IRS Concrete Bridge Code..1997
V-34
equipped with an approved automatic
check valve, the upper end of the pipe
shall be plugged before delivering the
concrete to the tremie pipe through the
hopper, so that when the concrete is
forced down from the hopper to the
pipe, it will force the plug (and alongwith
it any water in the pipe) down the pipe
and out of the bottom end, thus
establishing a continuous stream of
concrete. It will be necessary to raise
the tremie pipe by 25cm to 30cm slowly
in order to cause a uniform flow of the
concrete, but the tremie shall not be
emptied to avoid flow of water into the
pipe. At all times even while
changing/adding pipes to tremie, the
bottom of tremie pipe shall be atleast
600mm below the top of concrete as
ascertained by sounding. This will cause
the concrete to build up from below
instead of flowing out over the surface,
and thus avoid formation of laitance
layers. If the charge in the tremie is lost
while depositing, the tremie shall be
raised above the concrete surface, and
unless sealed bye a check value, it shall
be replugged at the top end, as at the
beginning, before refilling for depositing
concrete.
8.6.2.4 To minimise the formation of
laitance, great care shall be exercised
not to disturb the concrete as far as
possible while it is being deposited.
8.6.3 Concrete in Sea Water
8.6.3.1 Special attention shall be given
to the design of the mix to obtain the
densest possible concrete; slag, broken
brick, soft limestone, soft sandstone, or
other porous or weak aggregates shall
not be used.
8.6.3.2 As far as possible, preference
shall be given to precast members
unreinforced, well cured and hardened,
without sharp corners, and having
trowel-smooth finished surfaces free
from crazing, cracks or other defects;
plastering should be avoided.
8.6.3.3 No construction joints shall be
allowed within 600mm below low water
level or within 600mm of the upper and
lower planes of wave action. Where
unusually severe conditions or abrasion
are anticipated such parts of the work
shall be protected by bituminous or
silico-fluoride coating or stone facing
bedded with bitumen.
8.6.3.4 In reinforced concrete
structures, care shall be taken to protect
the reinforcement from exposure to
saline atmosphere during storage and
fabrication.
8.6.4 Concrete in Aggressive Soils
and Water
8.6.4.1 General - The destructive action
of aggressive waters on concrete is
progressive. The rate of deterioration
which varies with the alkali resisting
property of the cement used, decreases
as the concrete is made stronger and
more impermeable and increases as the
salt content of the water increases.
Where structures are only partially
immersed or are in contact with
aggressive soils or waters on one side
only, evaporation may cause serious
concentrations of salts with subsequent
deterioration, even where the original
salt content of the soils or water is not
high. The selection of type of cement,
therefore, should be made after
thorough investigation. For particular
problems, engineer-incharge should
decide upon the method.
8.6.4.2 No concrete shall be allowed to
come in contact with sea water within 72
hours of casting.
8.7 Sampling, Strength Tests and
Acceptance Criteria
8.7.1 General – Samples from fresh
concrete shall be taken as per IS:1199
and cubes shall be made, cured and
tested at 28 days in accordance with IS:
516.