PERFORMANCE OF FANS
AFTER RETROFITTING
AT VARIOUS PLANTS
At the heart of perfect systems
Saving in, power consumed for a period of one year,
considering at Rs. 4.50 per kW for 7000 operating hours.
(252-165) x 7000 x 4.50 = Rs. 27,40,500/-
Therefore average saving in power for one month
=Rs. 27,40,500.00 / 12
=Rs. 2,28,375.00
Return on investment = 10,00,000/2,28,375 = 4.37 Months.
Example : Application : Cooler ESP Fan in Cement Plant
Client : Manikgarh Cement
At the heart of perfect systems
Client : Manikgarh Cement Application : Cooler ESP Fan
Before Retrofitting
420,120 m
3
/HrFlow
Static Pressure
Power
Fan Speed
180 mm WG
402 kW
740 rpm
After Retrofitting
500,040 m
3
/Hr
85 mm WG
165 kW
472 rpm
Components replaced : Impeller, Shaft &
Inlet Cone
Reason for retrofitting : Improving Efficiency
Existing Fan Make : ABB
Efficiency 51.2 % 70.1 %
441,360 m
3
/Hr
45 mm WG
252 kW
469 rpm
21.5 %
Design Operating
At the heart of perfect systems
Client : India Cements Ltd.. Application : VRM Exhaust Fan
Before Retrofitting
6,30,000 m
3
/HrFlow
Static Pressure
Power
Fan Speed
950 mm WG
2100 kW
980 rpm
After Retrofitting
6,30,000 m
3
/Hr
1000 mm WG
2016 kW
971 rpm
Components replaced : Impeller, Shaft &
Inlet Cone
Reason for retrofitting : Improving Efficiency
Existing Fan Make : Hamada Blower Co.
Efficiency 77.6 % 85 %
At the heart of perfect systems
Client : Raasi Cement Ltd. Application : Waste Gas Fan
Before Retrofitting
414,000m
3
/HrFlow
Static Pressure
Power
Fan Speed
900 mm WG
1463 kW
950 rpm
After Retrofitting
414,000 m
3
/Hr
900 mm WG
1424 kW
950 rpm
Components replaced : Impeller, Casing &
Inlet Cone
Reason for retrofitting : Improving Efficiency
Existing Fan Make : Andrew Yule
Efficiency 69.4 % 77.26 %
At the heart of perfect systems
Client : Orient Cements Application : Pre Heater Fan
Before Retrofitting
384,240m
3
/HrFlow
Static Pressure
Power
Fan Speed
800 mm WG
1186 kW
990 rpm
After Retrofitting
432,000 m
3
/Hr
750 mm WG
1086 kW
880 rpm
Components replaced : Impeller, Casing &
Inlet Cone
Reason for retrofitting : Improving Capacity &
Increasing Efficiency
Existing Fan Make : KHD HUMBOLDT
Efficiency 70.6 % 81.3 %
At the heart of perfect systems
Client : ACC - Wadi Application : K3 Waste Gas Fan
Before Retrofitting
293,400 m
3
/HrFlow
Static Pressure
Power
Fan Speed
900 mm WG
1060 kW
980 rpm
After Retrofitting
332,800 m
3
/Hr
975 mm WG
1065 kW
989 rpm
Components replaced : Impeller, Shaft &
Inlet Cone
Reason for retrofitting : Power Saving and
Increasing Capacity
Existing Fan Make : ABB
Efficiency 67.8 % 78.2 %
At the heart of perfect systems
Before Retrofitting
6,50,000 m
3
/HrFlow
Static Pressure
Power
Efficiency
140 mm WG
413 kW
60 %
After Retrofitting
738,000 m
3
/Hr
250 mm WG
646 kW
82 %
Components replaced : Impeller, Shaft &
Inlet Cone
Reason for retrofitting : Improving Efficiency,
power saving and
increasing capacity
Existing Fan Make : FLS
At the heart of perfect systems
Client : Larsen & Toubro - Awarpur Application : Kiln ESP Fan
Fan speed 300 rpm 365 rpm
Client : ACC - Wadi Application : K1 & K2 Waste Gas Fan
Before Retrofitting
189,360m
3
/HrFlow
Static Pressure
Power
Fan Speed
960 mm WG
660 kW
980 rpm
After Retrofitting
189,360 m
3
/Hr
960 mm WG
586.5 kW
992 rpm
Components replaced : Impeller, Shaft &
Inlet Cone
Reason for retrofitting : Power Saving and
Increasing Capacity
Existing Fan Make : ABB
Efficiency 75 % 84.5 %
At the heart of perfect systems
Client : Larsen & Toubro - Awarpur Application : Cooler ESP
Fan
Before Retrofitting
780,000m
3
/HrFlow
Static Pressure
Power
Fan Speed
150 mm WG
501 kW
500 rpm
After Retrofitting
780,000 m
3
/Hr
180 mm WG
474 kW
509 rpm
Components replaced : Impeller, Casing &
Inlet Cone
Reason for retrofitting : Power Saving and
Increasing Capacity
Existing Fan Make : FLS
Efficiency 63.5 % 80.7 %
