Unit 1 Power System Stability

10,803 views 59 slides Aug 20, 2020
Slide 1
Slide 1 of 59
Slide 1
1
Slide 2
2
Slide 3
3
Slide 4
4
Slide 5
5
Slide 6
6
Slide 7
7
Slide 8
8
Slide 9
9
Slide 10
10
Slide 11
11
Slide 12
12
Slide 13
13
Slide 14
14
Slide 15
15
Slide 16
16
Slide 17
17
Slide 18
18
Slide 19
19
Slide 20
20
Slide 21
21
Slide 22
22
Slide 23
23
Slide 24
24
Slide 25
25
Slide 26
26
Slide 27
27
Slide 28
28
Slide 29
29
Slide 30
30
Slide 31
31
Slide 32
32
Slide 33
33
Slide 34
34
Slide 35
35
Slide 36
36
Slide 37
37
Slide 38
38
Slide 39
39
Slide 40
40
Slide 41
41
Slide 42
42
Slide 43
43
Slide 44
44
Slide 45
45
Slide 46
46
Slide 47
47
Slide 48
48
Slide 49
49
Slide 50
50
Slide 51
51
Slide 52
52
Slide 53
53
Slide 54
54
Slide 55
55
Slide 56
56
Slide 57
57
Slide 58
58
Slide 59
59

About This Presentation

Unit No-1 Subject-PSOC
Power System Stability
Class-BE
Electrical Engineering
SPPU


Slide Content

DEPARTMENT OF ELECTRICAL ENGINEERING JSPMS BHIVARABAI SAWANT INSTITUTE OF TECHNOLOGY AND RESEARCH , WAGHOLI, PUNE A.Y. 2020-21 (SEM-I) Class: B.E. Subject: Power System Operation Control Unit No-1: Power System Stability Prepared by Prof. S. D. Gadekar [email protected] Mob. No-9130827661

Content Introduction Classification of Power System States Power System Stability Dynamics of Synchronous Machines Synchronous Machines Swing Equation Power Angle Equation and Power Angle Curve Numerical of Steady State Stability Limit Equal Area Criteria Applications of equal area criteria Sudden change in mechanical input power Effect of clearing time on stability and Numerical Sudden Short circuit on one of parallel lines and Numerical Numerical Solution of Swing Equation Methods to Improve Steady State Stability Limit and Transient Stability Limit

Introduction to Power System Stability Modern power system is a complex non linear interconnected network. It consists of inter connected transmission lines, generating plants transformers and a variety of loads. With the increase in power demand nowadays some transmission lines are more loaded than their normal limits. With the increased loading of long transmission lines, the problem of transient stability has become a serious limiting factor .

Classification of Power System States The power system is a highly nonlinear system that operates in a constantly changing environment; loads, generator outputs and key operating parameters change continually . When subjected to a disturbance, the stability of the system depends on the initial operating condition as well as the nature of the disturbance. Stability of an electric power system is thus a property of the system motion around an equilibrium set, i.e., the initial operating condition . Steady state Dynamic state Transient state Power system states

POWER SYSTEM STATES STEADY STATE In an interconnected power system, the rotors of each synchronous machine in the system rotate at the same average electrical speed. The power delivered by the generator to the power system is equal to the mechanical power applied by the prime mover, neglecting losses. During steady state operation, the electrical power out balances the mechanical power in.

POWER SYSTEM STATES DYNAMIC STATE Dynamic instability is more probable than steady state stability. Small disturbances are continually occurring in a power system (variations in loadings, changes in turbine speeds, etc.) which are small enough not to cause the system to lose synchronism but do excite the system into the state of natural oscillations. In a dynamically unstable system, the oscillation amplitude is large and these persist for a long time (i.e., the system is under damped ).

POWER SYSTEM STATES TRANSIENT STATE For a large disturbance, changes in angular differences may be so large as to cause the machines to fall out of step. This type of instability is known as transient stability and is a fast phenomenon usually occurring within 1sec for a generator close to the cause of disturbance .

