Testing of transformers and reactors.ppt

vikramdesai15 424 views 52 slides Jun 24, 2024
Slide 1
Slide 1 of 52
Slide 1
1
Slide 2
2
Slide 3
3
Slide 4
4
Slide 5
5
Slide 6
6
Slide 7
7
Slide 8
8
Slide 9
9
Slide 10
10
Slide 11
11
Slide 12
12
Slide 13
13
Slide 14
14
Slide 15
15
Slide 16
16
Slide 17
17
Slide 18
18
Slide 19
19
Slide 20
20
Slide 21
21
Slide 22
22
Slide 23
23
Slide 24
24
Slide 25
25
Slide 26
26
Slide 27
27
Slide 28
28
Slide 29
29
Slide 30
30
Slide 31
31
Slide 32
32
Slide 33
33
Slide 34
34
Slide 35
35
Slide 36
36
Slide 37
37
Slide 38
38
Slide 39
39
Slide 40
40
Slide 41
41
Slide 42
42
Slide 43
43
Slide 44
44
Slide 45
45
Slide 46
46
Slide 47
47
Slide 48
48
Slide 49
49
Slide 50
50
Slide 51
51
Slide 52
52

About This Presentation

testing of transformers


Slide Content

TESTING OF
TRANSFORMERS
Tests on Bushing CTs
IR , Continuity and polarity, Ratio and Magnetization test
IR measurements
Ratio test
Vector group test
Floating Neutral point measurement
Magnetization current test
Magnetic balance test ( for 3 phase unit )
C & Tan delta measurement of bushings and windings

TESTING OF TRANSFORMERS
contd…
Winding resistance measurement
Tests on OLTC and Cooler controls
Alarm and trip tests
Core Isolation test
Testing of oil for DGA & other parameters
Oil filling , oil circulation and air venting

TESTS ON BUSHING CTs
Purpose
Thesetestsarecarriedouttoascertainthehealthinessofbushing
currenttransformeratthetimeoferectionandinservice.
Insulationresistancemeasurement
Insulation-resistancetestsisperformedbetweenCTwindingsand
togroundusingaMegger.Testvoltagewillbe500V.theneutral
groundmustberemovedandCTisolatedfromitsburden.Accepted
min.IRvalueis1M-Ohm
PolarityTest
DCKick/FlickTest:ThisisthetriedandtruemethodfortestingCT
polarity.Forthistest,adcbatterypack(6-10V),adcvoltmeteror
ammeter(preferablyanalog),andtestleadsarerequired.This
methodisaquickandeasytestforpolarityThestepsofthedc
kick/flicktestareasfollows:
ConnectthebatterypacktotheprimaryofbushingCTand
momentarydeflectionofpointerofvoltmeter(centreZero)
connectedtosecondaryisnoted.

Tests on Bushing CTs contd…
Closelywatchtheneedleoranalogscaleofthevoltmeter.It
shouldjumpinthepositivedirection.Thishappensina
fractionofasecond,sothemetermustbemonitoredvery
closely.Ifthevoltmeterkicksinthepositivedirection,the
polaritymarksarecorrect.Ifitkicksinthenegativedirection,
the polarity marks are incorrect.
Primaryandsecondaryleadsaresaidtohavesamepolarity
whenatagiveninstantthecurrententerstheprimaryleadin
questionandleavesthesecondaryleadinquestioninthe
samedirectionasthoughtwoleadsformedacontinuous
circuit.

Tests on Bushing CTs contd…
Ratiotest
TheCTratiotestdeterminestheCTaccuracy,andthe
resultsshouldbecomparedtotheaccuracyclass.The
stepsforaratio-verificationtestareasfollows:
Asuitablevoltage,belowsaturationisappliedtothe
secondary(fullwinding)andtheprimaryvoltageisread
withahighimpedancelowrangevoltmeter.
Connectavoltagesource(variabletransformer)and
voltmeteracrosstheCTsecondary.
ConnectavoltmeteracrosstheCTprimary.

