Line to Line & Double Line to Ground Fault On Power System
qwerty7696
19,049 views
15 slides
Aug 05, 2017
Slide 1 of 15
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
About This Presentation
In this slide given the information about symmetrical fault , its derivations , examples etc..
Size: 280.48 KB
Language: en
Added: Aug 05, 2017
Slides: 15 pages
Slide Content
Name :- Smit Shah -140410109096 T.Y Electrical 2 Sem 6 Subject :- Electrical power system 2 Topic :-Line to Line & Double Line to Ground Fault On Power System 1
Line-‐to-‐Line Faults To represent a line-‐to-‐line fault through impedance Z f the hypothetical stubs on the three lines at the fault are connected as shown. Bus k is again the fault point P, and without any loss of generality, the line-‐to-‐line fault is regarded as being on phases b and c. Clearly: I fb I fc a Z f k k c I fa I fa k b I fb I fc V kb V kc Z I f f b 2
Line‐To‐Line Fault Three‐phase generator with a fault through an impedance Z f between phase b and c . I a =0 Z s N Z s Z s E a E b E c I b V a Z f I c V b V c Assuming the generator is initially on no‐load, the boundary conditions at the fault point are: V b V c Z f I b I a I b I c 3
Line‐To‐Line Fault 4 Substituting for I a = 0, and I c = ‐I b , the symmetrical components of the currents from are: From the above equation, we find that: a I (10.68) b a 3 1 1 2 I ( a a ) I a 1 2 2 I ( a a ) I b (10.69) (10.70) 3
Line‐To‐Line Fault Also, from (10.69) and (10.70), we note that: 1 2 a a I I From (10.16), we have: (10.71) 1 2 b a a a a V V a 2 V 1 aV 2 a a a V V V V (10.16) a a Z f I b ( a a ) ( V V ) V V ( V a 2 V 1 aV 2 ) ( V aV 1 a 2 V 2 ) b c a a a a a a 2 1 2 (10.72) 0 1 2 2 a a a c V V aV a V Substituti ng for V 1 and V 2 from (10.54) and noting I 2 I 1 , we get : a a a a a f b ( a a )[ E a ( Z Z ) I ] Z I 2 1 2 1 (10.73) (10.54) 2 2 2 a a V Z I a a V Z I V 1 E Z 1 I 1 a a a Substituti ng for I b from (10.69), we get : 1 3 I a a a f ( a a 2 )( a 2 a ) E ( Z 1 Z 2 ) I 1 Z (10.74) b a 1 1 2 I ( a a ) I 3 (10.69) 5
Line‐To‐Line Fault a Since (a a 2 )(a 2 a) 3, solving for I 1 results in : f a E a ( Z 1 Z 2 Z ) I 1 (10.75) The fault current is b I I ( a 2 a ) I 1 c a or a b I j 3 I 1 (10.77) (10.78) 6
Line‐To‐Line Fault Eq. (10.71) and (10.75) can be represented by connecting the positive and negative – sequence networks as shown in the following figure. 1 2 a a I I 1 a E I f a ( Z 1 Z 2 Z ) 7
Line- ‐to-‐Line Faults Thus , all the fault conditions are satisfied by connecting the positive-‐ and negative-‐sequence networks in parallel through impedance Z f as was shown. The zero-‐sequence network is inactive and does not enter into the line-‐to-‐line calculations. The equation for the positive-‐sequence current in the fault can be determined directly from the circuit as: 8
Double Line-‐to-‐Ground Faults Again it is clear, with fault taken on phases b and c, that the relations at fault bus k are: I fa I fb I fc a Z f I fa V kb V kc Z f I fb I fc k k b k c 9
Double Line‐To‐Ground Fault Figure 10.14 shows a three‐phase generator with a fault on phases b and c through an impedance Zf to ground. Assuming the generator is initially on no‐ load, the boundary conditions at the fault point are V b V c Z f ( I b I c ) (10.79) (10.80) I I I 1 I 2 a a a a From (10.16), the phase voltages V b and V c are 10
Double Line‐To‐Ground Fault 0 2 1 2 a a a V V aV 1 a 2 V 2 V b V a V aV a a c a (10.81) (10.82) SinceV b V c , from above we note that 1 2 a a V V (10.83) Substituting for the symmetrical components of current in (10.79), we get V Z ( I a 2 I 1 aI 2 I aI 1 a 2 I 2 ) ( b ) f a a a a a a Z (2 I I 1 I 2 ) f a a a f a I 3 Z (10.84) 11
Substituti ng for V from (10.84) and for V 2 from (10.83) into (10.81), we have : b a a a f a a a V V 1 3 Z I V ( a 2 a ) V 1 (10.85) E Z 1 I 1 Substituti ng for the symmetrical components of voltage from (10.54) into (10.85) a and solving for I , we get : a a a ( Z 3 Z ) I f Also, substituting for the symmetrical components of voltage in (10.83), we obtain E Z 1 I 1 (10.86) Z 2 a I 2 a a Substituti ng for I and I 2 into (10.80) and solving for I 1 , we get : a a a (10.87) E a a 2 0 1 Z 2 Z 3 Z f Z ( Z 3 Z f ) Z I 1 (10.88) 12
Equation (10.86) - (10.88) can be represented by connecting the positive - sequence impedance in series with the paralel combination of the negative - sequence and zero - sequence networks as shown in the equivalent circuit of figure 10.15. The value of I 1 found from (10.86) is substituted in (10.86) and (10.87), a and I and I 2 are found. The phase current are then found from (10.8). a a Finally, the fault current is obtained from (10.89) I I I 3 I c a b f Figure 10.15 Sequence network connection for double line‐to‐ground fault 13
Double Line-‐to-‐Ground Faults For a bolted fault Z f is set equal to 0. When Zf = ∞, the zero-‐ sequence circuit becomes an open circuit, no zero-‐sequence current an flow, and the equations revert back to those for the line-‐to-‐line fault. Again we observe that the sequence currents, once calculated, can be treated as negative injections into the sequence networks at the fault bus k and the sequence voltage changes at all buses of the system can then be calculated from the bus impedance matrices, as we have done in all along. 14