Date: 03.09.24
File: PRO1_14E.1
SIMATIC S7
Siemens AG 1999. All rights reserved.
Information and Training Center
Knowledge for Automation
Analog Value Processing
Level
transmitter
High level
Low level

Date: 03.09.24
File: PRO1_14E.2
SIMATIC S7
Siemens AG 1999. All rights reserved.
Information and Training Center
Knowledge for Automation
Use of Analog Modules
Process
Physical
quantity
Standard
analog signal
Sensor
Transducer
• Pressure
• Temperature
• Flow
• Speed
• pH value
• Viscosity
• etc.
± 500mV
± 1V
± 5V
± 10V
± 20mA
4...20mA
etc.
DAC
PQW ...
PQW ...
:::
PQW ...
Analog output module
MR
module
ADC
Result
memory
PIW ...
PIW ...
:::
PIW ...
Analog input module CPU
:
:
:
:
:
:
L PIW 352
T PQW 368
:
Analog
actuator
Physical
quantity
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

Date: 03.09.24
File: PRO1_14E.3
SIMATIC S7
Siemens AG 1999. All rights reserved.
Information and Training Center
Knowledge for Automation
Measuring Range Module

Date: 03.09.24
File: PRO1_14E.4
SIMATIC S7
Siemens AG 1999. All rights reserved.
Information and Training Center
Knowledge for Automation
Analog Module Addresses with S7-300
IM 256
to
270
336
to
350
352
to
366
368
to
382
304
to
318
320
to
334
272
to
286
288
to
302
(Send)
Slot 2 3 4 5 6 7 8 9 10 11
384
to
398
400
to
414
432
to
446
448
to
462
464
to
478
480
to
494
496
to
510
416
to
430
Rack 1
R
0
Power
Supply
IM
(Receive)
Power
SupplyCPU
512
to
526
528
to
542
544
to
558
560
to
574
576
to
590
592
to
606
608
to
622
624
to
638
Rack 2
IM
(Receive)
Power
Supply
Rack 3
640
to
654
656
to
670
672
to
686
688
to
702
704
to
718
720
to
734
736
to
750
752
to
766
IM
(Receive)
Power
Supply

Date: 03.09.24
File: PRO1_14E.5
SIMATIC S7
Siemens AG 1999. All rights reserved.
Information and Training Center
Knowledge for Automation
Analog Module SM335 (Inputs)

Date: 03.09.24
File: PRO1_14E.6
SIMATIC S7
Siemens AG 1999. All rights reserved.
Information and Training Center
Knowledge for Automation
Analog Module SM335 (Outputs)

Date: 03.09.24
File: PRO1_14E.7
SIMATIC S7
Siemens AG 1999. All rights reserved.
Information and Training Center
Knowledge for Automation
Analog Input Module SM331

Date: 03.09.24
File: PRO1_14E.8
SIMATIC S7
Siemens AG 1999. All rights reserved.
Information and Training Center
Knowledge for Automation
Analog Value Representation and Measured Value Resolution
2
0
2
1
2
2
2
3
2
4
2
5
2
6
2
7
2
8
2
9
2
10
2
11
2
12
2
13
2
14
VZHex.Bit valueDec.
0123456789101112131415Bit no. Units
Reso-
lution
in bits
+ sign
1 11 ******** *******15
*
= 0 or 1
80 00000001128 ********8
40
20
10
8
4
000000
00000
0000
000
00
02
164
132
116
18
14
12
******** *
******** **
******** ***
******** ****
******** *****
******** ******
9
10
11
12
13
14