POWER SYSTEM STABILITY STEADY STATE STABILITY DYNAMIC STABILITY TRANSIENT STABILITY VOLTAGE STABILITY Small- signal stability is the ability of the system to return to a normal operating state following a small disturbance Dynamic stability refers to the ability of a power system subject to a relatively small and sudden disturbance Transient stability is the ability of power system to maintain synchronism when it is suddenly subjected to a severe transient disturbance Voltage stability is concerned with the ability of a power system to maintain steady acceptable voltages at all buses

Transient stability is the ability of the power grid system to maintain synchronism when subjected to severe disturbances . Transient stability analysis is considered with large disturbances like : Suddenly change in load. Generation or transmission system configuration due to fault. Switching. TRANSIENT STABILITY

It is the ability of the system to remain in synchronism when subjected to a disturbance. The rotor angle of a generator depends on the balance between the electromagnetic torque due to the generator electrical power output and mechanical torque due to the input mechanical power through a prime mover. Remaining in synchronism means that all the generators electromagnetic torque is exactly balanced by the mechanical torque. If in some generator the balance between electromagnetic and mechanical torque is disturbed, due to disturbances in the system, then this will lead to oscillations in the rotor angle. Rotor angle stability is further classified into small disturbance angle stability and large disturbance angle stability. Rotor Angle Stability

Voltage Stability Definition By IEEE: “Voltage stability refer to the ability of power system to maintain steady voltages at all buses in the system after being subjected to a disturbance from a given initial operating point. The system state enters the voltage instability region when a disturbance or an increase in load demand or alteration in system state results in an uncontrollable and continuous drop in system voltage.” Voltage Stability

Dynamics of Synchronous Machine The kinetic energy of the rotor at synchronous machine is, Where, J=rotor moment of inertia in =rotor speed in radian (mechanical)/second But rotor speed in radian (electrical)/second Where P is no of machine poles. Where, GH , Where G is machine rating in MVA and H is inertia constant in MJ/MVA  

Synchronous Machine Swing Equation Under normal operating conditions, the relative position of the rotor axis and the resultant magnetic field axis is fixed. The angle between the two is known as the power angle or torque angle. During any disturbance, the rotor decelerates or accelerates with respect to the synchronously rotating air gap mmf, creating relative motion. The equation describing the relative motion is known as the swing equation, which is a non-linear second order differential equation that describes the swing of the rotor of synchronous machine . Generator         Motor            

A synchronous generator is driven by a prime mover. The equation governing the rotor motion is given by: …….1 where J is the total moment of inertia of the rotor mass in kgm 2 T m is the mechanical torque supplied by the prime mover in N-m T e is the electrical torque output of the alternator in N-m  m is the angular position of the rotor in rad (Mechanical) Multiply equation 1 by then equation 1 becomes ………2 ……….3 Where is the angle in radian (Electrical).   Generator          

……….3 The above equation we can rewrite as, ………5 Rotor angular displacement from synchronously rotating frame called as torque angle or power angle. ……...6 Thus equation 4 becomes ………7 The above equation is called as swing equation of synchronous alternator.  

Power Angle Equation and Power Angle Curve- in Pu of machine rating as base Certain assumptions are usually made Mechanical power input to the machine (Pm) remains constant during the period of electromechanical transient of interest. Rotor speed changes are insignificant. Effect of voltage regulating loop during the transient is ignored, as a consequence the generated machine emf remains constant.   Generator          

This equation is called as power angle equation. The above equation shows that the power transmitted depends upon the transfer reactance and the angle between the two voltages.   G1      

Where The curve vs is known as the power angle curve. Steady State Stability limit occurs at an angular displacement of 90 . When a generator is suddenly short –circuited the current during the transient period is limited by its transient reactance  

Power Angle Curve Generator          

Example-1 Find the steady state power limit of a power system consisting of a generator equivalent reactance 0.50 Pu connected to an infinite bus through a series reactance of 1.0 Pu. The terminal voltage of the generator is held at 1.2 Pu and the voltage of the infinite bus is 1.0 Pu. G L           + j0.5 * ……….1 ………..2    

G L           If we put equation 2 in equation 1 for + 0.5j * + 0.5j * Separating Real and Imaginary Part +j(1.8 ……..3    

G L           +j(1.8 ………3 Steady State Power Limit is reached when E has an angle of AS , here This can be written as ) Thus the real part will be zero. In t he Equation 3 equate real part to zero. =0 =73.87    

G L           In above equation put =73.87 =1.152+j0.668 PU + j0.5 * ……….1 Similarly In above equation put =73.87 & =1.152+j0.668 Amp =1.728 Steady State Power Limit is given by =1.152 PU    

G L           If instead, the generator emf is held fixed at a value of 1.2 PU, the steady state power limit would be, = 0.8 PU Conclusion- When =1.152 PU And if =0.8 PU It is observed that regulating the generator emf to hold the terminal generator voltage at 1.2 PU raises the Power Limit from 0.8 to 1.152 PU.    

