2. Self-wt of S = 5/12 150 = 62.5 psf, and of FS = 7/12 150 = 87.5 psf
Factored load on S = 1.4 (62.5 + 30 + 40) + 1.7(50) = 270.5 psf
and on FS = 1.4 (87.5 + 30 + 40) + 1.7(50) = 305.5 psf
Factored load from beam and wall = 1.4 {(1211)/144 150 + (5/12(1016/12) 120} = 1.4570.8 = 799.2 lb/ft
Factored load from FS wall = 1.4 {(5/12(107/12) 120} = 1.4470.8 = 659.2 lb/ft
Column Load per floor = [{270.5 1010 + 305.5 (2020100)} + 799.2 20 + 659.2 20)] lb = 147.87 k
Total Load on column C1 = 6 147.87 = 887 k
(i) Assuming 3% reinforcement, Pu = 0.85fc (1g) + g fy}Ag
887 = 0.8 0.7 {3.40 0.97 + 0.03 60}Ag Ag = 310.8 in
2
; i.e., Assume 20-dia column
(ii) (a) Working floor loads are (62.5 + 30 + 40 + 50) = 182.5 psf and (87.5 + 30 + 40 + 50) = 207.5 psf
Working load from beam and wall = 570.8 lb/ft, Working load from FS wall = 470.8 lb/ft
Column Load per floor = 182.5 1010 + 207.5 (2020100) + 570.8 20 + 470.8 20 lb = 101.33 k
Total Load on footing = 6 101.33 = 608 k
Assuming 4-depth of footing (optional), allowable bearing capacity = 4 3 0.11 1 0.15 = 3.52 ksf
Required footing size = 608/3.52 = 172.73 ft
2
; i.e. (13.5 13.5)
Net soil pressure = 887/(13.5 13.5) = 4.87 ksf
(b) Punching shear force = 887 4.87 /4(20+d)
2
/12
2
= 887 0.0266(20+d)
2
, and Area = (20+d)d
887 0.0266 (20+d)
2
= (20+d)d 4 0.85(3/1000) dreq = 28.84
Beam shear force = 4.87 {(13.520/12)/228.9/12} = 26.40 k, and Area = 12 28.84 = 346.1 in
2
Beam shear stress = 26.40/346.1 = 0.076 ksi; which is 2 0.85(3/1000) = 0.093 ksi OK
Maximum bending moment Mu(max) = 4.87 {(13.5 20/12)/2}
2
/2 = 85.21 k-ft/ft
max = 0.75 87/(87 + fy) fc /fy = 0.75 87/(87 + 60) 0.72 4/60 = 0.0213
Ru = max fy (10.59 max fy /fc) = 0.90 0.0213 60 (10.59 0.0213 60/4) = 0.934 ksi
dreq = (Mu/Ru) = (85.21/0.934) = 9.55
Choose d = 29.0; i.e., t = 29.0 + 3.5 = 32.5
3. Working load P = 120 k (i.e., 60 + 60); Ultimate load Pu = 1.4 60 + 1.7 60 = 186 k
Net soil pressure = 186/(6 10) = 3.10 ksf
(i) For the wall footing, Maximum bending moment Mu(max) = 3.10 {(6 10/12)/2}
2
/2 = 10.34 k-ft/ft
Also d = 9 2.5 = 6.5, As = 0.85fc/fy[1(1 2Mn/(0.85fcbd
2
)]bd
= (3.4/60) [1(1 2 10.34/(3.4 6.5
2
)] 12 6.5 = 0.33 in
2
/ft
while As(temp) = 0.036t = 0.036 9 = 0.32 in
2
/ft
(ii) For the column footing, Maximum bending moments are
Mu1(max) = 3.10 {(6 12/12)/2}
2
/2 = 9.69 k-ft/ft, with d = 14 3.5 = 10.5
As1 = (3.4/60) [1(12 9.69/(3.410.5
2
)]12 10.5 = 0.19 in
2
/ft, while As(temp) = 0.036 14 = 0.50 in
2
/ft
and Mu2(max) = 3.10 {(10 12/12)/2}
2
/2 = 31.69 k-ft/ft, with d = 14 2.5 = 11.5
As2 = (3.4/60) [1(12 31.39/(3.4 11.5
2
)] 12 11.5 = 0.57 in
2
/ft
6
12
6
10
(12 12) Column 10-thick Wall
9
14
#5@11 c/c
#5@11 c/c
#
[email protected] c/c
#
[email protected] c/c