Tests on Bushing CTs contd…
ApplyvoltagetotheCTsecondaryand
measurethesecondary(VM1)andprimary
voltages(VM2)simultaneously.Calculate
theratiobetweenthetwovoltages(VM1/
VM2).
ThisvoltageshouldmatchtheCTratio
(primary/secondary).Youcanrepeatthe
procedureaboveforeachtapofamultitap
CT,butIprefertotreattheCTtapsasI
wouldanautotransformer.Iapplyavoltage
acrossthemaximumratiotapandmeasure
allremainingtapstoacommonpoint.

Tests on Bushing CTs contd…
Magnetization test
Some of the following conditions can cause CT
saturation:
CT secondary burden greater than rated.
Extremely high current flowing through the
CT (fault current).
Current flowing through CT primaries with
open-circuit secondaries.
DC current flowing through either winding.

Tests on Bushing CTs contd…
TheexcitationtestisusedtoprovethattheCTisnot
saturatedandwilloperatewithinspecificationsatthe
ratedburden.Itisimportanttorememberwhen
comparingtestresultstotheburdenratingthatthe
burdenratingisaminimumvalue.TheCTcould
actuallyhaveahigherrating.Thishappensoftenin
transformerbushingapplications.
Asaturationtestisperformedbyapplyingacvoltage
totheCTsecondaryandincreasingthevoltagein
stepsuntiltheCTisinsaturation.Thetestvoltageis
slowlydecreasedtozerotodemagnetizetheCT.
Thetestresultsareplottedonalogarithmicgraph
andevaluatedbasedonthetransitionperiod
betweennormaloperationandsaturation.This
transitioniscalledthekneeofthecurveandis
directlyrelatedtothevoltageburdenratingofthe
CT.

IR MEASUREMENTS
Purpose
Thisisthesimplestandmostwidelyusedtestto
checkthesoundnessoftransformerinsulation.
Thistestrevealstheconditionofinsulationi.e
degreeofdrynessofpaperinsulation,presenceof
anyforeigncontaminantsinoilandalsoanygross
defectinsidethetransformer.
TheinstrumentusedisMegohmMeterpopularly
knownasMegger.IRvaluemeasurementsofEHV
transformerstobedonewith5KVMegger.

IR MEASUREMENTS contd….
Safety instructions
Thetestspecimenisdischargedbyshort
circuitingforaperiodatleastfourtimesas
longasthetestvoltagewasapplied.Before
barehandcontact,theabsenceofvoltage
shallbeconfirmedbymeasurement.
Precautions
Cleanthebushingporcelainsbywipingwitha
pieceofdrycloth.

IR MEASUREMENTS contd…
Leadwiresfromthebushinglineleadandtankearth
tomeggershallbeasshortaspossiblewithoutjoints
andshallnottouchtankoreachother.
Testingprocedure
IRmeasurementsshallbetakenbetweenthe
windingscollectivelyi.ewithallthewindingsbeing
connectedtogetherandtheearthedtankand
betweeneachwindingandthetank,therestofthe
windingsbeingearthed.Followingmeasurementsare
relevantforauto-transformersandReactors

IR MEASUREMENTS contd…
ForAutotransformer ForReactor
HV+IV/E HV/E
LV/E
HV+IV/LV
HV-HighVoltage,IV-IntermediateVoltage,LV–Low
Voltage,E-Earth
Recorddateandtimeofmeasurementsl.no&makeof
megger,oiltemperatureandIRvaluesatintervalsof15
seconds,1minuteand10minutes

IR MEASUREMENTS contd…
Evaluation of test results
Inair,IRvalueswillbenearly15-20timesmorethan
intransformeroilatthesametemperature.
Withevery10°Cdropintemperature,IRvalues
increasesbyapproximately1.5timesi.e.anIRvalue
of200M-ohmsatanoiltemp.of40°Cisequivalentto
300M-ohmsat30°C.
FollowingIRvaluesasathumbrulemaybe
consideredastheminimumsatisfactoryvaluesat
30°C(oneminutemeasurements)atthetimeof
commissioning

IR MEASUREMENTS contd…
Rated Voltage class Minumum desired
of Winding IR value at 1 min.
11 KV 300 M-ohms
33 KV 400 M-ohms
66 KV & above 500 M-ohms

