1. QUALITY OBSERVATIONS 2. GOOD PRACTICES AND BAD PRACTICES 3. PMC/CLIENT MAJOR REPEATED COMMENTS 4. QUALITY ISSUES AND NCR ` INTRODUCTION:
QUALITY OBSERVATIONS A-BLOCK B-BLOCK PODIUM
QUALITY OBSERVATIONS A-BLOCK
LOCATION: A-BLOCK, 3 rd FLOOR,POUR-1,ARTIFICIAL GRASS TURF AREA HONEYCOMBS FOUND. ROOT CAUSE: LACK OF SUPERVISION NOT DONE PROPER MALLETING WITH RUBBER HAMMER CORRECTIVE ACTION: 1.REMOVE OFF LOOSE PARTICALS AND BINDING WIRES 2.FINISH WITH APPROVED METHODOLGY PREVENTIVE ACTION: AFTER CONCRETING PROPER MALLETING SHOULD BE DONE STATUS: CLOSED 03.02.24 04.02.24
LOCATION: A-BLOCK, 3 rd FLOOR,PARTY AREA,COLUMN BOTTOM HONEYCOMBS FOUND. ROOT CAUSE: LACK OF SUPERVISION NOT PACKING WITH FOAM SHEET PROPERLLY CORRECTIVE ACTION: 1.REMOVE OFF LOOSE PARTICALS AND FOAM SHEET 2.FINISH WITH APPROVED METHODOLGY PREVENTIVE ACTION: BEFORE CONCRETING PROVIDE FOAM SHEET IN GAPS STATUS: CLOSED 14.02.24 14.02.24
LOCATION: A-BLOCK, GROUND FLOOR,SW-3, WALL BULGE 20MM FOUND . ROOT CAUSE: LACK OF SUPERVISION NOT PROVIDE PROPER TIEROD AND SUPPORTS CORRECTIVE ACTION: 1.CHIPPING OF BULGE SURFACE AND CLEAN WITH WATER 2.FINISH WITH APPROVED METHODOLGY PREVENTIVE ACTION: BEFORE CONCRETING PROVIDE PROPER TIEROD AND SUPPORTS STATUS:OPEN
LOCATION: A-BLOCK, GROUND FLOOR,SW-3, WALL BULGE 25MM FOUND . ROOT CAUSE: LACK OF SUPERVISION NOT PROVIDE PROPER SUPPORTS CORRECTIVE ACTION: 1.CHIPPING AND GRINDING TO BULGED SURFACE 2.FINISH WITH APPROVED METHODOLGY PREVENTIVE ACTION: BEFORE CONCRETING PROVIDE PROPER SUPPORTS STATUS:OPEN
LOCATION: A-BLOCK, 3 rd FLOOR, MASTER SUIT ROOM,WINDOW OPENING TOP CONCRETE FILLED IN GROOVE AREA FOUND . ROOT CAUSE: LACK OF SUPERVISION NOT PROVIDE PROP HEAD WITH GROOVE CORRECTIVE ACTION: ENSURE PROPER SIZE GROOVE CUTTING AND CHIPPING TO BE . 2.FINISH WITH APPROVED METHODOLGY. AFTER THAT MAKE SURFACE GRINDING . PREVENTIVE ACTION : PROVIDE PROP HEAD WITH GROOVE STATUS:OPEN
QUALITY OBSERVATIONS B-BLOCK
LOCATION: B-BLOCK 3 rd FLOOR, SUIT ROOM-02 ENTRANCE FOYER AREA , OPPOSITE LIFT LOBY ENTRANCE, HONEYCOMBS FOUND. ROOT CAUSE: LACK OF SUPERVISION NOT REMOVE BINDING WIRES AFTER TYING WORK COMPLETED CORRECTIVE ACTION: 1.REMOVE OFF LOOSE PARTICALS AND BINDING WIRES 2.FINISH WITH APPROVED METHODOLGY PREVENTIVE ACTION: PEP TALK CONDUCTED TO BARBENDERS AND CORPERNTERS . STATUS: CLOSED 05-02-2024 05-02-2024
LOCATION: B-BLOCK 4 TH FLOOR SUIT ROOM-01, CUTOUT BOTTOM REINFORCEMENT FOUND. ROOT CAUSE: LACK OF SUPERVISION NOT DONE PROPER MALLETING WITH RUBBER HAMMER CORRECTIVE ACTION: 1. SURFACE AREA SHOULD BE SHIPPING, REMOVE OFF LOOSE PARTICALS , CLEAN WITH WATER 2.FINISH WITH APPROVED METHODOLGY PREVENTIVE ACTION: PROVIDE BOTTOM COVER BLOCKS AND AFTER CONCRETING MALLETING SHOULD BE DONE STATUS: CLOSED 26-02-2024 26-02-2024