Equal Area Criteria If the system is unstable continues to increase indefinitely with time and the machine loses the synchronism. On the other hand if the system is stable performs oscillations whose amplitude decreases in actual practice because of damping terms.     t Unstable   Stable  

Consider the swing equation ……..1 Where is accelerating power and M   Now multiply both side by to equation 1 Integrating both sides System is stable if  

The condition of stability can therefore be stated as, the system is stable if the area under curve reduces to zero at the same value of . In other words, the positive (accelerating) area under curve must be equal to negative (decelerating) area and hence the name ‘equal area criteria’ of stability.  

Applications of Equal Area Criteria i) Sudden change in mechanical Input Consider the transient model of a single machine tied to infinite bus bar as shown in fig. Generator           G             The electrical power transmitted is given by  

              Under Steady State operating condition The initial operating point is given by point “a”. As mechanical input power is increased from to .         Generator               A1 --- Pm1> Pe ----Rotor Accelerates A2 --- Pm1< Pe ----Rotor decelerates

                        By equal area criteria the system is stable under sudden change in input mechanical power only when,  

Applications of Equal Area Criteria ii) Effect of clearing time on stability A generator is connected to an infinite bus bar through two parallel lines. Assume that input power Pm is constant and the machine is delivering power to the system with a power angle . A temporary three phase fault occurs at the sending end of the bus 1.       G     Bus 1 Bus 2 Three Phase Fault During the fault at sending end of the line, no power is transmitted to the infinite bus and is zero.  

                              A1 --- Pm> Pe ----Rotor Accelerates Here Pe is zero due to three phase fault A2 --- Pm< Pe ----Rotor decelerates   ∏  

                            Critical Clearing Angle “ - The critical clearing angle is reached when any further increase in to become less than the area representing accelerating energy. Critical Clearing Time “ – The maximum allowable value of the clearing time is called the critical clearing time.  

Critical Clearing Angle “ – Applying equal area criteria to the figure as shown. A1=A2 Using integration we can find out the areas.  

Critical Clearing Time “ – For this case the electrical power during fault is zero, the swing equation becomes Integrating both side w.r.t. time Again Integrating both side w.r.t. time and applying limits of  

Example-2 A 60 Hz synchronous generator having inertia constant H=5 MJ/MVA and direct axis transient reactance is connected to an infinite bus through a purely reactive circuit as shown in fig. Reactance are marked on the diagram on a common system base. The generator is delivering real power and to the infinite bus at a voltage of V=1 PU. A temporary three phase fault occurs at the sending end of the line at point F. When the fault is cleared both lines are intact. Determine the critical clearing angle and the critical fault clearing time.       G     Bus 1 Bus 2 Three Phase Fault =0.3        

The Internal Voltage of Generator is given by The transfer voltage of Internal Voltage of Generator and the infinite bus is given as, + + The total complex power delivered by generator is given by ( = Using equation 1,2 and 3  

Case-1 A temporary three phase fault occurs at the sending end of the line at point F. When the fault is cleared both lines are intact. Determine the critical clearing angle and the critical fault clearing time. Since both lines are intact when the fault is cleared, the power angle equation before and after the fault is The initial operating power angle is and corresponding =   Critical Clearing Angle-  

Critical Clearing Time-  

Applications of Equal Area Criteria iii) Sudden Short circuit on one of parallel lines Case 1-Short circuit at one end of line A generator is connected to an infinite bus bar through two parallel lines. Assume that input power Pm is constant and generator is operating at . A temporary three phase fault occurs at the generator end of the line. Thus at the instant of fault CB-0 operates and isolates the generator during fault, Power flow during the fault is zero. After time the circuit breaker at faulted lines operates and isolates the faulted line and power flow restores through healthy line.       G   Bus 1 Bus 2       CB1 CB2 CB0 CB3 CB4 CB5   The electrical power delivered by generator before fault occurs is given by  

                            ∏       G   Bus 1 Bus 2 Three Phase Fault       CB1 CB3 CB5   CB0   A1 --- Pm> Pe ----Rotor Accelerates Here Pe is zero due to three phase fault       f   CB0 CB4 CB2 A2 --- Pm< Pe ----Rotor decelerates   =0  

Applications of Equal Area Criteria iii) Sudden Short circuit on one of parallel lines Case 2-Short circuit away from line ends A generator is connected to an infinite bus bar through two parallel lines. Assume that input power Pm is constant and generator is operating at . When the fault occurs away from line ends, there is some power flow during the fault. After time the circuit breaker at faulted lines operates and isolates the faulted line and power flow restores through healthy line .   The electrical power delivered by generator before fault occurs is given by  

                            ∏       G   Bus 1 Bus 2 Three Phase Fault       CB1 CB3 CB5   CB0   A1 --- Pm> Pe ----Rotor Accelerates Here Pe is not zero during the fault.       f   CB4 CB2 A2 --- Pm< Pe ----Rotor decelerates   =    