IR MEASUREMENTS contd…
Polarisation Index
It is the ratio of the 10 min to 1 min readings.
Polarisation Index Insulation condition
Less than 1 Dangerous
1.0 –1.1 Poor
1.1 –1.25 Questionable
1.25 –2.0 Fair
Above 2.0 Good

RATIO TEST
Purpose
Todeterminetheturnsratiooftransformers.
Turnsratioistheratioofthenumberofturnsina
higherwindingtothatinalowerwinding.
PRECAUTIONS
ThevoltageshouldbeappliedonlyintheHigh
voltagewindinginordertoavoidunsafevoltage.

Ratio test contd…
Testingprocedures
KeepthetappositioninthelowestpositionandIVandLV
terminalsopen.
Apply3phase415VsupplyonHVterminals
Measurevoltagesappliedoneachphase(Phase-Phase)onHV
andIVterminalssimultaneously
Repeatabovestepsforeachofthetappositionseparately
RepeatabovestepsafterinterchangingthevoltmetersofHVand
IVwindingsandthenaveragethereadingsforfinalcalculationof
ratio.
TheabovetestcanalsobeperformedbyTransformerturns
rationmeter(TTR)
Twowindingsononephaseofatransformerareconnectedto
theinstrumentandintheinternalbridgeelementsarevariedto
produceanullindicationonthedetector

Ratio test contd…
Evaluation of results
Theturnsratiotoleranceshouldbewithin0.5%
Outoftoleranceratiomaybesymptomaticofshorted
turnsespeciallyifthereisanassociatedhigh
excitationcurrent.
Ratiomeasurementsmustbemadeonalltapsto
confirmtheproperalignmentandoperationofthetap
changers.
Openturnsintheexcitedwindingwillbeindicated
withverylowexcitingcurrentandnooutputvoltage

VECTOR GROUP TEST
Purpose
To determine the phase relationship and polarity of transformers.
Testing procedures
Connect Neutral point and LV phase with earth.
Join 1R1 of HV and 3R1 of tertiary.
Apply 415 V 3 phase supply to HV terminals
Measure voltage across the following terminals
1R1 –1Y1 3Y1 –1B1 3Y1 -N 2Y1 -N
1Y1 -1 B1 3Y1 –1Y1 1R1 –N 2B1 -N
1B1 –1 R1 3R1 –N 2R1 -N

Vector group test contd…
Evaluation of results
Ensure 2R1 –N = 2Y1 –N = 2B1 –N
Ensure 3R1 –N > 3Y1 –N > 3B1 –N
 3Y1 –1B1 >3Y1 –1Y1
The above confirms vector group Y naod 11

FLOATING NEUTRAL POINT
MEASUREMENT
Purpose
Thistestisconductedtoascertainpossibilityofshortcircuitina
winding.
Precaution
Nowindingterminalshouldbegrounded.
Testingprocedure
Keepthetapinnormalposition
Disconnectthetransformerneutralfromground.
Apply3phase415VintheHVwindingandmeasurevoltage
acrosseachoftheIVwindingandneutral,thenneutraland
ground.
Apply3phase415VtoIVwindingandmeasurevoltageacross
eachofthetertiarywindingterminalandneutral,thenneutral
andground.
Evaluationoftestresults
Forahealthytransformerthevoltagebetweenneutraland
groundshouldbezeroornegligible.

MAGNETISING CURRENT
TEST
Purpose
Thistestisperformedtolocatedefectinmagnetic
corestructure,shiftingofwindings,failuresinturnto
turninsulationorproblemsintapchangers.
Precautions
ThistestshouldbedonebeforeDCmeasurementsof
windingresistancetoreducetheeffectofresidual
magnetism.Thetransformermaybedemagnetised
beforecommencementofmagnetisingcurrenttest.

