Installation & Service Manual
PARALLEL COMPRESSORS
& ENVIROGUARD
June, 2007 Defrost Control Strategies /12-5
Hot Gas Defrost Requirements Chart
CASE DATA HOT GAS DEFROST
DISCHARGE EPR DEFROSTS FAILSAFE TERM. FAN
AIR TEMP SETTINGS PER TIME TEMP CYCLE
MODEL (°F) R-22 R404A DAY (MIN.) (°F) TEMPS.
NCSX, NCSGX -25 3 8 1 25-30 55 ----
NCNX
, NCNGX, -25 3 8 1 25-30 55 ----
NCBX, NCEX
NCJCX, NCJECX, -25 3 8 1 25-30 55 ----
NCJGCX, NCJGECX
NTJCX, NTJGCX -25/-15 3 8 1 25-30 55 ----
(DUAL TEMP) 7 14 2-3 20-25 55 ----
NCWX -25 3 8 1 25-30 55 ----
NMF, NMFG -15 7 14 2 16-20 55 ----
NFX, NFSX, NFSGX -15 7 14 2-3 25-30 55 ----
NFNX, NFNGX,
NFBX, NFBGX, -15 7 14 2-3 25-30 55 ----
NFEX, NEGEX
NFJCX, NFJGCX, -15 7 14 2-3 20-25 55 ----
NFJECX, NFGECX
NFMJCX, NFMJGCX -15/+22 7 14 2-3 20-25 55 ----
(DUAL TEMP) 37 50 2-3 16-20 55 50/40
NFWX, NFWGX, -15 7 14 2-3 20-25 55 ----
NFWEX
N6F, N6FL -10 10 17 3-4 22-25 60 60/40*
P5FG, P5FGN
(ANTHONY 101/) -8 19 27 1 20-25 55 25/10
(ELIMINAATOR) -8 12 19 1 20-25 55 25/10
NFL -5 13 21 2 17-20 55 ----
P5FG, P5FGN
(101/E2 withHEAT) +1 18 26 1 18-20 55 25/10
(ELIMINAATOR) +1 17 25.5 1 18-20 55 25/10
NFX, NFSX, NFSGX, +22 38 50 2-3 16-20 55 50/40
NFNX, NFNGX
NFBX, NFBGX, +22 38 50 2-3 16-20 55 50/40
NFEX, NFGEX
NFJCX, NFJGCX +22 38 50 2-3 16-20 55 50/40
NFJECX, NFJGECX
NFWX, NFWGX, +22 38 50 2-3 16-20 55 50/40
NFWEX
N3MGE +23 38 50 6 12-15 55 ----
N6F, N6FL
(MEAT) +24 38 50 3-4 22-25 60 60/40*
N2PSE
(MEAT/DELI) +24 38 49 6 12-15 55 ----
N3MG, N3HM, N3HMG +27 38 50 6 12-15 55 50/40
NSSD +27 38 50 6 12-15 55 50/40
NM, NMG +28 38 50 4 12-15 55 50/40
N5MG +28 38 50 6 12-15 55 50/40
* Primary Fans Only