuitisopenwhentheswitchisnot
closed,lampisOFFinthiscircuit.
•Closedcircuit:Circuitisclosedwhentheswitchis
closed,nowlampisON
•Shortcircuit:Whenany(+)wireor(-)wirebreaks
anditgetsconnectedwithoppositepolarity,the
circuitiscalledshortcircuit.Itisabnormalcondition
andnotdesiredtohappeninanyelectriccircuit.
Withoutproperselectionofsafety,itmaycause
damagetocostlyitems,wire,switches,etc.
Types of Circuit

General Items required as per load
•PVC wires: Generally 4.0 mm
2
, 2.5 mm
2
, 1.5 mm
2
, 1.0 mm
2
, 0.75
•MCB distribution Board: 6 Way, 8W, 10W, 12W, 16W
•MCB’s: 6 AMP,10A, 16A, 20A, 25A, 32A, (SP/SPN)
•RCCB or ELCB: 16A, 25A, 32A
•Switches: 6Amp, 16 Amp, 20 Amp
•Sockets: 5 Pin 6 Amp, 6 Pin-16Amp, 20A, 25A, 32A
•Bell Switch: 6Amp
•2-Way Switch: 6 Amp
•Various loads in rooms
•DP Isolator, etc.

Functions of different items used in house wiring
•Energymeter:ThemeterisinstalledbyPSPCLtochargeelectricity
beingconsumedbyconsumer.TheunitrateisfixedbyGovt.,units
areconsumedbyconsumeraspertheirload/requirementsand
hastopaytoGovt.
1 Unit = 1000 Watt x 1 hr. OR 1 kwh
E.g. if we operate the following per day
Ceiling fans –(5Nos. x 100W each) x 8 hrs. = 4000 Wh
Geyser-(1 No. x 1500 W) x 1 hr. = 1500 Wh
Tube Lights –(10 Nos. x 40 W each) x 8 hrs. = 3200 Wh
Total = 8700 Wh
OR 8.7 kwhOR 8.7 units
•Say Unit Rate is Rs.10/-
Per day Expense: (8.7 units x Rs.10/-) =
Monthly Expense: (Rs.80.70 x 30 days)=
Rs.87.00
Rs.2610/

•ResidualCurrentCircuitBreaker(RCCB)isadevicewhich
providesprotectioninanelectriccircuitincaseofoverload,
shortcircuitandearthfault.Usually,itistobeusedasamainin
theMCBdistributionboard.
•EarthLeakageCircuitBreaker(ELCB)isaprotectiondeviceand
usedforprotectionofelectriccircuitandhumansfromelectric
shock.e.g.whenanyitem/equipmentbodycomesincontact
withhotlineorduetoanyinsulationfailure.
•Thereisacoil,bimetalandhammerarrangementinsidethis
device,whichoperatesatitsdesignedvaluewithout
interruptingthecircuitundernormalcondition.
ResidualCurrentCircuitBreaker(RCCB)/EarthLeakage
CircuitBreaker(ELCB)

•Whensomefaultarises,thecircuitbecomesabnormalandmore
currentpassesthroughthecoils,bimetalstripsetc.Thenatureof
bimetalistoexpandwhenitgetshot.Sowhen,morecurrentfromthe
designedvalvepassesthroughit,itexpandsandoperateshammerdue
towhichthematchedcontactsgetstucktoeachother.Thus,thecircuit
isopenedwhichprovidesprotectiontocircuit/human,etc.
•Itisimportanttonotethat‘Earthing’mustdoneinhousewiringand
wiringshouldbeofgoodqualitytoprotecthumansfromelectricshock.
•Deathsduetoshockfromelectricalapplianceslike,cooler,press,
washingmachineandotherapparatusbeingusedinnormallifehas
beenobservedmanytimes.Topreventthiswiringshouldbeofgood
qualityandhighstandard.