LOCATION: B-BLOCK SECOND AND THIRD FLOOR SUIT-3 WINDOW-4, PROP HEAD WITH GROOVE NOT PROVIDE ROOT CAUSE: IMPROPER SUPERVISION NOT PROVIDE GROOVE PROP HEAD CORRECTIVE ACTION: 1. PROPER SIZE GROOVE CUTTING AND CHIPPING TO BE DONE. AFTER THAT MAKE SURFACE GRINDING . PREVENTIVE ACTION: 1.PROVIDE GROOVE PROP HEAD. STATUS: CLOSED 24-02-2024 24-02-2024
LOCATION: B-BLOCK SECOND FLOOR LIFT LOBBY AREA HONEYCOMBS FOUND ROOT CAUSE: IMPROPER SUPERVISION AFTER CONCRETING MELLETING NOT DONE CORRECTIVE ACTION: REMOVE LOOSE PARTICALS FINISH WITH APPROVED METHODOLGY PREVENTIVE ACTION: DURING CONCRETING MELLETING SHOULD BE DONE STATUS: CLOSED 03-02-2024 03-02-2024
LOCATION: B-BLOCK THIRD FLOOR STAIRCASE-1, FLIGHT-1 TOP, HONEYCOMBS FOUND ROOT CAUSE: IMPROPER SUPERVISION AFTER CONCRETING MELLETING NOT DONE CORRECTIVE ACTION: REMOVE LOOSE PARTICALS FINISH WITH APPROVED METHODOLGY PREVENTIVE ACTION: DURING CONCRETING MELLETING HAS SHOULD BE DONE STATUS: CLOSED 25-02-2024 25-02-2024
LOCATION: B-BLOCK SECOND FLOOR ARTIFICIAL GRASS TURF AREA, WALL SURFACE PEEL OFF FOUND ROOT CAUSE: IMPROPER SUPERVISION SHUTTERING OIL NOT APPLY TO MIVAN PANELS, AND NOT CLEAN PANELS AFTER DE-SHUTTERING CORRECTIVE ACTION: LOOSE PARTICALS REMOVED AND CLEAN THE SURFACE WITH WATER FINISH WITH APPROVED METHODOLGY PREVENTIVE ACTION: CLEAN THE PANEL REGULARLLY BEFORE FIXING AND APPLY SHUTTERING OIL STATUS: CLOSED 25-02-2024 25-02-2024
LOCATION: B-BLOCK 5 TH FLOOR MASTER SUIT HONEYCOMBS FOUND ROOT CAUSE: IMPROPER SUPERVISION AFTER CONCRETING MELLETING NOT DONE CORRECTIVE ACTION: LOOSE PARTICALS REMOVED AND CLEAN THE SURFACE WITH WATER FINISH WITH APPROVED METHODOLGY PREVENTIVE ACTION: AFTER CONCRETE MELLETING NEED TO BE DONE STATUS: CLOSE 03-03-2024
LOCATION: B-BLOCK 3 RD FLOOR STAIRCASE-1, BULGE FOUND ROOT CAUSE: IMPROPER SUPERVISION NOT PROVIDE PROPER SUPPORTS CORRECTIVE ACTION: BULGE SURFACE CHIPPING AND CLEAN THE SURFACE WITH WATER FINISH WITH APPROVED METHODOLGY PREVENTIVE ACTION: PROVIDE PROPER SUPPORTING TO PANELS STATUS: OPEN
LOCATION: B-BLOCK GROUND FLOOR SHEAR WALL-9 BULGE FOUND ROOT CAUSE: IMPROPER SUPERVISION NOT PROVIDE PROPER SUPPORTS CORRECTIVE ACTION: BULGE SURFACE CHIPPING AND CLEAN THE SURFACE WITH WATER FINISH WITH APPROVED METHODOLGY PREVENTIVE ACTION: PROVIDE PROPER SUPPORTING TO PANELS STATUS: OPEN
LOCATION: B-BLOCK GROUND FLOOR SHEAR WALL-10 BULGE FOUND ROOT CAUSE: IMPROPER SUPERVISION NOT PROVIDE PROPER SUPPORTS CORRECTIVE ACTION: BULGE SURFACE CHIPPING AND CLEAN THE SURFACE WITH WATER FINISH WITH APPROVED METHODOLGY PREVENTIVE ACTION: PROVIDE PROPER SUPPORTING TO PANELS STATUS: OPEN