MAGNETISING CURRENT TEST
contd
Testing Procedure
KeepthetappositioninthelowestpositionandIVandLV
terminalsopen.
Apply3phase415VsupplyonHVterminals.
Measurethevoltagesappliedoneachphase(phase–phase)
onHVterminalsandcurrentineachphaseofHVterminal.
Aftercompletionoftheabovesteps,repeatthemeasurements
intappositionNormalaswellasinHighestposition.
KeepthetappositioninnormalandkeepHVandLVterminals
open.
Apply3phase415VsupplyonIVterminals
MeasurephasetophasevoltagebetweentheIVterminalsand
currentoneachoftheIVterminals.

MAGNETISING CURRENT TEST
contd…
Evaluation of test results
Thesetofreadingsforcurrentmeasurementsineach
ofthetappositionshouldbeequal.Unequalcurrents
shallindicatepossibleshortcircuitsinwinding.
Resultsbetweensimilarsingle-phaseunitsshouldnot
varymorethan10%.Thetestvaluesontheoutside
legsshouldbewithin15%ofeachotherandvalues
forthecentrelegshouldnotbemorethaneither
outsidefora3phasetransformer.
Ifanoutoftolerancereadingisexperiencedwhile
turnsratio,windingresistanceandimpedancetests
arenormal,residualmagnetismshouldbe
suspected.

MAGNETIC BALANCE TEST
Purpose
Thistestisconductedtochecktheimbalance
inthemagneticcircuitonlyin3phaseX’mers.
Precautions
Nowindingterminalshouldbegrounded,
otherwiseresultswouldbeerraticand
confusing.

MAGNETIC BALANCE TEST
contd…
Testing Procedures
Keepthetapinnormaltapposition
DisconnecttheX’merneutralfromground
Applysinglephase230Vacrossonephase
ofIVwindingterminalandneutral(sayV1)
thenmeasurevoltageinothertwoIV
terminalsacrossneutral(sayV2&V3).
Repeatthetestforeachofthethreephases.
RepeattheabovetestforHVwindingalso.

MAGNETIC BALANCE TEST
contd…
Evaluation of results
Ensure that V1 = V2 + V3
Zero voltage or very negligile voltage induced
in other two windings should be investigated.

C AND TAN DELTA
MEASUREMENT( BUSHING)
Purpose
Insulationpowerfactorordissipationfactor(Tan
delta)andcapacitancemeasurementofbushing
provideanindicationofthequalityandsoundnessof
theinsulationinthebushing.
Precautions
Measurementmaybemadeatlowvoltagesusually
below10KV.
Connectiontooverheadbusatthebushingneedto
beremovedonlyifthebusaffectthereadings
appreciably.
Porcelainofthebushingsshallbecleananddry.

C AND TAN DELTA MEASUREMENT(
BUSHING)contd…
Testsshallnotbecarriedoutwhenthereiscondensationonthe
porcelainandwhentheRHisinexcessof80%.
Terminalsofthebushingsofeachwindingshallbeshortedtogether
usingbarebraidedcopperjumper.Thesejumpershallnotbeallowedto
sag.Transformerwindingsnottestedshallbegrounded.
Measureandrecordambienttemperatureandrelativehumidityfor
reference.
Ensurethatthetestspecimenisisolatedfromotherequipments.
Connectthegroundterminalofthetestsettoalowimpedanceearth
ground(toearthmatofthesub-station)

TypeTests
Routine Tests
Special Tests
Tan Delta & Capacitor Measurement

TypeTests
Routine Tests
Special Tests
Tan Delta & Capacitor Measurement
Mains & Commutating Mode

Routine Tests
Special Tests
Tan Delta Testing
For Null Condition
N
1
I
1
= N
2
I
2
For Capacitive Current
N
1
ICs = N2 ICx
N
1
VCs = N
2
VCx
Cx = (N1/N2)/Cs

TypeTests
Routine Tests
Special Tests
Tan Delta Measurement of Bushings

TypeTests
Routine Tests
Special Tests
Tan Delta Measurement of Bushings
For C
1
: Apply 10kV between HV and test tap on UST mode.
For C
2
: Apply 500 kV between Test tap and Ground with
HV Guarded on GSTg mode

TypeTests
Routine Tests
Special Tests
UST Mode
Earth will be connected to N Point
Hence only C
HL
will be measured

TypeTests
Routine Tests
Special Tests
GST Mode
Here measurement is made for the
Parallel combination of C
H
and C
HL