Date: 03.09.24
File: PRO1_14E.9
SIMATIC S7
Siemens AG 1999. All rights reserved.
Information and Training Center
Knowledge for Automation
Analog Value Representation of Different Measuring Ranges
Range
Overflow
Overrange
Rated range
Underrange
Underflow
Meas.range
± 10V
Voltage
e.g.:
>= 11.759
11.7589
:
10.0004
10.00
7.50
:
-7.5
-10.00
- 10.0004
:
- 11.759
<= - 11.76
Units
32767
32511
:
27649
27648
20736
:
-20736
-27648
- 27649
:
- 32512
- 32768
Meas.range
4 .. 20mA
Current
e.g.:
>= 22.815
22.810
:
20.0005
20.000
16.000
:
:
4.000
3.9995
:
1.1852
<= 1.1845
Units
32767
32511
:
27649
27648
20736
:
:
0
- 1
:
- 4864
- 32768
Meas.range
-200...+850ºC
Temperature
e.g. Pt100
Units
32767
10000
:
8501
8500
:
:
:
-2000
- 2001
:
- 2430
- 32768
>= 1000.1
1000.0
:
850.1
850.0
:
:
:
-200.0
- 200.1
:
- 243.0
<= - 243.1
Meas.range
0...300Ohm
Resistance
e.g.:
>=352.778
352.767
:
300.011
300.000
225.000
:
:
0.000
Negative
values
not
possible
Units
32767
32511
:
27649
27648
20736
:
:
0
- 32768
- 1
:
- 4864

Date: 03.09.24
File: PRO1_14E.10
SIMATIC S7
Siemens AG 1999. All rights reserved.
Information and Training Center
Knowledge for Automation
Scaling Analog Input Values
500,0
0,0
0 27648

Date: 03.09.24
File: PRO1_14E.11
SIMATIC S7
Siemens AG 1999. All rights reserved.
Information and Training Center
Knowledge for Automation
Unscaling a Real Number for Analog Output
27648
0
0,0 100,0

Date: 03.09.24
File: PRO1_14E.12
SIMATIC S7
Siemens AG 1999. All rights reserved.
Information and Training Center
Knowledge for Automation
Analog Value Representation for the Analog Outputs
Range
Overflow
Overrange
Rated range
Underrange
Underflow
Units
>=32767
32511
:
27649
27648
:
0
:
- 6912
- 6913
:
:
:
- 27648
- 27649
:
- 32512
<=- 32513
Output ranges:
Voltage
0
11.7589
:
10.0004
10.0000
:
0
0 to 10V 1 to 5V
0
5.8794
:
5.0002
5.0000
:
1.0000
0
11.7589
:
10.0004
10.0000
:
0
:
:
:
:
:
:
:
-10.0000
- 10.0004
:
- 11.7589
0
± 10V
0
0.9999
0
0
Output ranges:
Current
0
23.515
:
20.0007
20.000
:
0
0 to 20mA 4 to 20mA
0
22.81
:
20.005
20.000
:
4.000
0
23.515
:
20.0007
20.000
:
0
:
:
:
:
:
:
:
-20.000
- 20.007
:
- 23.515
0
± 20mA
0
3.9995
0
0

Date: 03.09.24
File: PRO1_14E.13
SIMATIC S7
Siemens AG 1999. All rights reserved.
Information and Training Center
Knowledge for Automation
Exercise: Assigning Parameters to the Analog Module SM335

Date: 03.09.24
File: PRO1_14E.14
SIMATIC S7
Siemens AG 1999. All rights reserved.
Information and Training Center
Knowledge for Automation
Exercise: Assigning Parameters to the Analog Module SM331

Date: 03.09.24
File: PRO1_14E.15
SIMATIC S7
Siemens AG 1999. All rights reserved.
Information and Training Center
Knowledge for Automation
Exercise: Controlling the Level in a Tank
Level
transmitter
Min. level 50 l.
When the level falls below
this, a message is to be
output at output Q9.2
(Q 5.2).
Max. level of 600 l,
equals 10 V at
analog channel 0

Date: 03.09.24
File: PRO1_14E.16
SIMATIC S7
Siemens AG 1999. All rights reserved.
Information and Training Center
Knowledge for Automation
Exercise: Diagnostic Interrupt from an Analog Module
Analog input module
When the value measured at an analog
channel of the module exceeds the
overflow range, OB82 is called, as well
as when it re-enters the range.
Rated range
Overrange
Overflow
Task:
Output Q 9.1 (Q 5.1) is to flash as long
as one of the encoded values is in the
overflow range.
.
Tags