Double Pole (DP) or Single Pole and Neutral Miniature
Circuit Board (SPN MCB)
•DPMCBcanbeusedfor2-PhasesupplyorOnepoleforphaseandother
polefornatural
•DP/SPNMCBcanbeusedforphaseandneutral.
•DP/SPNMCBcanbeusedasmainswitchinMCBDistributionBoard.
•ActuallyMCBisamoderndeviceandhasreplacedtheuseoffusein
electriccircuitduetomoresafety.MCBandfuseareprotectiondevices.
•Therewerelimitationsandlackofknowledgetoselectthepropersize
fusewiretomeettherequiredprotectionswhilereplacingburntfuse
wire.MCBshaveovercomethislimitationandthereisnoneedtoputany
fusewirebecauseMCBtrips(off)whenthereisanyshortcircuit/over
loadinginthecircuit.
•Itdoesnotrestart(getON)untilfaultisremoved,thusprotectingcircuit.
•OneshouldbecarefultoselectproperratingofdevicesusedintheCKTto
achieveprotectioninelectriccircuit.
•SinglePole(SP)MCBshavethesamerole,itisusedforsinglephasesupply.

•ItlookslikeaDP-MCBandiscommonlyusedasamainswitchin
ahouseMCBDBox.
•Asitsnameisisolator,itcanswitchON&OFFloadjustlike
ordinaryswitchesdo.
•Thereisnotrippingarrangementinthisdevice,sonoprotection
canbeachievedfromthis.
•BeingmuchcheaperfromDPMCB,itiscommonlyusedasa
mainswitchofhouse,asindependentMCB’s(SP)arealways
availableroomwise/loadwiseintheMCBBox.
•DPIsolatorisavailableintherating16A,20A,25A,32Aand63
Amp.
•AproperselectionofDPIsolatorisrequiredtomeettheload
requirement.
DP Isolator

•GenerallyPVCcopperflexiblewiresareusedinwiring.PVCisan
insulatingmaterialcoveringcopperthinwiresinsideit.
•Generally,220Visavailableforsinglephasesupplyandwire
insulationisratedforminimum660Vor1100V.
•GoodqualitywiresareofFR/FRLS,whicharefireretardantand
superqualitywiresareboth,fireretardantandlowsmoke.
•Now-a-days,flexiblePVCwirescopperareusedinthesizes0.75
mm
2
,1.0mm
2
,1.5mm
2
,2.5mm
2
,4.0mm
2
.
•Foreconomicalwiring,itisdesiredtocalculatetotalloadof
house,rooms,etc.toselectpropersizeofwiretobeused.
•Normally,0.75mm
2
wireisusedasEarthwire.1.0mm
2
canbe
withstand1KWload(6Amp.).1.5mm
2
canbeusedfor1.5KW
load(7-8Amp.)and2.5mm
2
for2.5KWload(16-17Amp.).
Poly Vinyl Chloride (PVC) Wires
Contd.

•Inpast,PVCcopperwirestrandedtypeconductorwasusedforwiringandtheirsizes
were3x22SWG,7x16SWG,3x20SWG,1x18SWG.
•3x22SWGmeans3wirecopper,eachof22GaugecoveredwithPVCinsulation.
•Beingnotflexible,itwasdifficulttodrawthemthroughconcealedconduitpipesand
also,itsreplacementwasverydifficult.So,flexiblePVCcopperwiresarenowwidely
used.
•Currentcarryingcapacityofflexiblewiresismore,hence,itdoesnotheatup.
•Itissuggestedtousealwaysbranded,ISImarkedwiresonlyandcheapwiresshould
notbeused.
Poly Vinyl Chloride (PVC) Wires

