Fire hazard of Banani Club No existing professional Fire Alarm System No proper fire Escape Stairways Present Fire Extinguishers are only for superficial Fire , We need proper fire protection ,water supply/Hydrant system The greatest fire risk is the existing Haphazardly placed LPG Cylinders in the Kitchens.
Assessing the risks of having too many LPG cylinders , Cylinders on the ground floor . Presently 7 active Cylinders + 2 stock/backup Cylinders The 6th floor has 2 active Cylinders + 1 stock/backup
. .Most of the gas cable( yellow cables) are lying in the ground and getting stomped by workers, posing a gas leak threat. This all can be reduced to a Cylinder Bank in a safe distance away and backup Cylinders. Proper planning and use of ' Regulator ' will reduce wastage. And proper positioning of the Cylinders, with a planned " Reticulation “ will make the whole process , safe and efficient.
Ground Floor Kitchen LPG Cylinder Locations 3 LPG cylinders , 2 Active one backup at the corner or the entrance. Pls notice the cables lying on the floor
Pls give attention to the cables on the floor
2 LPG Cylinders kept near the Service Elevator,
LPG Cylinders are often kept in the middle of the room
LPG cylinder in the cutting section, connected to the Bangla stove
This is the passage behind the kitchen, The LPG cylinder is connected to the Muglai Stoves , and one kept as backup
6 th Floor : 2 Active Cylinders and 1 Backup This is the LPG cable connecting to one of those cylinders to the stoves: this is lying on the floor prone to damages.
. Burner Layout Plan of the Kitchen, showing the Present LPG Cylinder positions. Building Setback Area. Entry Active LPG Cylinder Burners Backup LPG Cylinder
Proposed LPG Cylinder Area. Burner Proposed Relocation of LPG cylinder Building Setback Area. Entry
Presently we are using Domestic LPG Model. From which we have to go to Commercial LPG Reticulation (Distribution)Design. DOMESTIC/CONVENTIONAL LPG SYSTEM
CONVENTIONAL VS RETICULATED SYSTEM
Commercial LPG CYLINDER INSTALLATION Design
Conclusion: LPG cylinders should be immediately moved out to a suitable and safe location. Reticulated system should be installed. Consultant should be appointed for , Fire Escape Design Fire safety Installation option assessment Fire Alarm system design