TypeTests
Routine Tests
Special Tests
GSTg mode
Here measurement is done for C
H
as L is guarded

C & Tan measurement contd…
Windings
ForICTs(2WindingTransformers),followingcombinationshall
betaken:
HV+IV&LVinUSTmode,bothMainsandreverseandaverage
tobetakentonullifyexternalinterference
HV+IV&Tank(LVtoGndtoGuard)inGSTgmode
LV&Tank(LVtoGndandHVtoGuard)inGSTgmode
-ForReactors,themeasurement shouldbedonein
HV/Tank+GndinGSTmode
-For3windingtransformer,measurementtobemadebetween
eachwindingandGndwithoneremainingwindingguardedand
thesecondremaoningwindinggroundedinGSTgtestmode

C & Tan measurement
contd…
Windings contd.
Thetestisperformedat10KV
Max.valueofTanofclassApaperinsulation,oil
impregnatedat20°Cshouldbe0.007.
RateofchangeofTanandcapacitanceshouldbe
marginal.Tanshouldnotvarymorethan0.001
frompreviousvalue.Capacitancevalueshouldbe
+10%,-5%
Tanmeasurementistemperaturedependentand
correctionfactorshouldbeapplied,if
measurementistakenattemperatureotherthan20
°C.

C & Tan measurement contd…
For ICTs :
Tan delta and Capacitance measurement of windings
should be done in combination of
HV+IV / LV+TANK+E
HV+IV+LV / TANK+E
LV/HV+IV+TANK+E IN GST TEST MODE
For Reactors
HV / TANK+E IN GST TEST MODE

WINDING RESISTANCE
MEASUREMENT
Purpose
Transformerwindingresistancearemeasuredinthefieldto
checkforanyabnormalitiesduetolooseconnections,broken
strandsandhighcontactresistanceintapchangers.
Precautions
Asthetransformerresistanceisoflowresistance,the
measurementhastobecarriedoutwiththehelpofKelvin
DoubleBridge/Transformerohmmeter
Toreducethehighinductiveeffectitisadvisabletousea
sufficientlyhighcurrenttosaturatethecore.Thiswillreducethe
timerequiredtogetastabilisedreading.
Itisessentialthatthetemperatureofthewindingsisaccurately
measured.

WINDING RESISTANCE
MEASUREMENT contd…
Testing Procedure
Forstarconnectedauto-transformerstheresistance
oftheHVsideismeasuredbetweenHVterminaland
IVterminal,thenbetweenIVterminalandneutral
Fordeltaconnectedwindings,suchastertiary
windingofautotransformers,measurementshallbe
donebetweenpairsoflineterminalsandresistanceof
windingshallbecalculatedasperthefollowing
formula
Resistanceperwinding=1.5xMeasuredvalue
Calculatetheresistanceat75°Casperthefollowing
formula
R75=Rt(235+75)/(235+t)WhereRtisthe
resistancemeasuredatwindingtemperature

WINDING RESISTANCE
MEASUREMENT contd…
Evaluation of test results
Expecteddeviationforthistestatsiteis5.0%
ofthefactorytestvalue.
Theresistancevalueobtainedshouldbe
comparedwiththefactorytestvalueincase
ofpre-commissioningandwithpre-
commissioningtestvalueincasethetestis
carriedoutduringroutinemaintenance.

OPERATIONAL TEST ON
OLTC
Purpose
OLTCaredesignedtobeoperatedwhilethetransformeris
energised.
OLTCbeingacurrentinterruptingdevicerequiresperiodic
inspectionandmaintenance.
Thefrequencyofinspectionisbasedontimeinservicemrange
ofuseandnumberofoperations.
Precautions
ThistestshallbecarriedoutduringshutdownperiodunderSFT
EnsureisolationofX’merforHVandLVsidewithphysical
openingofconcernedisolators.
Iftertiaryisconnected,ensureisolationofthesame

TAP CHANGER HAND
OPERATION
Checkhandoperationofthetapchanger
upanddownthefullrangebefore
electricaloperation.
Checkthecontinuityduringtapchanging
operationbyconnectingananalogue
multimeteracrossHV&IVbushingand
changethetappositionsfrommaximumto
minimum.