•Inthesepipes,PVCwireisdrawntovariouslocationsofhousethrough
roofceiling,walls,groundetc.
•Generally,25mmheavyduty(ISImarked)pipeshouldbelaidinLanter
duringconstruction.Ifignored,thepipemaycrackedandcivil(cement,
sand,concrete,etc.)materialbeingusedduringconstructionoflantermay
enterthepipeandblockitspathfordrawingwires.
•Forwalls,mediumweightpipecanbeusedtoreducetheexpense.
PVC Conduit Pipes
•Allconcealedlightboxes,fanboxesandotherboxesshouldbeproperlytiedafterlayingpipeswith
steelwireswithbars.Allunwantedholesshouldbecoveredwithpolytheneetc.
•Itisalwayssuggestedtouse60-65%diameterpipeforlaying/drawingwiresthroughitforlonglife
ofsystemwhilemakingprovisionforfutureuse,ifrequired.
•Theconcealedlayoutofpipesthroughlantershouldbeaccordingtothesizeofroomwhereone
shouldknowhowmanyfans,lights,etc.shallbeinusebyowner.
•Fanboxeswithheavyhooksshouldbeusedalways.
•Allswitchboxesshouldbeplaced/fixedatrelevantlocationsintheroomsatproperheight
generally,1.2Mfromfloorlevelandshouldbeconnectedwithpipe.
•Onwalls,chippingshouldbedonesothatthepipeisapprox.1”deepandcoveredwithplaster,
otherwise,crackswillappearonplastercoveringthepipe.

•6Aswitch,6Amp.5pinsocket,16A/20Aswitch,16/20Amp.6-pin
socket,ACplugpoint,Fanregulator,Dummy,plates,coverplate,
etc.,2wayswitch6Amp/16Ampareusedgenerally.
•6Aswitchisusedforalllightpoints,fanpoints,etc.
•6A5-pinsocketisusedforrefrigerator,Iron,washingmachine,tulu
pump,LEDTV,chimney,exhaustfan,chargingmobile,etc.
•16A/20Aswitchand16A/20A6-pinsocketisusedforgeyserpoint,
heavywashingmachine,ACloadetc..
•Fanregulatorisusedtocontrolthespeedoffan.
•Coverplateisusedtocoveralltheswitches,sockets,etc.with
matchingcolourofwalls.
•2wayswitchesareusedforstaircaselightcontrolandentrygate
lights.
Accessories

•AllaccessoriesshouldbeofISImarked,brandedbearinggoodlookandasperchoice
ofowner.
•Aftercompetingallwiringconnections,itshouldbecheckedagainforanyloose
connection.Operationofallpoints,MCBtrippingandELCBoperationshouldalsobe
checked.
•Undesirednails,screws,cutpieceofwiresshouldberemovedtoavoidanyinjury.
•Eachmetal&switchboxshouldbeearthedforhumansafety.
•Jointsshouldbealwaysavoided.
•MarkroomwiselocationontheMCB-DB-MCB’s.
Accessories

•Inserieswiring,switchisinserieswithphaseandloadisalways
connectedinparallelsothatphaseisgiventoanyloadthrough
switchandneutralisconnectedtoitsN-point.
•Whenswitchispressed,phasewillreachtoloadandthusitworks.
Thisisthewaytoconnectloadsinhouses/industries,etc.
•Ifloadsareconnectedinseriesinhouse,totalvoltageVwillbe
dividedinconnectedloadsaspertheirwattageandcurrentwill
flowaspermaximumwattageofloadfromtheconnectedloads
andsolesswattageloadsmayburnt.
•Voltageshouldberemainsamei.e.220voltforallloadstowork
properlyasallsinglephaselamps,tubes,fridge,iron,geyser,etc.
arealwaysratedat220volt.
•Inparallelwiring,wecanswitchON/OFFanyloadasperour
requirement.
Single line diagram for circuits (Single Phase)

•Earthingisveryimportantandcompulsoryworkrequiredtodoneduring
housewiring.Itisveryusefultoprotectthehumanfromelectricshock.
Procedure
•Diggingshouldbedoneuptothelevelofobservingwetclay.
•LayG.I.Pipeorcopperplate/copperstripdeepintothegroundupto
floorlevel.Fillborewithsalt,charcoal,kalmishoraetc.andpourwater.
Thiswillmaintainmoistureforlongduration.
•Afunnel/orpipemouthmaybeusedforfillingwaterperiodically.
•PitshouldbeconnectedwithMCBBoxusingcopperearthwire/G.I.wire.
•FromMCBBox,earthwireshouldbelaiduptoallswitchboxes,fanboxes,
metalboxes,allpowersockets,etc.
•Duringanycurrentleakage,phasecontactwithanymetalbox/apparatus
etc,ELCBinMCBBoxwillsenseandwilltripthemainsupply.ELCBcantrip
at30mAto100mAcurrent.
•Supplycannotbeswitchedonunlessfaultisremoved.
Earthing