At the heart of perfect systems
Client : Raasi Cement Ltd. Application : Cooler ESP Fan
Before Retrofitting
681,840 m
3
/HrFlow
Static Pressure
Power
Fan Speed
165 mm WG
381 kW
590 rpm
After Retrofitting
732,960 m
3
/Hr
150 mm WG
428 kW
678 rpm
Components replaced : Impeller, Shaft &
Inlet Cone
Reason for retrofitting : Improving Efficiency
Existing Fan Make : Batliboi
Efficiency 81.5 % 70.0 %
591,000 m
3
/Hr
80 mm WG
390 kW
600 rpm
33.0 %
Design Operating
At the heart of perfect systems
Client : Zuari Cement Application : Raw Mill Fan
Before Retrofitting
180,000 m
3
/HrFlow
Static Pressure
Power
Efficiency
615 mm WG
520 kW
58 %
After Retrofitting
180,000 m
3
/Hr
615 mm WG
365 kW
82.6 %
Components replaced : Impeller, Shaft &
Inlet Cone
Reason for retrofitting : Power Saving and
Improving Efficiency
Existing Fan Make :
At the heart of perfect systems
Client : ACC - Lakheri Application : Bag House Fan
Before Retrofitting
300,000 m
3
/HrFlow
Static Pressure
Power
Fan Speed
300 mm WG
298 kW
945 rpm
After Retrofitting
330,000 m
3
/Hr
270 mm WG
309 kW
980 rpm
Components replaced : Impeller, Shaft &
Inlet Cone
Reason for retrofitting : Improving Efficiency
& Increasing Capacity
Existing Fan Make : ABB
Efficiency 54.8 % 78.5 %
At the heart of perfect systems
Client : JK Corp - Lakshmi Cements Application : Cooler Vent
Fan
Before Retrofitting
2,45,000 m
3
/HrFlow
Static Pressure
Power
Fan Speed
330 mm WG
367 kW
985 rpm
After Retrofitting
4,66,000 m
3
/Hr
172 mm WG
297 kW
980 rpm
Components replaced : Impeller, Shaft &
Inlet Cone
Reason for retrofitting : Improving Efficiency
& Increasing Capacity
Existing Fan Make : Andrew Yule
Efficiency 60 % 73 %
At the heart of perfect systems
Client : Madras Cements Ltd. Application : Pre Heater Fan
Before Retrofitting
72,000 m
3
/HrFlow
Static Pressure
Power
Fan Speed
650 mm WG
164 kW
985 rpm
After Retrofitting
85,000 m
3
/Hr
750 mm WG
193 kW
980 rpm
Components replaced : Impeller, Casing &
Inlet Cone
Reason for retrofitting : Increasing Capacity
Existing Fan Make : Andrew Yule
Efficiency 78.0 % 79.6 %
At the heart of perfect systems
Client : Orient Cement Application : Cooler ESP Fan
Before Retrofitting
405,000 m
3
/HrFlow
Static Pressure
Power
Fan Speed
125 mm WG
187 kW
745 rpm
After Retrofitting
390,000 m
3
/Hr
100 mm WG
135 kW
745 rpm
Components replaced : Impeller, Shaft &
Inlet Cone
Reason for retrofitting : Improving Efficiency
Existing Fan Make : Andrew Yule
Efficiency 73.7 % 78.7 %
294,000 m
3
/Hr
70 mm WG
190 kW
710 rpm
29.5 %
Design Operating
At the heart of perfect systems
Client : ACC - Chanda Cement Works Application : Kiln ESP Fan
Before Retrofitting
2,00,000 m
3
/HrFlow
Static Pressure
Power
Fan Speed
130 mm WG
120 kW
980 rpm
After Retrofitting
2,00,000 m
3
/Hr
130 mm WG
95 kW
971 rpm
Components replaced : Impeller, Shaft &
Inlet Cone
Reason for retrofitting : Improving Efficiency
& Increasing Capacity
Existing Fan Make : Kilburn
Efficiency 59 % 75 %
At the heart of perfect systems
D) Overall dimensions of existing Fan arrangement, as marked `?’ ;
C) Overall dimensions of existing Fan Casing, as marked `?’ ;
IMPROVEMENT OF EFFICIENCY BY INSERTING HIGH EFFICIENCY IMPELLER
IN THE EXISTING CASING OF LOW EFFICIENCY CENTRIFUGAL FANS
A) DESIGN PARAMETERS B) REVISED PARAMETERS,
OF EXISTING FAN : IF ANY :
Application : …….……... : ……………..
Flow rate, m
3
/Hr: …………… : ……………..
Static Pressure, mm WG : …………... : ……………..
Temperature,
o
C : …………... : ……………..
Inlet Density, Kg/m
3
: …………… : ……………..
Fan Speed, RPM : …………… : ……………..
Dust Load, Kg/m
3
: …………… : ……………..
Fan Shaft Power, kW : …………... : ……………..
Arrangement of Fan : …………... : ……………..
Drive Arrangement : …………... : ……………..
Make of the Fan : ………. …. : ……………..
Model No. of the Fan : …………... : ……………..
Motor connected-kw&rpm : …………... : ……………..