QUALITY OBSERVATIONS PODIUM
WEST SIDE FOOTING CONCRETE WASTAGE DUE TO FOOTING PASCHAL SHUTTERING BULGED
PCC NOT DONE AS PER DRAWING DIMENSIONS . FOOTING MARKING COMES ON EDGE OF PCC
LOCATION: SOUTH SIDE RETAINING WALL HONEY COMBS FOUND ROOT CAUSE: IMPROPER SUPERVISION NOT DONE PROPER MALLETING WITH RUBBER HAMMER CORRECTIVE ACTION: REMOVE LOOSE PARTICALS AND CLEANING WITH WATER FINISH WITH APPROVED METHODOLGY PREVENTIVE ACTION: 1.AFTER CONCRETING MALLETING SHOULD BE DONE AND GAPS CLOSE WITH FOAM SHEET STATUS: CLOSED
GOOD PRACTICES
CONCRETE CASTING DATES MENTION WITH STENCIL SHEET
After slab concrete Constructed curing ponds and maintain curing continuously.
AFTER SLAB CONCRETING FINISHING SHOULD BE DONE WITH POWER TROWEL
WALLS CURING SHOULD BE DONE WITH WATER SPRINKLER
After slab concrete Placed Hessain cloths and maintain curing continuously. Due to summer heat increased curing time.
During s lab concrete, Slab levels checked by level gauge rod .
During concrete work boom head cover with bag to overcome falling of concrete while boom shifting to one place to another place
BEFORE START PUMPING OF CONCRETE BOOM HEAD SHIFT TO OUTER OF SLAB AREA FOR PUMP SLURRY WATER(HI PUMP PRIME ) TO OUTSIDE OF SLAB.
During wall concrete continuous Rubber Hammer Malleting doing for avoid air gaps
DURING AND AFTER CONCRETEING CURING DONE ON PANELS FOR DECREASING HEAT
Apply shuttering oil to Mivan Panels with rollers before Panels fixing .
PROVIDED SHEARKEYS IN WALLS FOR BONDING TO FRESH CONCRETE
PROVIDED WOODEN STOPPERS BEFORE SLAB CONCRETE CASTING
APPLY NITO BOND SBR FOR BONDING PURPOSE IN BETWEEN FRESH AND EXISTING CONCRERE BEFORE CONCRETE POURING
MENTIONED PROPER NUMBERING ON MIVAN PANELS
PLACEING OF STEEL IN SAFE MANNER ON CONCRETE SLEEPERS
Slump at RMC Plant Slump at Site Checked the slump of Every RMC Vehicle in plant and Site.
Before setting out of concrete surface make BROOMING finishing being ensured to avoid cracks.
BAD PRACTICES
AFTER WORK COMPLETION BLOCK ENGINEERINGS ARE NOT KEPT COVER BLOCKS IN SAFE MANNER COLLECTED THE COVER BLOCKS AND HANDOVER IN STORE
COLLECTED THE STUB PIN AND HANDOVER IN STORE
AFTER CURING POND CONSTRUCTED STEEL RODS PLACED ON AND BROKEN IT, SO THAT CURING NOT PROPERLY HAPPEN
FOR VERTICAL REINFORCEMENT BARS MASTER RING NOT PROVIDE AT 1M LEVEL FROM SLAB
MINOR CRACKS ARE DEVELOPED IN PLASTERING DUE TO CURING NOT DONE PROPERLY AFTER PLASTERING DONE
3.PMC/CLIENT MAJOR REPEATED COMMENTS
Wall and slab junction area binding wire not Properly tying. Cover blocks not properly provided. Spacing not maintain properly in reinforcement. Cleaning not done properly. Vertical lapping length of bars not maintain properly. Master rings not provided.