•Hammer
•Hacksaw&Blade
•Chiesel
•GrooveCutter
•Plier
•ScrewDriver/s
•NosePlier
•Cutterwire
•Crampingtool
•Wiresheather
•Multimeter
•Voltmeter
•Amperemeter
•Megger
•Earthtester
Tools Used
•Bocky
•LampTester
•TestingPen
•Drill(HiltyType)M/cHandheld
•Slowspeedhanddrillmachine
•LevelCheck(waterlevel)
•30Mtaperoll
•5Mtaperoll
•Knife
•SteelWire
•ContinuityTester
•Safetybelts
•Helmet
•SafetyShoes
•InsulatingGloves
•Goggles
•Mask
•ToolBox
•AdjustableWrench

•Toolsshouldbekeptneatandclean.
•Toolsshouldbekeptinproperway/sections.PVCsleevesonthehandlesofpliershouldnot
beusediffoundcracked.
•Tipsendsofscrewdrivershouldbeproper.
•Neverusetestpenonhighvoltage,fortighteningofscrews,etc..
•Donotbelieveontestpenindicator,pleaseusetestlamptoascertainthesupply.
•Donotuseplierasahammer.
•Donotgive/bypasstoolsfromfronttosubordinates,itmayhurt.
•Usepropertoolsforproperwork.
•Donotgossips,becool,donothurryupwhiledoingelectricworks.
•Usesimplewords,signalswithoneanothertoseekhelp,instruction,guidance,etc.
•Donotbeoverconfident,checkyourworkandifanydoubt,pleaseclearandgethelpfrom
someone.
Contd.
Some Important Tips

•Donotusemobileearphones/mobilephonesfrequently.
•Donotusepoorconditionladder,toolsetc.
•Usesafetybeltsformoreheights.
•Usesafetyshoes.Donotuseoldshoes,thatmaybecomeslippery.
•Donotwearlooseclothes.
•Alwaysdiscusswithoneanother,makeplanandactaccordingtoplan.
•Donotthrowyourtools.
•Cleanworkplaceandyourhands,etc.
Some Important Tips

•Allelectrical/electronicappliancesneedstodisplayvoltageandcurrentratingcompulsorye.g
Voltage:220V,Power:9Watt/15W/40W/100W/250W/1500W/2500W,Frequency:50HZ,Rated
Current-In:asperload,Manufacturername/Trademark:ISImarkwithCM/LNo.,PowerFactor:
0.8or0.9,MadeinIndia.
•Theselectionofwires,switches,MCB’s,MainMCB,plugtopsetc.dependsuponthecurrenttobe
drawnbyload.E.g.
Power : 1500W(ACload)
Voltage: 220Volt
Current: Power = 1500= 8.5Ampere
VoltagexP.F. 220x0.8
•UseofitemsforACloadbaseduponitscurrentisasunder:
oSwitch : 16A-220V
oSocket : 16A–220V
oPlugTop : 16A–220V
oMCB/SPN : 16A–220V
oPVCwires : 2.5mm
2
Contd.
Calculation of Current and Selection of Items

•Loadusedinthehousesareasunder:
oLEDLamps : 0.2Wto40Wareavailableforhouses
oFans : 50Wto100W
oGeyser : 1500Wto3000W
oAC’s : 1500Wto2500W
oPress : 200Wto300
oFridge : 190Wto300W
Calculation of Current and Selection of Items

THANKS
PUSHPA GUJRAL SCIENCE CITY, KAPURTHALA