TAP CHANGER HAND
OPERATION contd…
CheckthatthetapchangermovesonetapatatimebypushingRor
Lpushbutton.
Checkaccurateindicationofmechanicalpositionindicatorinall
positions.Alsochecktheremoteinstrumentoperatesinthesame
sequencetothesameaccuracy.
Checktheoperationoftapchangerincompletealarmincludingthe
flagrelaybywindingtheunitbyhandhalfwaythroughatap
change.
Checkthetapchangercounteroperatescorrectlyandrecordthe
readings.
Checktheremoteindicationandcontrolfacilityisprovedtothe
outgoingterminalsofthemarshallingkiosk.
Checktheoutofsteprelayoperationbymovingonetapchangerin
thethreephasebanktoonepositionoutofstepwithothertwo.The
tapchangerfaultyalarmshouldcome.Repeatforothertwophases.

Operational checks on Cooler
Cooler Control Switch
Auto control from WTI
Time delay for pump
Pump failure alarm
Auto start of standby pump
Stand pump indication
Cooler fail alarm
Fuse rating correct
Differential pressure alarm

VIBRATION MEASUREMENT ON
SHUNT REACTOR
Purpose
Tomeasurethevibrationsofcore/coilassemblyinthetankof
thereactor.Movementofcor-coilassemblyandshielding
structurecausedbythetimevaryingmagneticforcesresultsin
vibrationofthetankandancilliaryequipment
Testingmethod
Minimumno.ofreadingsrequiredshallbe48.
EachofthefoursidesoftheSRtankshallbedividedinto12
rectangularareasofapproximatelythesamesize.Theseareas
aresuitablymarkedandnumberedforreference.Vibration
readingsaremeasuredatthesepointsandrecorded.
Evaluationoftestresults
Theaverageamplitudeofalllocalmax.pointsshallnotexceed
60µm.Themax.amplitudewithinanyrectangularareashallnot
exceed200µm.

Protection & Alarm checks
Check for correct operation of protection by sorting contacts at MB / relay and
appearance of alarm at control panel in C.R.:
Buchholz relay/ OSR of Main tank / OLTC
WTI/ OTI
PRD
Low oil level in conservator
Tap change incomplete
Cooler fan/ pump fail

CORE ISOLATION TEST
Purpose
Thistestisrecommendedbeforetheunitisplacedinserviceor
followingmodificationstothetransformerthatcouldaffecttheintegrity
ofitscoreinsulationandatothertimesduringamajorinspection.
Testingprocedure
ThegroundconnectionterminalsfortheX’merorreactoractivepartare
locatedinabox.
Theterminalboxcontainsaterminalblockwiththreeterminals.
CL–connectedtocorelaminations
CC–connectedtocoreclamps
G–connectedtoground(thetank)
Forcoreinsulationgroundtest,disconnecttheclosinglinkthat
connectsthetwoterminalsCL-G.Apply2.5KVdirectvoltagebetween
CLandCC+G.Thetankshallbegroundedduringthetest.
Theinsulationvalueafter1minutetesttimeshallbeminimum100M-
ohmsforservicetransformersandmorethan1000M-ohmsfornew
transformers.

DGA & Oil parameters tests
OIL SAMPLE TO BE TAKEN FOR DGA AS PER
FOLLOWING FREQUENCY
BEFORE COMMISSIONING
24 HOURS AFTER 1ST CHARGING
15 DAYS AFTER 1ST CHARGING
ONE MONTH AFTER 1ST CHARGING
3 MONTHS AFTER 1ST CHARGING
THEREAFTER EVERY SIX MONTHS

Oil Parameters before energisation
Prior to energisation of transformer, the oil sample
shall be tested for following properties & acceptance
norms:
1.BDV (kV rms)-60 kV (Min.)
2.Moisture content -15 ppm (Max.)
3.Tan delta at 90 ºC-0.05 (Max.)
4.Resisitivity at 90 ºC-1*10-cm (Min.)
5.Interfacial Tension-0.03 N/m (Min.)