Applications of Equal Area Criteria iii) Sudden Short circuit on one of parallel lines Case 3-Reclosure A generator is connected to an infinite bus bar through two parallel lines. Assume that input power Pm is constant and generator is operating at . When the fault occurs away from line ends, there is some power flow during the fault. After time the circuit breaker at faulted lines operates and isolates the faulted line and power flow restores through healthy line . Now if the circuit breaker of line 2 are reclosed successfully, i. e. the fault was a transient one and therefore vanished, The power flow is again restored using both lines.   The electrical power delivered by generator before fault occurs is given by  

                            ∏       G   Bus 1 Bus 2 Three Phase Fault       CB1 CB3 CB5   CB0   A1 --- Pm> Pe ----Rotor Accelerates Here Pe is not zero during the fault.       f   CB4 CB2 A2 --- Pm< Pe ----Rotor decelerates   =     CB2 CB4  

Example-2 A 60 Hz synchronous generator having inertia constant H=5 MJ/MVA and direct axis transient reactance is connected to an infinite bus through a purely reactive circuit as shown in fig. Reactance are marked on the diagram on a common system base. The generator is delivering real power and to the infinite bus at a voltage of V=1 PU. A temporary three phase fault occurs at the sending end of the line at point F. When the fault is cleared both lines are intact. Determine the critical clearing angle and the critical fault clearing time. A three phase fault occurs at the middle of one of the lines the fault is cleared, and the faulted line is isolated. Determine the critical clearing angle.       G     Bus 1 Bus 2 Three Phase Fault =0.3        

Critical Clearing Angle-  

Step 1-Before Fault occurs The Internal Voltage of Generator is given by The transfer voltage of Internal Voltage of Generator and the infinite bus is given as, + + The total complex power delivered by generator is given by ( = Using equation 1,2 and 3  

The initial operating power angle is and corresponding =  

Step 2-During Fault During fault the generator delivers some amount of power to infinite bus. As The equivalent circuit can be draw by referring above mentioned single diagram,       G   Three Phase Fault = 0.3 + 0.2      

    Three Phase Fault X=0.5     G         =0.5   Convert this star in to Delta 1 2 3 N 1 2 3 N Similarly  

    Three Phase Fault     G        

Step 3-After Fault When the fault is cleared, the faulted line is isolated from the system as shown below. The transfer reactance in step 3 is given as, + + =0.3+0.2+0.3 =0.8 PU = 33.17 =146.83  

Critical Clearing Angle-  

Example-3 A 50 Hz, Four Pole turbo generator rated 100 MVA, 11kV has an inertia constant of 8.0 MJ/MVA. Find the stored energy in the rotor at synchronous speed. If the mechanical input is suddenly raised to 80 MW for an electrical load of 50 MW, find the rotor acceleration, neglecting mechanical and electrical losses. If the acceleration calculated in part (b) is maintained for 10 cycles, find the changes in torque angle and rotor speed in revolutions per minute at the end of this period. a. Stored Kinetic Energy- GH , Where G is machine rating in MVA and H is inertia constant in MJ/MVA Stored Energy=100*8 =800 MJ  

Example-3 A 50 Hz, Four Pole turbo generator rated 100 MVA, 11kV has an inertia constant of 8.0 MJ/MVA. Find the stored energy in the rotor at synchronous speed. If the mechanical input is suddenly raised to 80 MW for an electrical load of 50 MW, find the rotor acceleration, neglecting mechanical and electrical losses. If the acceleration calculated in part (b) is maintained for 10 cycles, find the changes in torque angle and rotor speed in revolutions per minute at the end of this period. Generator           b. Swing Equation is given as, Where M=  

Methods to Improve Steady State and Transient Stability Limit G1       The Power Angle equation is given as, Steady State Stability limit occurs at The Steady State Stability limit can be increased by reducing and increasing either or both . If the transmission lines are of sufficiently high reactance, the stability limit can be increased by using two parallel lines which incidentally also increases the reliability of the system.  

Methods to Improve Steady State and Transient Stability Limit The Power Angle equation is given as, Series capacitor are sometimes employed in lines to get better voltage regulation and to raise the stability limit by decreasing the line reactance. Some time excitation voltages and quick excitation system are also employed to improve the stability limit. Use of high speed reclosing circuit breaker.  

Numerical Solution of Swing Equation The critical clearing time can not be obtained from equal area criteria and we have to make this calculation numerically through swing equation. If more than one machine is connected to the infinite bus bar then solving the swing equation will become very complicated task. The point by point method for one machine tied to infinite bus bar gives the solution of the swing equation . This method can be applied to every machine of a multi machine system.